Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance CW 545 SANJAY GANDHI TRANSPORT NAGAR NEW DELHI 110042 | NORTH | DELHI | 110042 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance PROP NO A 80 FIRST FLOOR FLAT NO 3 CHATTAR PUR ENCLAVE PHASE 2 NEW DELHI SOUTH WEST DELHI DELHI 110074 | SOUTH DELHI | DELHI | 110074 | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹9,400
Closing Date
18 Feb 2025, 11:30 amClosed
EE(EnM) M-4 Mukherjee Nagar
EE(EnM) M-4 Mukherjee Nagar
Dehydration and Transformer oil Top-up of 1000 KVA Transformer No. 2 installed at Burari Authority BPS.
2025_DJB_268399_1
NIT No. 15 item No. 4 (24-25) EE (T)/EE(EnM)M-4
Open Tender
Miscellaneous Works
Works
30 days
EE(EnM) M-4 Mukherjee Nagar
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Online
₹9,400
28 Feb 2025
11 Feb 2025
18 Feb 2025
11 Feb 2025
18 Feb 2025
11 Feb 2025
Disconnecting of HT Supply from main HT panel after proper switching off 11 KV VCB & discharging the supply. Complete drain out of transformer oil from transformer to empty oil drum by oil machine and dismantling of conservator tank all protection relays cable end boxes, vent pipes & other items as required. DJB SOR 6.1.1
Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and re- installation of weak point with the help of HT insulation material and proper taping etc. DJB SOR 6.1.2
Replacement of Top Cover gasket vertical vent gasket & missing hardware to stop the oil leakage DJB SOR 6.1.3
Replacement of silica gel DOB SOR 6.1.4
Checking & matching of control wiring of all protection 5 relays and calibration of buchholz relay and protection relays testing the same. DJB SOR 6.1.5
Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides HI pot machine. DOB SOR 6.1.6
Filling of transformer oil to up to top up level as required. Make – Power DOB SOR 6.1.7
P/F of winding protection pad. DOB SOR 6.1.8
Repair of cooling fins, replacement of cooling fins gasket and oil seal for stopping the leakage. DJB SOR 6.1.9
Dehydration & filtration of complete transformer oil &and checking the die electric strength up to 50 KV at Site as required. DJB SOR 6.1.10
Complete cleaning and chemically washing of the oily and muddy transformer body and painting of the transformer with enamel paint. 6.1.11
M/s AADRIKA ASSOCIATES (BID ID -1563433)
NEW INDIA ELECTRICALS (BID ID -1563733)
Devraj Enterprises (BID ID -1563711)
GOGIA BROTHERS (BID ID -1563449)
Gupta Brothers (BID ID -1563693)
M G Traders and Engineers (BID ID -1563673)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .