Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.2 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹11.4 L+₹1.2 L (11.3%)Rejected-Finance | L2 | Rejected-Finance L1 being accepted | |
| 3 | L3₹11.6 L+₹1.4 L (13.6%)Rejected-Finance | L3 | Rejected-Finance L1 being accepted | |
| 4 | L4₹11.8 L+₹1.5 L (14.9%)Rejected-Finance | L4 | Rejected-Finance L1 being accepted | |
| 5 | L5₹11.8 L+₹1.5 L (15.0%)Rejected-Finance | L5 | Rejected-Finance L1 being accepted |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
15 Feb 2020, 6:00 pmClosed
GE 867 EWS
GE 867 EWS C/O 99 APO PIN 913867
REPAIRS/MAINTENANCE OF DG SETS AT PEDONG, ALGARAH, DALAPCHAND, AP ALGARAH AND TEESTA TCP UNDER GE 867 EWS
2020_MES_311723_2
CA NO GE / 867 / TOKEN / 35 OF 2019-2020
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Pedong
Refer tender documents
8 documents required · 8 mandatory
₹500
GE 867 EWS
₹20,000
Yes
27 Feb 2020
1 Feb 2020
17 Feb 2020
1 Feb 2020
15 Feb 2020
8 Feb 2020
1 Feb 2020 - 5 Feb 2020
Amount
M&L for servicing of diesel engine at site Make:-Kirloskar 82.5 KVA water cooled engine,for overhauling tuningup and gresing to all .movable parts, repair/replacement of old unserviceable accessories/parts with new accessories/parts, including draining of complete engine oil and washing the internal engine with kerosene oil and refilling new engine oil of required quantity all as specified and directed by the Engineer -In-Charge. Note:-Quoted rate shall be deemed to include for lub oil filter, fuel filter and Engine oil of required quantity.
M&L for servicing of diesel engine at site Make:-Greaves 82.5 KVA water cooled engine,for overhauling tuningup and gresing to all .movable parts, repair/replacement of old unserviceable accessories/parts with new accessories/parts, including draining of complete engine oil and washing the internal engine with kerosene oil and refilling new engine oil of required quantity all as specified and directed by the Engineer -In-Charge. Note:-Quoted rate shall be deemed to include for lub oil filter, fuel filter and Engine oil of required quantity.
M&L for servicing of diesel engine at site Make:-Greaves 45 KVA water cooled engine,for overhauling tuningup and gresing to all .movable parts, repair/replacement of old unserviceable accessories/parts with new accessories/parts, including draining of complete engine oil and washing the internal engine with kerosene oil and refilling new engine oil of required quantity all as specified and directed by the Engineer -In-Charge. Note:-Quoted rate shall be deemed to include for lub oil filter, fuel filter and Engine oil of required quantity.
M&L for servicing of diesel engine at site Make:-Kirloskar 15 KVA water cooled engine,for overhauling tuningup and gresing to all .movable parts, repair/replacement of old unserviceable accessories/parts with new accessories/parts, including draining of complete engine oil and washing the internal engine with kerosene oil and refilling new engine oil of required quantity all as specified and directed by the Engineer -In-Charge. Note:-Quoted rate shall be deemed to include for lub oil filter, fuel filter and Engine oil of required quantity.
Supply only new engine oil 30 W 50 all as specified and directed by the Engineer -In-Charge Make: Servo/Castrol
Supply only Air filter element all as specified and directed by the Engineer -In-Charge
S & F four pole onload changeover 200 Amp with advance neutral onload changeover SS Enclosure type incl taking down existing unserviceable changeover complete all as specified and directed by the Engineer -In-Charge Make : Havells /L&T/Indoasian/HPL
Earhing complete with galvanized steel earth plate electrode 600X600X6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to GI earth strip of size 32x6mm, by means of galvanized iron or steel bolts, nuts, check nuts and washers, and conneced to equipments as directed, including funnel with GI med grade watering pipe 20 mm bore, wire mesh charcoal or coke and common salt in alternate layers, of 15 cm compacted thickness all around the earth electrode, with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1:2:4 type B1 cover slab reinforced with 8 mm dia reinforced bar 15 cm C/C and earth lead handle protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc.50m and necessary testing complete all as shown on electrical plate No.3 of MES SSR Part I including taking out existing earthing complete all as specified and as directed by Engineer-in-charge. NOTE: Rate quoted shall be deemed to include for GI earth strip upto 7.5m.
M&L for MCCB 4 Pole 200 Amp breaking capacity 50 KA, 415 Volts, 50 Hz, AC complete all as specified and directed by the Engineer -In-Charge. MAKE: Legrand cat No 420278 or equivalent in Schneider/Seimens/L&T.
M&L for MCCB 3 Pole of 200 Amps, 50Amp , 415 Volts, 50 Hz, AC complete all as specified and directed by the Engineer -In-Charge. MAKE: Legrand cat No 420268 or equivalent in Schneider/Seimens/L&T.
M&L for motor control consol for 50 HP pump set consisting of fully automatic star delta starter of minimum capacity 60 HP air greak type, 3 phase 415 volts, overload relay, single phase preventer, digital type ammeter 0 to 200 Amp, on / off push button, indicator for on/off duly wired with suitable PVC insulated copper conductor complete all as specified and directed by Engineer-in-charge. MAKE: Cat No. MS23AI27 of Schneider or equivalent of Seimens/L&T/Legrand
Supply laying and testing cable PVC insulated PVC sheated electric cables (heavy duty) 1100 Volts grade with stranded copper conductor of cross Sectional area 35 Sqmm single core conforming to IS- 694 drawn in and including suitable size medium grade rigid PVC conduit fixed on walls floors etc., complete including taking down existing cable all as specified and directed by Engineer-in-Charge. Make: (i) Finolex, (ii) Plaza, (iii) Havells, (iv) Polycab, (v) KEI, (vi) Anchor or equivalent as approved by GE.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. Note:- Excavation, earth work, brick protection, protection pipe and sand coushioning shall be measured and paid separately. Make of cable shall be CCI / Gloster / ICC / Unistar / NICCO / Asian (RPG) / Havells / Polycab/PRG/Universal/Plaza/Crystal cables/Terracom/ Rallison/Mescab/Jeypore/KEI
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5 in depth for taking out /laying of cable etc., and getting out in soft/loose soil.complete all as specified and directed by Engineer-in-Charge.
Returning, filling in soil, including spreading leveling, watering and wall ramming in laying not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance n.exe 50m and depositing where directed at alevel n.exe 1.5m above the starting point complete all as directed by Engineer - in -Charge.
Supply and spreading of dry sand in trenches for cable coushioning and punned down complete all as specified and directed by Engineer-in-Charge. Note:- Punned thickness only shall be measured for payment purpose.
M&L for common burnt bricks, sub class 'B', of size 250 x 125 x 75 mm laid in trenches for cable protection complete all as specified and directed by Engineer-in-charge.
Sub Total of Schedule 'A'
Schedule of Credit (Minus) Rs. 20,653.00 B/F from Ser page No. 26 NOTE: Bidder shall insert credit amount as rate Rs. 20,653.00 in Green field under Col-M. If bidder does not insert the amount the same will be deducted from total amount of Schedule 'A' and accordingly total amount of tender will be considered in deciding the lowest tender.
Sub Total of Schedule of Credit
MS BRAHMA CONSTRUCTION
RAJU TAMANG
RAMESH GURUNG
SANJAY SAW MILL
G K SUTHAR
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .