Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹12.9 L
EMD Value
₹12,900
Closing Date
27 May 2024, 5:00 pmClosed
S.E. E D C- MVVNL,Unnao
Superintending Engineer Electricity Distribution Circle-Unnao
QUANTUM OF WORKS INVOLVED IN INCREASING CAPACITY OF DISTRIBUTION TRANSFORMER/ PROVIDING NEW DISTRIBUTION TRANSFORMER DUE OVERLOADING OF EXISTING T/F AT DIFF. SITES IN BUSINESS PLAN YEAR 2024-25 UNDER THE AREA OF 33/11 KV S/S CITY POWER HOUSE AND KASI
2024_MVVNL_922840_2
364/E.D.C./Unnao/2023-24
Open Tender
Electrical Works
Fixed-rate
180 days
Unnao
AS PER TENDER DOCUMENT
2 documents required · 2 mandatory
₹3,540
A/C-No.3355002101008374,IFSC-Code-PUNB0335500
₹12,900
1 Jun 2024
21 May 2024
28 May 2024
21 May 2024
27 May 2024
21 May 2024
Amount
Safe Carriage of following materials from Elec. Store Center Unnao to work dump site along with loading unloading and propoer stocking.
Three Phase A.B. Cable of diff. size
LT PVC Cable size 1x400 sq mm
LT PVC Cable size 3.5x150 sq mm
Safe Carriage of following T/F from Elec. Store Center Unnao to diff. work dump site along with loading unloading and propoer stocking.
T/F 250 KVA 11/0.4 KV
T/F 100 KVA 11/0.4 KV
Dismantling of following Transformer by opening of H.V./L.V. connections and its removal from Plinth / Double Pole with Safe Carriage from work site to dump site along with loading unloading and propoer stocking.
T/F 100 KVA 11/0.4 KV
T/F 25 KVA 11/0.4 KV
Fixing of 11 KV D.O. Fuse Set at Double Pole with D.O. Fuse mounting Channel, clamps and nut & bolts including all associated work.
Supply & Fixing of following materials for above job-
11 KV D.O. Fuse Set
D.O. Fuse mounting Channel
Clamp for mounting Channel with N&B
Construction of masonry type T/F plinth, suitable for mounting of distribution transformer. Size of the plinth will be 1.5 mtr x 1.5 mtr x 1.5 mtr (LxBxH) solid with brick work. 75 mm thick C.C. in ratio 1:4:8 with cement, coarse sand and brick ballast laid on the base and 75 mm thick done on all the exposed sides to the plinth as per RESPO norms. (All the material will be arranged by the contractor)
Placement of 11/0.4 KV T/F from dump site to newly constructed T/Fs Plinth & installation and commissioning of 250 KVA T/F and All the jumpering & connection with the system are included in the scope of work.
Supply & Fixing of following materials for above job-
Al. Lugs for 250 KVA T/F @ 04 nos. for each T/F
Copper L-piece of appropriate size @ 04 nos. for each T/F
Insulated Lead of Single Core Al. Cable of size 25 sqmm for HT side connection @ 30 mtr for each T/F
Earthing of Neutral of Transformer & Transformer body by way of boring and lowering of ‘B’ class G.I. Pipe 1.5” dia from ground up to the water level (Minimum 40 ft. Deep) with a solid cone at the lower end of G.I. pipe. Connecting and bringing out contineous G.I. Strip size 32X5 mm. from the cone to the ground surface where it will be connected with G.I. pipe clamp from which Transformer neutral & Body connection being done by G.I. Strip as per RESPO norms . (All the material will be arranged by the contractor)
Fixing of L.T. Tailless Fuse Unit with 01 nos. I/C and 03 nos. O/G Circuit arrangement by erection & fabrication of Distribution Pillar Box Pinth and LT Distribution Pillar Box including all associated work as per RESPO Norms. (All the material will be arranged by the contractor)
Supply & Fixing of following materials for above job-
Distribution Pillar Box Pinth
Henley type tailless unit of 500 Amp @ 03 nos. for each LT Fuse Unit with fuse wire of appropriate rating
LT Distribution Pillar Box with Canopy type top along with front & back opening double door with locking arrangement made of MS Sheet
Copper bus bar of appropriate size @ 03 nos. for each LT Fuse Unit
Al. Bus bar of appropriate size @ 01 nos. for each LT Fuse Unit
Al. Lugs/Clamps of diff. sizes @ 16 nos. for each LT Fuse Unit
Painting of LT Pillar Box with 02 coat red oxide paint and 02 coat enemal red paint.
Laying of LT PVC Cable of size 1x400 sq mm from Transformer to LT Fuse Unit system including all associated work. (All the required materials for above job shall be provided by contractor except LT PVC Cable)
Fabrication and erection of Distribution Transformer fencing around Transformer and L.T. Distribution Pillar Box with frame size 3x2.4 Mtr. Including cost of M.S. Angle size 40x40x5 and M.S. Flat size 35x5, fixing of welded steel wire fabric on steel frames by welding of 10SWG wire fabric, including Painting of two coats of paint in iron based surfaces with ready mixed paint to give bus green shade including cleaning of oil & dust as per RESPO norms. (All the material will be arranged by the contractor)
Mounting of following Transformer on double pole including its cartage and dragging from dump site to pit site & installation and commissioning of T/Fs and All the jumpering & connection with the system are included in the scope of work. (All the required materials as 04 nos.-Al. Lugs for each T/F, Nut & bolts for S/S Angle etc for this job shall be provided by contractor except T/Fs and LT PVC Cable)
T/F 100 KVA
Laying of LT PVC Cable of size 3.5x150 sq mm/3.5x70 sq mm from Transformer to LT Fuse Unit system including all associated work. (All the required materials for above job shall be provided by contractor except LT PVC Cable)
Earthing as per RESPO Norms.
Laying stringing and sagging of O/H Three Phase L.T. Line by ABC of diff. size including all associated work with joint/jumpers and binding of insulator as required.
Supply & Fixing of following materials for above job-
L.T. Clamp with Nuts & Bolts
L.T. Shackle Insulator
Bolts & Nuts for Shackle
Piercing Connector
Safe Carriage of following T/F from work dump site to Electricity store center Unnao with loading, unloading and proper stocking.
T/F 100 KVA 11/0.4 KV
T/F 25 KVA 11/0.4 KV
Pankaj Trading Company
M/s PRAMENDRA SINGH
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .