GE AF THANE
Office of Military Engineer Services ,Garrison Engineer (AF) Thane, Kolshet Road, Sandoz Baugh Post, Thane 400607
REPAIR, MAINT OF SERVICE CONNCT, DISTR BOARD, BUILDING SUB MAIN, EXTERNAL WATER SUPPLY DISTRIBUTION SYSTEM, LT CABLE/ EXTERNAL ELECTRIC POWER TRANSMISSION SYSTEM, REPAIR MAINT RENEWAL OF EOT CRANE AND ALLIED WORKS AT SITE P AND R UNDER GE AF THANE
2025_MES_693108_1
8424/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
THANE
AS PER NIT
8 documents required · 8 mandatory
₹500
GE AF THANE
₹71,000
Yes
13 Mar 2025
13 Jan 2025
17 Feb 2025
13 Jan 2025
10 Feb 2025
28 Jan 2025
Amount
Periodical maintenance of electrically operated travelling (EOT) Crane of 2 Ton capacity each for 2 Nos of EOT crane, 11.5 mtrs span, 32.5 mtrs moving bay length,7 mtrs hook lift double girder pendent operated, EOT crane including 4 way LT shrouded Bus bar type DSL (Clear height above Gantry Girder is only 400 mm) Speed Hoist 4 mtr/min, LT 15 mtr/min, CT 12mtr/min Main hoist motor rating 3HP CT motor rating 1HP LT motor rating 0.5HPx2 Nos all motor of sqirrel cage crane duty motors, 40% CDF ,150 Sts/hr , power control voltage 415V , 3ph, 50Hz/110V ,1Ph,50 Hz including independent moving push button station for 11.5 mtrs, Lt cabling, painting of existing gantry & rail for 42 mtrs. including dismentling / replacing unserviceable parts with new parts at installation complete all as specified and as directed . Notes for Sl Item No. 1.01 :- (i) Contractor shall quote the rate for periodical maintenance of 2 Nos of EOT crane/per month ,nothing shall be paid extra on this account.(ii) Major Spare Parts/accessories required for rectification/maintenence of EOT shall be mesured seperately under relevent item of Sch A as a supply only ,whereas other minor Parts/accessories required for rectification/maintenence of EOT shall be deemed to be included in quoted rate,nothing extra shall be paid on this account.(iii) Contractor shall carry out necessary load testing after replacement of major parts of crane every time and cost for the same shall be deemed to be included in the quoted rates and nothing extra shall be paid on this account. However annual load testing of crane and necessary painting will be measured and paid separately under relevent item of Sch A .Note: Contractor quoted rate shall be inclusive of Periodical maintenance for 2 EOT crane/per month
M&L for annual load testing of electrically operated travelling (EOT) Crane of 2 Ton capacity each for 2 Nos of EOT crane, 11.5 mtrs span, 32.5 mtrs moving bay length,7 mtrs hook lift double girder pendent operated,including transportation of load and its necessary equipments,complete all as specified and as directed by Engr-in-charge. (i) Contractor shall quote the rate for 2 Nos of EOT crane/per Job ,nothing shall be paid extra on this account. Note : Painting of 2 Nos of EOT crane is deemed to be included in unit quoted rate
M&L for rewinding the following capactiy 3 phase electric motors for hoist motion, LT motion, CT motion of crane with copper winding wire of gauge as per existing with class 'B' insulation including dismantling ,transporting, refixing and testing on load ,complete all as specified and as directed by Engr-in-charge. for 3HP 3/6 Pole ,Sq Cage phase with 1450 RPM electric motor ,complete all as specified and as directed by Engr-in-charge.
All as per item no 3.00 above but for 1HP electric motor.
All as per item no 3 above but for 0.5HP electric motor.
S & F Wire rope of 16 mm dia ,6/36 const. Fibre core galvanised steel Make- Usha Martin or all as Approved and as directed by Engr-in-charge.
S & F Wire rope 8 mm dia 6/36 const. Fibre core galvanised steel Make- Usha Martin or all as Approved and as directed by Engr-in-charge.
Supply only Flexible copper cable 3 core ,2.5 sqmm ,PVC insulated and sheathed of 1100 volts grade multi stranded in box girder between control panel to all motors for EOT crane ,complete all as specified and as directed by Engr-in-charge.
Supply only Flexible copper cable 4 core, 4 sqmm, PVC insulated and sheathed of 1100 volts grade multi stranded in box girder between control panel to all motors for EOT crane ,complete all as specified and as directed by Engr-in-charge.
Supply only Flexible copper cable 12 core ,1.5 sqmm ,PVC insulated and sheathed of 1100 volts grade multi stranded in box girder between control panel to all motors for EOT crane ,complete all as specified and as directed by Engr-in-charge.
Supply only TP contact, 3 phase, 20 Amps with coil ,complete all as specified and as directed by Engr-in-charge. Make :Siemens , Cuttler Hammer, L&T
Supply only Carbon brush for clutch for micro movement of EOT crane ,complete all as specified and as directed by Engr-in-charge.
Supply only push button switch for EOT crane with elements 6 Amps 415 volts 50 Hz ,complete all as specified and as directed by Engr-in-charge. Make :SIEMENS / L&T/ABB/SCHNIEDER
Supply only Ball bearing No 1209 K / 1212 K for plummer box of EOT Crane of 40/50 mm dia shaft ,complete all as specified and as directed by Engr-in-charge. Make : NBC/ TATA/ SKF.
Supply only thermal over load relay type MC - 305 ANA full current 1.58 to 2.5 Amp ,complete all as specified and as directed by Engr-in-charge. Make SIEMENS / L&T/ABB/SCHNIEDER
Ditto- all as per srl item No 15.00 herein before but for 2.5 Amps to 8 Amps
Supply only packing kit for gear box ,complete all as specified and as directed by Engr-in-charge. Make CRANEX/ API/KM Engg
M&L for checking the fire alarm/ fire detector system ,comprising as given below, by deployemnt of minimum 01 Electrician and 01 Helper as a service representive ,minimum once in two month at Armory Bldg Thane,complete all as specified and as directed by Engr-in-charge. Comprising of the following:- a) fire alarm pannel 8 Zone - 01 No. b) Smoke detector - 10 No. c) Heat detector - 2 No. d) Response Indicator - 10 No . e) Manual operating glass point - 5 No . f) Hooters - 2 No.
M&L for checking the fire alarm/ fire detector system ,comprising as given below, by deployemnt of minimum 01 Electrician and 01 Helper as a service representive ,minimum once in two month at Signal exchange Thane ,complete all as specified and as directed by Engr-in-charge.Comprising of the following:- a) fire alarm pannel 8 Zone - 01 No. b) Smoke detector - 10 No. c) Heat detector - 2 No. d) Response Indicator - 10 No . e) Manual operating glass point - 5 No . f) Hooters - 2 No.
M&L for checking the fire alarm/ fire detector system ,comprising as given below, by deployemnt of minimum 01 Electrician and 01 Helper as a service representive ,minimum once in two month at HQ bldg Thane. ,complete all as specified and as directed by Engr-in-charge. Comprising of following:- a) fire alarm pannel 8 Zone - 01 No. b) Smoke detector - 10 No. c) Heat detector - 2 No. d) Response Indicator - 10 No . e) Manual operating glass point - 5 No . f) Hooters - 2 No.
S&F, in repair, adjustable smoke detectors photo Electric/Optical complying with and type certified to EN 45 with self built intelliganvce as per IS 11630 complete with all fixtures as specified and directed by Engineer in charge . Make - Apollo/Zicom/Jayshwal
S&F,in repairs,adjustable manual call point resettable including sunken boxes,complete all as specified and as directed by Engr-in-charge. Make - Apollo/Zicom/Jayshwal
S&F,in repairs, Alarm Sounders/ Electronic sirens horizontal single stage normal operation for atleast 50 Minutes with sound level 65 DB to 120 DB Measured at 1.5 Meter with sound out put variation of 50 DB at 500 mtr range ,complete all as specified and as directed by Engr-in-charge. Make :ZICOM/Apollo or equivalent .
S&F,in repair, armoured CAT-5 cable in existing position ,complete all as specified and as directed by Engr-in-charge. Make - Apollo/Zicom/Jayshwal
Supply and fix 1.5 Sqmm 3 Core Copper multistranded FRLS Armoured cable provided at ceiling/along the wall/ floor/ ground etc including bens, end caps, junction boxes etc. ,complete all as specified and as directed by Engr-in-charge.
Supply and fix 1.5 Sqmm 4 Core Copper multistranded FRLS Armoured cable provided at ceiling/along the wall/ floor/ ground etc including bens, end caps, junction boxes etc.,complete all as specified and as directed by Engr-in-charge.
S&F,in repair,Fire alarm Control Panel in existing position ,complete all as specified and as directed by Engr-in-charge .Make - Apollo/Zicom/Jayshwal
S&F,in repair, Response Indicators in existing position ,complete all as specified and as directed by Engr-in-charge. Make - Apollo/Zicom/Jayshwal
Supply and fixing First aid box made with MS sheet 16swg including requisite medicine with complete assembley in existing position ,complete all as specified and as directed by Engr-in-charge .Make - Apollo/Zicom/Jayshwal
Taking down unserviceable flame proof main switches and MCB distribution boards single phase ,complete all as specified and as directed by Engr-in-charge.
Taking down unserviceable flame proof Rotary switch/socket single phase ,complete all as specified and as directed by Engr-in-charge.
Supply and fix Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V ,complete all as specified and as directed by Engr-in-charge. MAKE: M/S SUDHIR SWITCHGEARS LTD/CROMPTON GREAVES/ M/S BALIGA
Supply and fix Flame proof switch socket &plug combined in LM6 cable termination box in LM6, 16A,250V, 2P+earth ,complete all as specified and as directed by Engr-in-charge.MAKE: M/S SUDHIR SWITCHGEARS LTD/CROMPTON GREAVES/ M/S BALIGA
S&F Flame proof Distribution board single door made out of aluminium housing with powder coating surface mounting SPN 8way 240 volts with bus bar rating 200 Amps dust and vermin proof suitable for incorporation of MCB's and isolators ,complete all as specified and as directed by Engr-in-charge.MAKE: M/S SUDHIR SWITCHGEARS LTD/CROMPTON GREAVES/ M/S BALIGA
S&F MCB suitable for 240 volts AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 KA and 5 to 32 Amps ,complete all as specified and as directed by Engr-in-charge.
S & F of MCB suitable for 240 volts AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA and 16 to 32 Amps ,complete all as specified and as directed by Engr-in-charge.
Taking down old us flame proof light fitting ,complete all as specified and as directed by Engr-in-charge.
S&F 50W IP66 LED Flame proof luminaire comprising of rectangular shape pressure Die-Cast aluminium housing with weather proof gasket for lamp & driver compartment with system wattage of 50W+/- 10% W and rated lumens of min. 4200 lumens. The LED Make must be of CREE/LUMILED/NICHIA/OSRAM with 120 degree view angle, > 120 lumen/watt, >70 color rendering and LM80 test compliance. The driver must be constant current type having THD <10% and power factor >0.95 with short circuit protection, open circuit protection, reverse polarity protection, high voltage protection, protection against 5 kV high surges and comply to IEC 60598/IS 10322(PT.5/Sec.5)1987.The luminaire must have secondary optics with perfectly matched lens for better lightcontrol complete all as spd and directed.MAKE: M/S SUDHIR SWITCHGEARS LTD/CROMPTON GREAVES/ BAJAJ
S&F 45W IP66 LED Flame proof flood light luminaire comprising of pressure Die-Cast aluminium housing with weather proof gasket for lamp & driver compartment with system wattage of 45W+/- 10% W and rated lumens of min. 4600 Lumens. The LED Make must be of CREE/LUMILED/NICHIA/OSRAM with 120 degree view angle, > 120 lumen/watt, >70 color rendering and LM80 test compliance. The driver must be constant current type having THD <15% and power factor >0.95 with short circuit protection, open circuit protection, reverse polarity protection, high voltage protection, protection against 5 kV high surges and comply to IEC 60593/IS 10321(PT.5/Sec.5)1989. The luminaire must have secondary optics with perfectly matched lens for better light control complete all as spd and directed.MAKE: M/S SUDHIR SWITCHGEARS LTD/CROMPTON GREAVES/ BAJAJ
M&L for annual sprey Painting with approved make of electrically operated travelling (EOT) Crane of 2 Ton capacity each for 2 Nos of EOT crane, 11.5 mtrs span, 32.5 mtrs moving bay length,7 mtrs hook lift double girder and its necessary equipments,complete all as specified and as directed by Engr-in-charge
Taking out old unservicable LT UG cable of 3.5 core x 70 Sqmm to 150 Sqmm size and shall be deposited to place where as directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3½core.Make: Polycab/Havells/Paragon
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3½core.Make: Polycab/Havells/Paragon
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3½core.Make: Polycab/Havells/Paragon
Excavation in trenches, n exc 1.5 mtr wide and n,exc 1.5 mtr in depth; for foundation etc. or for shafts, wells cesspit, manholes, pier holes,etc n,exc 10 Sqm on plan and n exc 1.5mtr in depth and getting out as in Soft/loose Soil,complete all as specified and directed by Engg-in-Charge.
Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, in Soft/Loose Soil, ,complete all as specified and directed by Engg-in-Charge.
Removing excavated material n exc. 50m in soil and depositing where directed at a level n exc. 1.5 m above the starting point , including loading, unloading and stacking at the destination , complete all as specified and directed by Engr-in-charge.
M&L for Sand cushioning for UG cable protection/ducts, consolidated sand compacted with clean dry sand , complete all as specified and directed by Engr-in-charge.
M & L for Boring of road crossing in any kind of soil/rock strata , complete all as specified and directed by Engr-in-charge.
Supply and laying un reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches complete all as specified and as directed.
Supply & laying GI pipe light graded of size 50mm dia in trenches and fixing on wall / pole with help of suitable size MS clamp for cable protection with all fitting; complete all as specified and directed by Engr-in-charge.
M & L for earthing in repalacement, with coper earth plate electrode 600 x 600 x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal ground level and connected to earth test point by means of copper strip 32X6 mm all as specified and show in electric plate No 3 of MES SSR Part -I 2009 Including earthwork, PCC Chamber CI cover,protection and watering pipe, funnel,mesh etc all as reuired at site and all as directed note (i)7.5 M Copper strip in deemed to be cluded in quoted rates beyond 7.5 RM shall be meaured and paid separately (2) Earth resistance of earth pit should be less than 0.5 Ohms.on testing after completion if teh desired earth resistance in not obtained the earthing will be redone at no extra cost (3) Rate quoted by the tenderer is deemed of include salt & charcoal upto & above 450 mm top of copper plate
S&F GI pipe light grade of size 80mm dia fixing on pole/laid in trenches , complete all as specified and directed by Engg-in-Charge.
Supply, perform, testing, commissioning of LT cable straight through joint kit heat shrinkable of 3.5 core up to 35 Sqmm size , complete all as specified and directed by Engg-in-Charge. Make : Denson Part No : XSS-02/Raychem / M-Seal/ Birla-3M
Supply, perform, testing, commissioning of LT cable straight through joint kit heat shrinkable of 3.5 core upto 240 Sqmm size , complete all as specified and directed by Engg-in-Charge. Make : Denson Part No : XSS-02/Raychem / M-Seal/ Birla-3M
Supply, perform, testing, commissioning of LT cable End through joint kit heat shrinkable of 3.5 core x Sqmm size complete all as specified. Make : Denson Part No : XSS-02 /Raychem / M-Seal/ Birla-3M
S&F MCCB 4 pole 63 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.
S&F MCCB 4 pole 100 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as spd and directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts,ashers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint
S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw
S&F MCCB 4 pole 160 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.Make: Indoasian Cat No.X220M4T or equivalent
S&F MCCB 4 pole 200 A , 415 V, 50Hz having breaking capacity 36 KA with adjustable thermal & magnetic setting , complete all as specified and directed by Engr-in-Charge.Make: Indoasian Cat No.X250H4T or equivalent
S&F MCCB 4 pole 250 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting , complete all as specified and directed by Engr-in-Charge .Make: Indoasian Cat No.N3200M4P or equivalent
Inspection/checking & testing after repair of APFC panel 3 Phase,440 voltage 50Hz AC supply system to improve power factor 0.80 to 0.99 automatic step wise switched capacitor panel to make it serviceable in auto and maunal mode, with the help of connecting relays, capacitors,contactors,MCB's.,CTs, re-wiring burnt/worn out control wires etc and rectifying the defects, replacement of unserviceable parts as required at site and cleaning of AMF panel as detecting during inspection or pointed out by department and carry out maintenance complete all as specified as directed by Engineer-in-Chrage. (Notes :-This items includes the cost of cleaning & rewiring of panel. Spare parts required shall be measured and paid for separately under respective items as supply only)
Supply only in replacement of AIPFC microprocessor based relay 8 stage PFC controller ,230 volts complete all as specified and directed by Engineer-in-Charge. Make- L&T/EPCOS/Siemens
Supply only in replacement of Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 10 KVAR complete all as specified and as directed by Engineer-in-Charge.
Supply only in replacement of Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 15 KVAR complete all as specified and as directed by Engineer-in-Charge.
Supply only in replacement of capacitor duty contactor 3 phase suitable upto 20 KVAR capacity 240 volts complete all as specified and as directed by Engineer-in-Charge.Make- Epcos, L&T
Supply only in replacement of capacitor duty contactor 3 phase suitable upto 16 KVAR capacity duty contactor 1NO1NC 240 volts complete all as specified and as directed by Engineer-in-Charge.Make- Epcos, L&T
Supply & fixing in repair of MCB TPN 63 Amps, 4 Pole, 10 KA coplete all as specified and directed by Enginner-in-Charge.
Supply & fixing in repair of MCB TPN 63 Amps, 3 Pole, 10 KA coplete all as specified and directed by Enginner-in-Charge.
Supply only in replacement of current transformer of ratio 200/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply only in replacement of current transformer of ratio 100/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing in replacement indictor lamp assembly LED type complete including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing Start/stop push button complete including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing in replacement of digital type multimeter 96 mm x96 mm, of range 0-500 Volts and 0-200 Amps ,Class-I complete all as specified and as directed by Engineer-in-Charge.
M&L for fixing MS sheet 2mm thick to existing LT panels / feeder pillar box including necessary straightening /correcting the distorted parts, cuttings, welding / riveting,drilling bend to shape as required, welding of hinges, sliding door bolts, locking arrangement, nut, bolts, washers etc and appying two coats of synthetic enamedled paint over a coat of red oxide primer to match with the existing surfaces comlepte including butt hinges sliding door bolts and taping , thimbling disconnecting all incoming and outgoing complete all as specified and as directed by Engineer-in-charge. Note :- Supply only butt hinges and sliding door bolts shall be measured and paid seperately.
Material and labour for carrying out repair/maintenance through manufacturer or authorised service center of Auto servo control voltage stabilizer 300KVA capacity located at HQ area . (i)Opening of stabilizer and maintanance of spare parts,fixing of new/repaired parts after repair in place of defective parts,repairing the defective control system etc and assembling complet all as specified and directed. Testing of stabilizer after repair on existing location to desired and rated output. Note:- All defective parts maint and cost of labour for maint is deem too be included in unit rate .
Disconnecting all incoming and outgoing connection of HT 22KV under ground cable,detecting fault by applying surge current 1.5 times the rated current & finding exact location of fault with PICO equipment and repair the same immediately etc complete all as specified and directed by Engineer.in.Charge. Note: Necessary Jointing kit to be measured and paid separately in respective items.
Takaing down GI water tubing with 100mm bore all fittings and fixtures complete from wall/floor / trenches all as dircted by engineer in charge of following sizes
All as per item No 82 here-in-before but GI pipe of size 80 mm complete aii as specified and directed by Engineer-in-Charge.
All as per item No 82 here-in-before but GI of size 50 mm complete aii as specified and directed by Engineer-in-Charge.
All as per item No 82 here-in-before but GI of size 40 mm complete aii as specified and directed by Engineer-in-Charge.
All as per item No 82 here-in-before but GI of size 25 mm complete aii as specified and directed by Engineer-in-Charge.
All as per item No 82 here-in-before but GI of size 20 mm complete aii as specified and directed by Engineer-in-Charge.
All as per item No 82 here-in-before but GI of size 15 mm complete aii as specified and directed by Engineer-in-Charge.
Supplying & Laying, connecting and testing GI pipe 100 mm bore medium grade including necessary fittings in trenches complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 80 mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 50 mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 40 mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 25 mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 20 mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 89 here-in-before but of size 15 mm bore complete all as specified and directed by Engineer-in-charge.
Refixing old steel GI tubing of size 50mm and connecting incuding fittings /fixtures on wall /floor or in trenches including cleaning all as directed
All As per Item No -96 but for 40mm
All As per Item No -96 but for 25 mm
All As per Item No 969 but for 20 mm
All As per Item No -96 but for15 mm
Providing and deployement of one pipe fitter with one helper for attending minor breakdown of GI water supply pipe line up to 80/100 mm dia pipe line, complete all as specified and directed by Engr-in-charge. Note: (a) Necessary pipe,fitting,excavation shall be measured in respective items of sch A. (b) Necessary tools,machinery ,ladder for providing stagging shall be arrange by the contractor at his own cost nothing extra shall be paid on this account.
Ditto as per Srl Item No 101.00 above but for size 50/40 mm bore diameter pipe line.
Ditto as per Srl Item No 101.00 above but for size 25/20/15 mm bore diameter pipe line.
S&F,in repair, water meter of 100 mm dia with flanged joints; including removal of flanged connecting piece, or blank flange (if required) or taking out meter for testing, etc., and fixing (but not supplying) a length of flanged connecting pipe (or two blank flanges) and labour only for two flanged joints ,complete all as specified and directed by Engr-in-charge.
Supply only Grade IV ferric alum suitable for drinking water , complete all as specified and directed by Engr-in-charge.
Supply Only "CALCIUM HYPOCHLORITE" in plastic drum (Having 60% to 70% available chlorine) ,complete all as specified and as directed by Engineer in Charge
Material ,labour and services for taking sample water in sterlised bottles from water supply point, UG Sump / OH Resorvier for Analysis of water for the following parameters and obtaining sample test report from Govt Recognized Laboratories ,complete all as specified and as directed by Engr-in-charge.Following are the parameters need to check :- (i) Physio Chemical Analysis of Water ( Colour , odour , pH Total solids, Dissolved Solids, Permanent hardness, temporary Hardness, Ammonia feree and salinbe, Ammonia Albuminoidal, Nitrites, Nitreates, Oxygen absorption at 15 Min, Iron , Fluoride) (ii) Microbiological Analysis ( Total Choliforms , Escherichia coli) Notes :- 1. A certificate of approval / certification of Lab by Govt of India / State Govt shall be submitted by the contractor to the department. 2. Sample shall be submitted to the Laboratory within 24 Hrs of collection of sample. 3. Three samples shall be checked in each job
M&L for Cleaning of underground RCC sump of capacity upto 100000 gallon with the following process,complete all as specified and as directed by Engr-in-charge. (i) Dewatering the sump by using submersible pump and sludge pump which empty the tank up to base level.(ii) High pressure jet cleaning:- Cleaning of manhole of the tank, inside wall/ceiling of RCC sump with the help of high pressure rotary jet (Dirt killer) of capacity with variable pressure of 50-140 bars to remove the calcination (Fungal) layer.(iii) Removing sludge from the tank:- The sludge and infection sahll be remove from walls, Ceiling & bottom of the tank sahll also to be remove with the help of special sludge pump and remaining dirt which may have hidden in rough slots of the bottom of the tank have to be sucked with special Industrial Vaccum cleaner, so that, the tank is totally dirt free. (iv) Disinfection of the tank:- Cleaning of walls/ceiling with fresh water and biodegradable anti bacterial agent. (v) Sterilization of the tank:- After complete cleaning apply ultraviolet sterilizer having a Virocidal wavelength to ensure perfect disinfection of the tank.(Note:- Tools & Plant or machiney required for cleaning of sump shall be arrange by contractor at his own cost,nothing shall be paid extra on this account).
S&F,in repair,copper strip of 20x3.15 mm as roof conductor and down conductor till test point,complete all as specified and as directed by Engr-in-charge. Note:- Copper strip to be jointed through brazing only.
M&L for Cleaning of RCC over head tank of capacity 25000 gallon with the following process ,complete all as specified and as directed by Engr-in-charge. (i) Dewatering the sump by using submersible and sludge pump which empty the tank up to base level. (ii) High pressure jet cleaning:- Cleaning of manhole of the tank, inside wall/ceiling of RCC sump with the help of high pressure rotary jet (Dirt killer) of capacity variable pressure 50-140 bars to remove the calcination (Fungal) layer. (iii) Removing sludge from the tank:- The sludge and infection sahll be remove from walls, Ceiling & bottom of the tank sahll also to be remove with the help of special sludge pump and remaining dirt which may have hidden in rough slots of the bottom of the tank have to be sucked with special Industrial Vaccum cleaner, so that, the tank is totally dirt free. (iv) Disinfection of the tank:- Cleaning of walls/ceiling with fresh water and biodegradable anti bacterial agent. (v) Sterilization of the tank:- After complete cleaning apply ultraviolet sterilizer having a Virocidal wavelength to ensure perfect disinfection of the tank.(Note:- Tools & Plant or machiney required for cleaning of sump shall be arrange by contractor at his own cost,nothing shall be paid extra on this account).
Supply and fixing in Repairs of 50 mm bore gun - metal glove or gate Valves,With iron Wheel head,Screwed both ends for iron pipe and fixed for GI pipe including dismantling and taking out unserviceable valve complete all as specified and directed by Engineer -in- Charge.
All as per item No 111 here in before ,but of size 40 mm dia
All as per item No 111 here in before ,but of size 25 mm dia
All as per item No 111 here in before ,but of size 20 mm dia
M&L for GI bends, Tees, Nipple, Tail piece etc (any type & shape and angle) tapers of any type (straight, bend, increasing, decreasing or double socket etc) Tee pieces , all sockets or socket and plugs suitable for GI pipe 50 mm dia , complete all as specified and directed by Engr-in-charge.
Taking down sub main wiring of any size complete and making good disturbed surface of walls/floors etc ,complete all as specified and as directed by Engr-in-charge.
M & L for submain wiring with two runs of single core PVC insulated unsheathed FRLS copper conductor as mentioned below of similar type cable multistranded copper conductor 1100 volts grade IS:694 marked drawn in and including 25mm dia PVC non metallic PVC conduit , medium grade, ISI marked complete with all acessories and fittings laid/fixed concealed in wall/ceiling or surface conduit on wall/ceiling, and connecting to common earth dolly ,complete all as specified and as directed by Engineer-in-Charge. (Note : Cutting chases for counduit and sinking for boxes and making good to walls ,floors etc for sub main wiring will be measured & paid separately in respective items). OF THE FOLLOWING:-
Cable of size 2X4 sq mm and 1X4 sq mm earth continuity conductor
Cable of size 2X6 sq mm and 1X6 sq mm earth continuity conductor
Cable of size 2X10 sq mm and 1X6 sq mm earth continuity conductor
M & L for submain wiring with two runs of single core PVC insulated unsheathed FRLS copper conductor as mentioned below of similar type cable multistranded copper conductor 1100 volts grade IS:694 marked drawn in CASING CAPPING , medium grade, ISI marked complete with all acessories and fittings laid/fixed concealed in wall/ceiling or surface capping on wall/ceiling, and connecting to common earth dolly ,complete all as specified and as directed by Engineer-in-Charge. OF THE FOLLOWING:-
Cable of size 2X4 sq mm and 1X4 sq mm earth continuity conductor
Cable of size 2X6 sq mm and 1X6 sq mm earth continuity conductor
M & L for HDPE chamber for earth pit including necessory PCC 1:3:6 type B-2 for fixing the PVC inspection chember of size 200 mm depth, 300mm length and 300mm width ,complete all as specified and as directed by Engineer-in-Charge.
S&F,in repair, aluminium strip of 25x3mm as roof conductor and down conductor till test point all as directed by.Note-Aluminium strip to be jointed through nut,bolt and washers only ,complete all as specified and as directed by Engineer-in-Charge.
S&F,in repair, Porcelain insulators of Copper/Aluminium strip on wall / on Roof building with necessary screws washers and nut bolts etc complete all as specified and as directed by Engr-in-charge. Note - Rates are inclusive of copper screws with washers for fixing copper strip on Porcelain insulator with minimum size 1 inch and maximum size 1.5 inch with max external dia of screw is 8mm and 2 nos of GI nut for fixing insulator on wall all as per site requirement ,complete all as specified and as directed by Engineer-in-Charge.
Taking down unserviceable and dislocated air termination rod of any type from floor of any size ,complete all as specified and as directed by Engineer-in-Charge.
S&F in repair, of single pointed soild aluminium rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/dowen conductor all as specified and directed
S&F in repair, of single pointed soild COPPER rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/dowen conductor all as specified and directed
Material and labour for earth pit chamber of size 0.6mx0.6mx0.6m made with PCC 1:2:4 type B-2 including HDPE earthing pit cover inspection chember of size 200 mm depth, 300mm length and 300mm width ,complete all as specified and as directed by Engineer-in-Charge.
M&L for periodical testing and measuring the earth resistance value of the existing earthings / Down conductor / air terminal by means of wheat stone bridge method after disconnecting the earth continuity conductor from the test point , applying secondary voltage across the terminals, maintaining proper record of the measurement in presence of the users rep, MES rep, submitting the test records, pouring saline water in the earth pit to achieve low earth resistance, observing the same complete for monthly/Quarterly/Half yearly L2/L3 eqpts/E&M installations/Lightning arresters test ,complete all as specified and as directed by Engineer-in-Charge.
Taking down unserviceable main switches and MCB distribution boards single phase ,complete all as specified and as directed by Engr-in-charge
S&F in repair, MCB distribution board double Door of sheet metal TPN 4 way with 200 amps rated bus bar 415 volts ,complete all as specified and as directed by Engineer-in-Charge.
S&F in repair, MCB distribution board double Door of sheet metal Single pole and neutral 8 way with 200 amps rated bus bar 240 volts ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB ,SPN 240 volt 32/40/63 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB ,TPN 415 volt 63 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB single Pole 240 Volts 6 to 40 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw ,complete all as specified and as directed by Engineer-in-Charge.
M & L for replacement of Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to a depth of not less than 1.5 mtr below ground level connection to and including 4mm dia (8 SWG) GI earth wire from earth plate to main switch board including necessary GI bolts, nuts, check nuts, washers, thimble etc to the extend 7.5 mtr as earth lead by means of GI bolts & nuts etc, connecting to LT panel wlith provision of charcoal and salt all as per electrical plate No 3 of SSR Part-I including water arrangement with GI pipe 20mm dia (medium grade) excavation and earth work returning , filling, ramming and remove of soil to a distance not exc 50 mtr, make good to match with existing surface and testing on completion.Note:1.After completion if test results are nor satisfied, earthing should be redone by contractor without any extra cost. 2. Contractor should quote the rate deemed to be included with testing
All as per Srl item No 134.00 but GI Strip of size 25X4mm
All as per Srl item No 134.00 but using copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead
Supply and fix distribution board made out of sheet metal, powder coated, factory made enclousure, double door type, TPN 4 way vertical type, with 200 Amps rated copper bus bar, neutral bar, earth bar, TP 43 protection including provision of housing of incomer MCCB 63 Amps, triple pole and neutral, 415V, 16 KA breaking capacity and fixing of DB flush to wall surface complete all as specified and directed.
M/s PIONEER CONTRACTORS (BID ID -3230655)
EVEREST POWER CONTROL ENGINEERS (BID ID -3229696)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .