FOOD CORPORATION OF INDIA REGIONAL OFFICE, NO.10 EAST END MAIN ROAD, JAYANAGAR, 4th T BLOCK BANGALORE 560041
Renovation of existing electrical supply infrastructure by providing new underground power cables for restoration of power supply to the entire depot complex, godowns No. 4,5,6,10,11,12,16,17, and ancillaries, including Design,Fabrication, SITC OF FP
2026_FCI_898219_2
21/2025-26
Open Tender
Electrical Works
90 days
BSC WHITEFIELD, BANGLAORE
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹1.2 L
10 Mar 2026
12 Feb 2026
26 Feb 2026
12 Feb 2026
25 Feb 2026
12 Feb 2026
Supply of PVC insulated and PVC sheathed XPLE power cable of 1.1 KV grade armoured UG aluminium conductor cable conforming to IS 7098 part 1 with up-to-date amendment of the following size as required.
4 x 300 sq.mm
4 x 240 sq.mm
4 x 95 sq.mm
4 x 70 sq.mm
4 x 35 sq.mm
4 x 25 sq.mm
4 x 16 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Up to 35 Sq mm
Above 35 sq. mm and upto 95 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
90 mm dia (OD-90 mm & ID-76 mm nominal)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 X 6 sq. mm (22mm)
3 X 10 sq. mm (22mm)
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
4 X 35 sq. mm (32mm)
4 X 70 sq. mm (45mm)
4 X 95 sq. mm (50mm)
4 X 240 sq. mm (62mm)
4 X 300 sq. mm (75mm)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Design, Fabrication, Supplying, Installation, Testing and commissioning of Concrete base Mounted Dust and vermin proof Cubicle type Feeder pillar box suitable for 3 Phase, 415v, 50 Hz 4 Wire AC Supply System fabricated in compartmentalized System made out of 14 SWG CRCA Sheet Steel with doors and painted with powder coating in approved shade, ELR with CBCT, Complete with aluminium busbars of adequate capacity for Phases & neutral, Suitable M.S Angle Base Frame of 50 X 50 mm, interconnections control wiring, including incoming and outgoing cables connections, Door Earthing 2.5 mm Flexible Copper, suitable spread terminals for MCCBs, danger plate etc as required at site of work and as directed by the Engineer in charge. of following sizes and switchgear:
Size: 120 x 135 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 25 x 6 mm Aluminium- 4no.s- 110cm length each. Earth Bar: 25 x 3 mm Copper- 1 no.s- 140 cm length. Incoming: 4 pole MCCB, 100A, 30KA- 1 No with extended rotary handle Outgoing: 63A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 32A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 63A, 4 Pole MCB, 10KA -04Nos 32A, 2 Pole MCB, 10KA -02Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Size: 120 x 135 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 25 x 6 mm Aluminium- 4no.s- 110cm length each. Earth Bar: 25 x 3 mm Copper- 1 no.s- 140 cm length. Incoming: 4 pole MCCB, 100A, 30KA- 1 No with extended rotary handle Outgoing: 63A, 4 pole MCCB, 25/30KA- 2 Nos with extended rotary handle 32A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 32A, 4 Pole MCB, 10KA -02Nos 32A, 2 Pole MCB, 10KA -02Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Size: 150 x 135 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 30 x 6 mm Aluminium- 4 no.s- 140mm length each. Earth Bar: 25 x 6 mm Copper- 1 no. 140mm length each. Incoming: 4 pole MCCB, 150A, 36KA- 1 No with extended rotary handle Outgoing: 100A, 4 pole MCCB, 30KA- 1 No with extended rotary handle 63A, 4 pole MCCB, 25/30KA- 4 Nos with extended rotary handle 63A, 4 Pole MCB, 10KA- 02 Nos 32A, 2 Pole MCB, 10KA -02Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Size: 150 x 135 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 30 x 6 mm Aluminium- 4 no.s- 140 mm length each. Earth Bar: 25 x 5 mm Copper- 1 no.- 140 length. Incoming: 4 pole MCCB, 150A, 36KA- 1 No with extended rotary handle Outgoing: 125A, 4 pole MCCB, 36KA- 1 No with extended rotary handle 63A, 4 Pole MCCB, 25/30KA- 04 Nos 32A, 2 Pole MCB, 10KA- 2Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Size: 120 x 120 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 25 x 6 mm Aluminium- 4 no.s- 110mm length each. Earth Bar: 25 x 3 mm Copper- 1 no.s - 125mm length. Incoming: 4 pole MCCB, 63A, 25/30KA- 1 No with extended rotary handle Outgoing: 32A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 63A, 4 Pole MCB, 10KA 3Nos 32A, 4 Pole MCB, 10KA 2Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Size: 120 x 120 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 25 x 6 mm Aluminium-4 no.s - 110cm length each. Earth Bar: 25 x 3 mm Copper- 1 no.s- 125mm length Incoming: 4 pole MCCB, 63A, 25/30KA- 1 No with extended rotary handle Outgoing: 32A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 63A, 4 Pole MCB, 10KA 3Nos 32A, 4 Pole MCB, 10KA 2Nos Metering Panneling Digital Voltmeter - 01 Nos Digital Ammeter - 01 Nos RYB phase indication lamps -1 set 6A SP MCB for control Ckts -04 Nos
Supply, testing and commissioning of 6 meter high octagonal pole made of hot dip galvanised G.I. sheet 70 mm top diameter, 130 mm bottom diameter, thickness 3 mm, base plate dimensions of 200 x 200 x 12 mm, suitable for wind speed as per IS 875 part III, fixed head frame including 1 m channel arm bracket luminary carriage suitable to install 2 nos luminiaries including connector, 3C 2.5 sq. mm copper wire for connection, 6A SPN MCB for control, 4 nos EN-8 grade M20x600 mm foundation bolt fixed in existing RCC foundation along with nuts, washers, anchor plate etc., complete as required.
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Above 4.5 Meter and upto 6.5 Meter
Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way , Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole and neutral
Single pole
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
Group C
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
12 Module (200mmX150mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
6 pin 15/16 A socket outlet
15/16 A switch
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
Supplying and fixing of single phase, 230V, 50Hz, 300mm dia sweep, 4 blade Exhaust fan with bird screen for protection against birds & foreign material and fixing on the wall surface including giving connections etc. at site of work as required.
Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
90 W (DSR EM 2025 -Item no. 8.12.14)
Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 ̊C to 50 ̊C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt) Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast/ Extruded aluminium Body including trim. 18watt
Supplying, installing, testing, and commissioning 10-W LED bollard lights (surface-mounted) with potted driver, polycarbonate diffuser, and IP66 aluminium housing, energy-efficient, weather-resistant, and suitable for outdoor landscape lighting including providing all necessary fixing accessories (clamps, nuts, bolts) and making connections from the existing point, complete as required at site the work.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and drawing of 2.5 Sq.mm,three core PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts, conforming to IS: 694 in the existing surface/ recessed steel/ PVC conduit and connection of the fixtures as required.
Credit Items
Dismantled scrap of MS conduit/DB's/GI wir/clamps etc.
Dismantled scrap wire of Al.conductor cable.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.66 MB
MTF.pdf
Tender Documents • 2.11 MB
BOQ_944134.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid