| 1.20 | Item no.1
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set upto 50 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any Inspect alternator,
3) stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages,
4) checking battery cells gravity and topping up with distilled water,
5) checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator,
6) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
7) checking of AVR, excitation diodes, its connections confirming proper output voltage.
8) checking & resetting of valve tappets,
9) Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
10) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material.
(Comprehensive) as per specification | 1 | JOB | 19,500 ₹19,500 | 8,460 ₹8,460 Lowest | 8,460 ₹8,460 Lowest | 33,000 ₹33,000 | 50,000 ₹50,000 |
| 1.30 | Item No. 2
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 62.5 kVA to 200 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages,
4) checking battery cells gravity and topping up with distilled water,
5) checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator,
6) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
7) checking of AVR, excitation diodes, its connections confirming proper output voltage.
8) checking & resetting of valve tappets,
9) Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
10) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material.
(Comprehensive) as per specification | 1 | JOB | 33,500 ₹33,500 | 10,980 ₹10,980 Lowest | 10,980 ₹10,980 Lowest | 39,500 ₹39,500 | 60,000 ₹60,000 |
| 1.40 | Item no.3
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 250 kVA to 500 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment,
4) checking and retightening of nut bolts including coupling bolts of engine and alternator,
5) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
6) checking of AVR, excitation diodes, its connections confirming proper output voltage.
7) checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
8) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material
(Comprehensive) as per specification | 1 | JOB | 40,500 ₹40,500 | 15,552 ₹15,552 Lowest | 15,552 ₹15,552 Lowest | 42,000 ₹42,000 | 57,000 ₹57,000 |
| 1.50 | Item no.4
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 550KVA to 750 kVA with/without AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment,
4) checking and retightening of nut bolts including coupling bolts of engine and alternator,
5) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage.
6) checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge. (Comprehensive) as per specification
7) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material | 1 | JOB | 47,500 ₹47,500 | 23,320 ₹23,320 Lowest | 23,320 ₹23,320 Lowest | 52,500 ₹52,500 | 65,000 ₹65,000 |
Tender Value
₹60.4 L
EMD Value
₹60,420
Closing Date
25 Jun 2026, 12:00 pmClosed
City Engineer
MBMC Head Office
Two Yearly Maintenance of DG Set (Generators) at various places in MBMC Area.
2026_MBMC_1308692_1
MBMC/PWD/Tender/05_01/26-27
Open Tender
Electrical and Maintenance Works
Item Rate
730 days
MBMC
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,180
₹60,420
20 Aug 2026
17 Jun 2026
29 Jun 2026
17 Jun 2026
25 Jun 2026
17 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0.0 | Description | - | - | - | - |
| 0.9 | Item no.1
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set upto 50 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any Inspect alternator,
3) stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages,
4) checking battery cells gravity and topping up with distilled water,
5) checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator,
6) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
7) checking of AVR, excitation diodes, its connections confirming proper output voltage.
8) checking & resetting of valve tappets,
9) Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
10) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material.
(Comprehensive) as per specification | 1 | JOB | - | - |
| 0.0 | Item No. 2
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 62.5 kVA to 200 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages,
4) checking battery cells gravity and topping up with distilled water,
5) checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator,
6) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
7) checking of AVR, excitation diodes, its connections confirming proper output voltage.
8) checking & resetting of valve tappets,
9) Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
10) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material.
(Comprehensive) as per specification | 1 | JOB | - | - |
| 0.9 | Item no.3
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 250 kVA to 500 kVA with AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment,
4) checking and retightening of nut bolts including coupling bolts of engine and alternator,
5) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes,
6) checking of AVR, excitation diodes, its connections confirming proper output voltage.
7) checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
8) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material
(Comprehensive) as per specification | 1 | JOB | - | - |
| 0.0 | Item no.4
Providing Comprehnsive Maintenance 4 Time Visit in Month Compulsary and Providing Regular Servicing with all necessary Material
1) Carrying out servicing of DG set from 550KVA to 750 kVA with/without AMF panel of any make to ensure smooth running of DG set for 30 mins on load.
2) Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any.
3) Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment,
4) checking and retightening of nut bolts including coupling bolts of engine and alternator,
5) checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage.
6) checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge. (Comprehensive) as per specification
7) Removing all Rusted Parts from Generator and Providing New Welding with appropriate Material | 1 | JOB | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.61 MB
1.pdf
Tender Documents • 0.78 MB
BOQ_2245439.xls
BOQ • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .