RequiredOEM Annual Turnover Bid to RA enabled No Line Intractive UPS With AVR ( 30 pieces ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) GENERIC Rating in KVA/min VAH capacity of battery (KVA/VAH) 0.65/168 0.65/168 Technology MOSFET-PWM MOSFET-PWM Type of battery SMF-VRLA confirming to JISC-8702 Pt 1
Required2 &3 SMF-VRLA confirming to JISC-8702 Pt 1
Required2 &3 Rated Output (Volt) Single phase sinewave 230v AC
Required50Hz Single phase sinewave 230v AC
Required50Hz 1/4 Degree of protection IP-21 IP-21 Inverter Efficiency (%) >/= 60% >/= 60% Warranty for the battery from the date of delivery 1 year 1 year Warranty for Line Interactive UPS 2 Years 2 Years Installation and commissioning instructions Yes * CONSTRUCTIONAL Type of enclosure ABS * AC out put for printer (not through inverter) No No Inverter out put socket AC out put for printer (not through inverter) Not applicable Not applicable FUNCTIONAL Total harmonic distorsion (%) </= 40% * Input (Volt) Single phase sinewave(160-280v) * Switching over time (Mili sec) Maximum 10 milli seconds * Overload Time (Minutes) >/= 10 minutes >/= 10 minutes Load power factor >/= 0.6 >/= 0.6 Variation in AVR output in AC mode (%) AVR (Voltage regulation) output voltage in AC Mode 230 Volts +/-9%
Required50 +/-3 Hz 230 Volts +/-9%
Required50 +/-3 Hz Overload (%) >/=10% * Variation in output voltage in battery mode (%) (UPS output voltage in battery mode) 230 Volts +/- 10% * Variation on output frequency in battery mode (Hz) </=0.5 * PROTECTION Protection against (over discharge) discharge per 12v battery (Volt) 10.5 * Protection for outside input voltage range: If Yes * 2/4 Input voltage goes outside the range 160 to 280 Volts
Requiredthe system shall switch over to battery mode Protection against short circuit of UPS Yes * Protection for over voltage and over load Yes * REPORTS AND CERTIFICATIONS Damp heat Test at 45 degree
RequiredRH -95% for 2-cycle as per IS:9000 pt-5/sec-1 Yes * Dry heat Test at 45 degree for 16 Hrs as per IS:9000 pt-3/sec-5 Yes * Cold Test as per IS:9000 pt-2/sec-4 Yes * Availability of the type test report from central Govt./NABL/ILAC Accredited Lab Yes * Type Test certificate no. and date - * Name Of Lab - * Address of Lab - * As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes * * Specifications highlighted in bold are the Golden Parameters. * Bidders may note that In respect of non-golden Parameters
Requiredthe specifications 'Values' chosen by Buyer will generally be preferred over 'Bid requirement ( allowed Values) by the Buyer.