Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.8 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹25.8 L Quoted ₹26.5 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹27.2 L+₹67,011.92 (2.53%)Rejected-Finance | ₹27.2 L+₹67,011.92 (2.53%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹27.9 L+₹1.4 L (5.23%)Rejected-Finance | ₹27.9 L+₹1.4 L (5.23%) | L3 | Rejected-Finance Not Lowest |
Tender Value
₹39.2 L
EMD Value
₹78,460
Closing Date
19 Aug 2021, 6:00 pmClosed
GE Kamptee
Garrison Engineer, Kamptee Cantt - 441 001
REPAIR / REPLACEMENT OF LT UNDERGROUND CABLE, LT PANELS, STREET LIGHTS, INTERNAL WIRING, FANS AND OTHER CONNECTED ITEMS IN UNIT 371 AREA UNDER GE KAMPTEE
2021_MES_462074_1
8307/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
Class D Cat b (i)
7 documents required · 7 mandatory
₹500
Yes
GE Kamptee
₹78,460
Yes
14 Sept 2021
23 Jul 2021
21 Aug 2021
23 Jul 2021
19 Aug 2021
7 Aug 2021
Amount
Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5m in depth for laying of cables, poles, stay and getting out of excavated material complete all as specified and directed.
Excavation of road /floor cutting by manually for laying of cables including making good to disturbed surface to match with the existing surfaces after laying of cable/ GI pipe in trenches etc complete all as specified and directed.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 50mm outer diameter and 38 mm inner diameter with IS 14930 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 63mm outer diameter and 51mm inner diameter with IS 14930 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed.
S&F double wall corrugated high density polymer ethyl (HDPE) pipe for laying of electric cable of size 120mm outer diameter and 103.5 mm inner diameter with IS 14930 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc 50m and deposited where directed at a level not exc 1.5m above the starting point complete all as specified and directed.
Taking down unserviceable underground cable, any size from trenches, wall, floor etc and removing from site complete all as specified and directed.
Supply and Laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 300 sq mm, 3.5 core including testing after laid and jointed with lugs, nuts, bolts, washers complete all as specified and directed.
All as per item No 9 above but size 50 sq mm 3.5 core complete all as specified and directed.
All as per item No 9 above but size 35 sq mm 3.5 core complete all as specified and directed.
All as per item No 9 above but size 25 sq mm 4 core complete all as specified and directed.
All as per item No 9 above but size 16 sq mm 4 core complete all as specified and directed.
All as per item No 9 above but size 10 sq mm 4 core complete all as specified and directed.
Fabrication, Supplying Installing, testing & Commissioning outdoor type feeder pillar box with rain cowl weather / vermin proof, outdoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of size not less than 1200mm x 1500mm x 450mm including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of MS CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door with locking arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 450mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 600 Amps (30mm x 20mm) alumunium bus bar duly insulated, (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) one set of pilot lamp. (d) Incoming MCCB 400 amps 4 Pole 415 volts 35 KA thermal magnetic setting type- 1 Nos (e) Outgoing MCCB 200 amps 3 pole 415 volts 25 KA thermal magnetic setting - 01 Nos (f) Outgoing MCCB 125 amps 3 pole 415 volts 25 KA thermal magnetic setting - 01 Nos (g) Outgoing MCCB 100 amps 3 pole 415 volts 25 KA thermal magnetic setting - 01Nos (h) Outgoing MCB 63 amps 3 Pole 415 volts 10 KA thermal magnetic setting- 6 Nos
Fabrication, Supplying Installing, testing & Commissioning outdoor type feeder pillar box with rain cowl weather / vermin proof, outdoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of size not less than 1200mm x 1500mm x 450mm including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of MS CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door with locking arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 450mm below the ground grouted in & including PCC (1:3:6) type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 600 Amps (30mm x 20mm) alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) One set of pilot lamp. (d) Incoming MCCB 400 amps 4 Pole 415 volts 35 KA thermal magnetic setting type- 1 Nos (e) Outgoing MCCB 32 amps 3 pole 415 volts 25 KA thermal magnetic setting - 08Nos (f) Outgoing MCB 63 amps 3 Pole 415 volts 10 KA thermal magnetic setting- 08 Nos
Taking down existing unserviceable LT panel any capacity & disconnecting properly all electric supply complete all as specified and directed.
M&L for spray painting to existing LT panel of any capacity with two coats of approved colour synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint and writing feeder name with approved colour synthetic enamel paint complete all as specified and directed.
S&F thermoplastic cable junction boxes IP 55/IP65 with metric knockout for cable entry of size 200 x 160 x 98mm fixing on pole with 30 x 5mm MS clamps, nut bolts, washers, terminal block and glands suitable for 16 Sq mm core cable including 6-32 amps MCB SP complete all as specified and directed. Make:- HENSEL or equivalant in Neptune
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/ control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 15mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 complete all as specified and directed. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore, medium grade & copper lug etc. (f) 15mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
M&L for earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases as required 32x4 mm galvanised strip complete all as specified and directed.
Supply of 45W LED street light comprises of pressure die cast aluminium housing with frame and toughned glass cover having system lumen output > 4950 lumens, All LEDs are Tier 1 LEDs with induvial lens, Input voltage working range is 140 V AC to 270V AC, Driver is used with 4KV Internal Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection, Fixture is IP65 Protected & IK05 protected, THD < 10%, CCT 5700 +/-300K, PF > 0.9, CRI > 75 complete all as specified and directed. Make:- Cat No.LSTS-45-CDL-M of CG or equiv. in Wipro, Philips, Bajaj.
S&F 200W LED flood light made up of pressure dia cast aluminium housing with toughened glass cover having system lumen output > 22000 lumens, All LEDs are Osram LEDs with induvial lens, Input voltage working range is 120V AC to 280V AC with upper limit cut of at 300V AC, Fixture can withstand for 8hr in case of High Voltage fault up to 400V AC, Potted driver is used with 4KV Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection with one External 5KV Surge protection, Fixture is IP66 Protected & IK08 protected, THD < 10%, CCT 5700 +/-300K, PF > 0.9, Cable entry through PG9 Cable gland including suitable size bracket 1.2 mtr long complete all as specified and directed. Make:- Cat No. LFLN-200-CDL/60-M of CG or equiv. in Wipro, Philips, Bajaj.
S&F 40W LED post top luminaire has a single piece construction, Comprises of die cast housing and PC diffuser & spun aluminium reflector having system lumens > 4000. The operating voltage 120-277V AC with PF > 0.9. The LED is SMD type only with CCT 5700K CRI >75. The luminaire is IP 65, IK 10 and Electrical protection Class I. Driver should have 4KV Internal & 5KV External surge protection, The life of LEDs > 50000 hours at L70. (Dimension: top: 410mm dia, 395mm height, OD Size : 62mm) complete all as specified and directed. Make:- Crompton LPTO-40-CDL or equiv. in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 20 W, 230 V, 50Hz prewired complete all as specified and directed. Make:- Cat No. S0DVES-24-700-20W of CG or equiv. in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 75W, 230 V, 50Hz prewired complete all as specified and directed. Make:- Cat No. X075C070V107FN1BO of CG or equiv. in Wipro, Philips, Bajaj.
S&F in repairs LED fitting including drivers having energy consumption upto 200 W, 230 V, 50Hz prewired complete all as specified and directed. Make:- Cat No. X220C070V315CNV1AO of CG or equiv. in Wipro, Philips, Bajaj.
S&F 25W LED Street light comprises of pressure die cast Aluminium housing with frame and toughned glass cover having system lumen output > 2500 lumens, All LEDs are Tier 1 LEDs with induvial lens, Input voltage working range is 140V AC to 270V AC, Driver is used with 4KV Internal Surge protection, Short Circuit Protection, open Circuit Protection, High & Low voltage protection, Fixture is IP65 Protected & IK05 protected, THD < 10%, CCT 5700 +/-300K, PF > 0.9, CRI > 75, including suitable size bracket 1.2 mtr long complete all as specified and directed. Make:- Cat No. LST-25-CDL-M/NL of CG or equiv. in Wipro, Philips, Bajaj.
S&F in repairs fuse unit, FN 63 Amp TPN 415 V complete all as specified and directed.
S&F in repairs fuse unit, FN 32 Amp, TPN 415 V complete all as specified and directed.
Taking down point wiring with aluminum conductor cable of light point fan & socket light & power complete including light fittings any type switches, sockets, ceiling rose, switch boards, bell/buzzer, bell push, tube light fitting, regulator etc, and making good to the disturbed surfaces of walls/ floor etc to match with existing surfaces including white washing/colour washing/ distemper to match with existing wall/ floor/ ceiling finishes complete all as specified and directed.
Taking down sheet metal enclosure DB, MCB, main switch etc and making good disturbed surfaces to match with existing surfaces complete all as specified and directed.
Taking down sub main wiring of any size/ capacity complete all as specified and making good disturbed surfaces to match with the existing surfaces complete all as specified and directed.
M&L for point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marked medium grade PVC caping casing on surface of wall/ ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxes sunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular cover with frame any size complete all as specified and making good to disturbed surfaces for one light point controlled by one, one way switch. Note:- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate. All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly.
All as per item No 34 above but one ceiling/exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 34 above but one 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 34 above but one 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 34 above but one bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per item No 34 above but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmm for 15 amps power point complete all as specified and directed.
M&L for point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marked medium grade concealed in surface of wall/ ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxes sunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular cover with frame of any size complete all as specified and making good to disturbed surfaces for one light point controlled by one, one way switch. Note:- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate. All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly.
All as per item No 40 above but one ceiling /exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 40 above but one 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 40 above but one 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 40 above but one bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per item No 40 above but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmm for 15 amps power point complete all as specified and directed.
M&L for sub main wiring with two single core PVC FR LSH insulated unsheathed stranded copper conductor and earth wire 1100 volt grade and drawing into PVC conduit not less than 20mm dia, medium grade, concealed in wall of size 2x2.5 Sqmm with earth wire of 1x2.5 Sqmm complete all as specified and directed. Note:- Accessories for point/sub main wiring like PVC junction box, bend, Tee, elbow shall be of same make.
As per item No 46 above but 2x4.0 Sqmm with earth wire of 1x4.0 Sqmm complete all as specified and directed.
As per item No 46 above but 2x 6.0 Sqmm with earth wire of 1x6.0 Sqmm complete all as specified and directed.
S&F ceiling rose surface type, 2/3 terminal, 5 amps complete all as specified and directed.
S&F Bell ding dong, AC 230 volts, single phase complete all as specified and directed.
S&F lamp holder, insulated body with back plate for angle/ batten fitting complete all as specified and directed.
S&F modular switch one way, 6A, 1 module complete all as specified and directed.
S&F modular switch one way 16A, 1 module complete all as specified and directed.
S&F modular bell push, 6A, 1 module complete all as specified and directed.
S&F modular socket 6A, 2/3 pin combined, 2 module complete all as specified and directed.
S&F modular socket 6A/ 16A, 2/3 pin combined, 2 module complete all as specified and directed.
S&F modular fan step regulator, 120 watt, 2 module complete all as specified and directed.
S&F highly durable surface mounted 18/20 watts LED batten/surface constructed of fire retardant engineering grade extruded aluminium body 100 lumen per watt, min 2000 lumen and decorative end cap complete with driver including 3 core 1.0 sqmm copper conductor cable for connection and accessories complete all as specified and directed. Make:- CG Cat No LDL-20-CDL or equivalent in Bajaj/ Philips/ Luker/ Halonix.
S&F light fitting 9W bulk head luminaries with lamp holders etc complete with all accessories and including connecting up with twin core twisted flexible cable of suitable size, 230V, 50HZ complete all as specified and directed. Make:- CG Cat No LBHP-10-CDL or equivalent in Philips/ Wipro/ Luker/ Halonix.
S&F energy efficient surface mounted 2'X2' grid ceiling LED fitting 36/40 W rated voltage 240 V, 50Hz combination with profiled and flat diffuse complete all as specified and directed. Make:- CG Cat No LCTLRF6-36-CDL or equivalent in Philips/ Wipro/ Luker Halonix.
S&F LED baton fitting 2' length including drivers having energy consumption, 10/11W, 230 V, 50Hz, 6500K, not less than 800 lumen prewired, complete all as specified and directed. Make:- CG Cat No LDL-10-CDL or equivalent in Philips/ Wipro/ Luker/ Halonix.
S&F LED post top light fitting 20W with all fixing accessories, fitted on pillar or poles complete all as specified and directed. Make:- CG Cat No LPTO-40-CDL or equivalent in Philips/ Wipro.
S&F sheet metal enclosure single pole & neutral for 240 volts, 8 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F sheet metal enclosure single pole & neutral for 240 volts, 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F sheet metal enclosure triple pole & neutral for 415 volts, 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
S&F MCB single pole, 240 volt, 6 to 40 amps, 10 KA breaking capacity, 'C' series complete all as specified and directed.
S&F MCB single pole and neutral, 240 volt, 6 to40 amps, 10 KA breaking capacity, 'C' series complete all as specified and directed.
S&F MCB triple pole and neutral, 415 volt, 40 to 60 amps, 10 KA complete all as specified and directed.
M&L for earthing complete with galvanized street earth plate electrode 600 x 600 x 6mm thick buried directly in ground (earth plate not less than 2.25mtr deep below normal ground level) with top edge of the plate not less then 1.50 mtr below the normal ground level connected to galvanized earth lead wire 4.00mm dia by means of bolts nuts check nuts & washer of galvanized iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified and testing on completion including the material and labour for:- (a) Excavation and earth work or drilling hole for electrode in any type of soil (b) PCC pit in cement concrete (1:2:4) type B-1 (c) Precast RCC cover with suitable handle 40mm thick in PCC (1:2:4) reinforced with welded steel wire fabric weighting not less than 1.87 Kg/sqmm (d) Funnel with watering pipe of GI 20mm nominal bore medium grade and Aluminum lugs etc all as specified. (e) 15mm nominal bore medium grade GI protection pipe up to 7.50 meter long for protection of earthing lead. (f) Requisite quantity of charcoal and common salt (g) Connection to earthing test point and testing on completion.
Disconnect and insulate electric supply wire and taking down carefully ceiling/ exhaust/ cabin/ wall fans of any make and sweep, dismantling blades, check for repairs required complete all as specified and directed. Note:- Repair/ Replacement of spares shall be carried out under appropriate items.
Hanging only ceiling fans of any make and sweep, connecting complete with & including provision of 3 core copper conductor cord PVC insulated and sheathed from ceiling rose to fan connector and testing, making of MES No complete all as specified and directed. Note:- The fan shall be fitted with new set of clamps, rubber shackle, split pins and top and bottom nut bolts etc.
Hanging only exhaust/ cabin/ wall fans of make and sweep, connecting lug complete with and including provision of three core copper conductor cord, PVC insulated and sheathed from ceiling rose to fan connector & testing, marking of MES No complete all as specified and directed. Note:- The fan shall be fitted with new set of washers, nuts, rubber packing etc.
Opening up of fan motor of ceiling/ Exhaust/ wall/ cabin fans, cleaning starter rotor, cleaning of all parts, greasing, oiling of bush and bearing, re-assembling and testing for smooth functioning complete all as specified and directed.
M&L for taking down burnt/ damaged winding, cleaning stator and rotor including slots etc, rewinding with suitable gauge of super enameled copper insulated wire for ceiling fan 1200mm sweep complete all as specified and directed.
All as per item No 74 above but exhaust fan 230mm sweep complete all as specified and directed.
All as per item No 74 above but exhaust fan 300mm sweep complete all as specified and directed.
All as per item No 74 above but exhaust fan 450mm sweep complete all as specified and directed.
S&F in replacement bearing for ceiling fan of 1200mm sweep complete all as specified and directed.
S&F in replacement bearing for exhaust fan of 230mm sweep complete all as specified and directed.
S&F in replacement bearing for exhaust fan of 300mm sweep complete all as specified and directed.
S&F in replacement bearing for exhaust fan of 450mm sweep complete all as specified and directed.
S&F gun metal bush for ceiling fan of 1200mm sweep complete all as specified and directed.
S&F in replacement condenser AC 230 Volt 2.5 MFD complete all as specified and directed.
S&F in replacement condenser AC 230 Volt 4.0 MFD complete all as specified and directed.
S&F ceiling fan blades for 1200mm sweep complete with nuts and bolts as per sample (set of three) complete all as specified and directed.
M&L for shaft work of ceiling fan of any make and sweep complete including filling metal and lathe machining complete all as specified and directed.
M&L for down rod for ceiling fan of any make and sweep, made out of medium grade GI tubing 15mm dia, duly painted with two coats of synthetic enamel paint and provision of holes for electric wire at top and bottom, also arrangement for fitment of ceiling fans complete all as specified and directed.
M&L for MS work such as fan hook, angle / FI clamp, MS pipe, nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts in any shape and size etc including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.73,884.00]
Vaidehi E Link
Chinmaya Enteprises
Bidder Name
Paragon Electrotechnics
Chinmaya Enteprises
Vaidehi E Link
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .