Repairing, Servicing and Overhauling of HT Electrical Installations at NBCC Town, Phase-I, Khekra, Baghpat, UP
NBCC/SBG-CEM/Khekra/2022/06
NBCC/SBG-CEM/Khekra/2022/06
Open Tender-Domestic
Electrical Work
Baghpat, Uttar Pradesh
₹2,950
₹10,251
7 Nov 2022
14 Oct 2022
7 Nov 2022
7 Nov 2022
9 Nov 2022
Repairing, Servicing and Overhauling of 33KV and 11KV Installations at NBCC Town, Phase-I, Khekra, Baghpat, Uttar Pradesh
Supply, Laying and Fixing of 33KV 300 sq mm 3 Core Aluminium Conductor HT Cable,
Stranded Compacted Circular Aluminium Conductor, Conductor Screen with Extruded
1 Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi RMT 60 3040.00 1,82,400.00
Conducting Compound in Combination with Copper Tape, AL Round Wire Armoured, and
Overall PVC Sheathed Cable Conforming to IS 7098.
SITC of 33 KV Outdoor type End Termination for 3C X 300 sq mm HT Cable, complete as
required at site.
Servicing, testing and Overhauling of 33kV Overhead line within 33/11kV Substation of NBCC
Town, Phase-I, Khekra, including with the following scope of
1) Isolate the GO switch from HT pole
2) Cleaning and servicing of GO switch with the help of CRC
3) Applyig of Petrolium jelly on all the moving joints of GO switch to work smoothly
4) Changing the conductors of GO switch with thimbles if required
5) Painting of 33KV GO switches, 33kV Poles, Cable Trays & Slotted Channels and other
metalic installation of 33kV electrical system
6) Replacement of Fuse Wires
7) Replacement of ACSR Conductor between GO Switch to Fuse Assembly
8) Cleaning and tightning of Insulators
9) Repairing and Testing of Earthing Systems
The scope of work is not limited to the baove items and contractor shall service, clean,
overhaul the entire installations of 33KV Over head Lines including GO/DO, Poles and all
other overhead installations etc., to make the system healthy and smoothly functional.
Servicing, testing and Overhauling of 11KV HT GO Switch including with the following scope
1) Isolate the GO switch from HT pole
2) Cleaning and servicing of GO switch with the help of CRC
3) Applyig of Petrolium jelly on all the moving joints of GO switch to work
4) Changing the conductors of GO switch with thimbles if required
5) Painting of 11KV GO switches and Poles and other metalic installation of 11kV electrical
6) Replacement of Fuse Wires
7) Cleaning and tightning of Insulators
8) Cleaning and HT taping or Reslveeing of 11KV Termination Ends of HT Cables
9) Repairing and Testing of the Earthing System
The scope of work is not limited to the baove items and contractor shall service, clean,
overhaul the entire installations of 11KV Over head Lines including GO/DO, Poles and all
other overhead installations etc., to make the system healthy and smoothly functional.
Digitally signed by ASHWANI
ASHWANI KUMAR BANSWA
KUMAR BANSWA Date: 2022.10.14 15:53:31
Servicing, Testing and Overhauling of 33KV VCB Set (1 I/C+ 1 O/G) Including with the
following scope of work:
1. Deep cleaning of VCB Panel with removing the dust from busbar & insulators for prevent
2. Servicing of VCB as per the OEM standard with the help of CRC/Petrol
3. Over current and Earth fault test with the help of secondary Injection kit
4. IR Value test
5. Electrical operations test
6. Re-calibration of Relays
7. Repairing and Testing of Emergency Power Supply
8. Re-sleeving of Bus Bars, wherever required.
9. Taping and Re-sleeving of Cable End Terminations , wherever required.
10) Repairing and Testing of the Earthing System
The scope of work is not limited to the baove items and contractor shall service, clean,
overhaul the 33kV VCBs and all other associated installations etc., to make the system
healthy and smoothly functional.
Servicing, Testing and Overhauling of 11KV VCBs (1 I/C+ 6 O/G) Including with the following
1. Deep cleaning of VCB Panel with removing the dust from busbar & insulators for prevent
2. Servicing of VCB as per the OEM standard with the help of CRC/Petrol
3. Over current and Earth fault test with the help of secondary Injection kit
4. IR Value test
5. Electrical operations test
6. Re-calibration of Relays
7. Repairing and Testing of Emergency Power Supply
8. Re-sleeving of Bus Bars, wherever required.
9. Taping and Re-sleeving of Cable End Terminations , wherever required.
10) Repairing and Testing of the Earthing System
The scope of work is not limited to the baove items and contractor shall service, clean,
overhaul the 11kV VCBs and all other associated installations etc., to make the system
healthy and smoothly functional.
Servicing, testing and Overhauling of 11KV HT Feeder pillar panels including with the
following scope of work:
1) Busbar tightning, replacement of heat shrinkable sleeves and other hardwares if required,
removing the dust and moisture from busbar and electrical operation testing etc.
2) Filling the gap between cable gland and panel at the cable entry point
3) Taping and Re-sleeving of Cable End Terminations , wherever required.
4) Replacment of Nutbolts of Cable Terminatios.
5) Painting of panels from both inside and outside
6) Repairing and Testing of the Earthing System
The scope of work is not limited to the above items and contractor shall service, clean,
overhaul the entire installations of 11KV Feeder Panels, to make the system healthy and
smoothly functional.
Servicing, testing, Overhauling and Dehydration of 250KVA, 11KV/415V Transformers
including with the following scope of work:
1) Cleaning of the Transformer and tightening of HT and LT side Transformer Terminals
2) Taping and Re-sleeving of Cable End Terminations , wherever required.
2)IR Value, Voltage Ratio and other test of transformers, as required
3) BDV Test of the Oil Before and After Dehydration
4) Dehydration of Transfromer including Top-Up of the Transformer Oil, wherever required
5) Replacement of Silica Gel
6) Repairing and Testing of the Earthing System
The scope of work is not limited to the above items and contractor shall service, clean,
overhaul the entire installations of Tranformer, to make the system healthy and smoothly
Digitally signed by ASHWANI
9 SITC of 18" Metal Body Heavy Duty Exhaust Fan complete as required at site.
Each 2 KUMAR BANSWA 9,900.00
KUMAR BANSWA Date: 2022.10.14 15:53:31
SITC of 2000 Watt Rod Type Room Heaters in the HT Meter Room, complete as required at
SITC of 400 Amp Changeover System with enclosure and all required accessories and spare
11 etc. including the retaping and resleeving of end terminaitons of cable, complete as Each 1 31,500.00 31,500.00
required at site.
Digitally signed by ASHWANI
ASHWANI KUMAR BANSWA
KUMAR BANSWA Date: 2022.10.14 15:53:31
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT1.pdf
Tender Document
BOQ.pdf
Tender Document
GCC2019FinaL18.pdf
Tender Document
Scope of Work.pdf
Tender Document
Instruction to bidder.pdf
Tender Document
corrigendum-1116-Corrigendum03.pdf
pdf • 0.21 MB
corrigendum-1106-Corrigendum02.pdf
pdf • 0.21 MB
corrigendum-1083-Corrigendum01.pdf
pdf • 0.21 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .