| Sl No | Description | Qty | Unit | Star Electrical L7 | KSP ENTERPRISES L13 | K.K.Enterprises L5 | Suchit constructions L1 | Fine-Tech. Electricals L9 | SOURABH ENGINEERS L3 | Chaulya Enterprises L8 | D H L ENTERPRISES L6 | PROLINK COMPUTERS L4 | SHRI PLACEMENT AND CONSULTANCY SERVICES L12 | Sanjivani Electricals L10 | TRINSIYA ASSOCIATE L2 | SARATH ENTERPRISES L11 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (60x10mm ) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers including connection of spider of various capacity of MCCB complete with comprising of following and including: (Location : 101 TA Ors Bldg back side, RAO Office) | 1 | Each Job | 2,12,211 ₹2,12,211 | 1,80,000 ₹1,80,000 | 1,72,000 ₹1,72,000 | 1,26,000 ₹1,26,000 Lowest | 1,97,000 ₹1,97,000 | 1,78,960 ₹1,78,960 | 1,90,000 ₹1,90,000 | 1,75,000 ₹1,75,000 | 1,50,000 ₹1,50,000 | 1,81,000 ₹1,81,000 | 2,05,000 ₹2,05,000 | 1,99,999 ₹1,99,999 | 2,00,000 ₹2,00,000 |
| 1.01Incoming | ||||||||||||||||
| 1.02(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No | ||||||||||||||||
| 1.03(b) Alum bus bar (60 x 10 mm) 600 Amps TPN -01 Set | ||||||||||||||||
| 1.04(ii) Ammeter 0-600 Amps with CTs & selector switch -01 No. | ||||||||||||||||
| 1.05(iii) Voltmeter 0-500 volts with selector switch -01 No | ||||||||||||||||
| 1.06(iv) Indicating lamp LED type - 01 set of three | ||||||||||||||||
| 1.07(B) Outgoing | ||||||||||||||||
| 1.08(a) MCCB 4 pole, 200 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos | ||||||||||||||||
| 1.09(b) MCCB 4 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos | ||||||||||||||||
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
14 Nov 2025, 6:00 pmClosed
GE NORTH PUNE
Garrison Engineers Office (North)General Cariappa Marg, Pune-01
GE (N) P/TOKEN- 56 OF 2025-2026 REPAIR/ REPLACEMENT OF OLD UNSV LT PANEL AND ALLIED INFRASTRUCTURE IN THE AOR OF AGE E/M UNDER GE (NORTH) PUNE
2025_MES_736613_1
GE (N) P/TOKEN- 56 OF 2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹80,000
Yes
17 Jan 2026
24 Oct 2025
21 Nov 2025
24 Oct 2025
14 Nov 2025
7 Nov 2025
25 Oct 2025 - 31 Oct 2025
Amount
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (60x10mm ) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers including connection of spider of various capacity of MCCB complete with comprising of following and including: (Location : 101 TA Ors Bldg back side, RAO Office)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (60 x 10 mm) 600 Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(a) MCCB 4 pole, 200 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 4 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
( e ) MCB DP 40 Amps -04
(f) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50 x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers including connection of spider of various capacity of MCCB complete with comprising of following and including: Location: 7 PG Road , 101 TA MD Accn, ZRO, Ghorpadi 164, Ghorpadi 184, 64 Supply depot
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (10mm x 50 mm) 500 Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(b) MCCB 4 pole, 100 Amp,adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 03 Nos
(b) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos
(c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 Nos
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50 x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB complete with comprising of following and including: (Location :DMSA Office )
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No (With sutiable spider)
(b) Manual change over switch 320 Amps with suitable spider )
(b) Alum bus bar (10 x 50 mm) 500Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(a) MCCB 4 pole, 200 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos (With suitable spider)
(b) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos (With suitable spider)
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (60 x 10 mm ) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB and the enclosure should be fix wall or above 2 feet ground level complete with comprising of following and including: (Location : NFS Node)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No (With sutiable spider)
(b) Manual change over switch 400 Amps with suitable spider )
(b) Alum bus bar (10 x 60 mm) 600Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(a) MCCB 4 pole, 320 Amp,adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(b) MCCB 4 pole, 200 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(c ) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (100 x 10 mm ) 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB and the enclosure should be fix wall or above 2 feet ground level complete with comprising of following and including: (Location : Gurudwara road near 88 block)
Incoming
(a) ACB, 4 Pole, 415 Volts,630 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No (With sutiable spider)
(b) Alum bus bar (100 x 10 mm) 1000Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(a) MCCB 4 pole, 320 Amp,adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(b) MCCB 4 pole, 200 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(c ) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (With suitable spider)
(c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (With suitable spider)
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (70 x 10 mm ) 700 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB and the enclosure should be fix wall or above 2 feet ground level complete with comprising of following and including: (Location : Vishwamitra marg sub stn No. 3)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No (With sutiable spider)
(b) Alum bus bar (10 x 70 mm) 700Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(a) MCCB 4 pole, 100 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 03 Nos (With suitable spider)
(b ) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos (With suitable spider)
(d) Automatic astronomical type timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 100 Amps, 220 Volts, 50 Hz. The sensor based timer should also have over voltage and low voltage trip with auto reset facility the sensor alongwith suitable power contactor, MCB and support terminals should be enclosed-1 No
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50 x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB and the enclosure should be fix wall or above 2 feet ground level complete with comprising of following and including: Location L (4 Victoriya road , Koima line near blocok 92)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (10mm x 50 mm) 500Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(b) MCCB 4 pole, 200 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(b) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 04 Nos
(c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 03 Nos
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (60 x 10 mm ) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers and including connection of spider of various capacity of MCCB and the enclosure should be fix wall or above 2 feet ground level complete with comprising of following and including: Location : (APNA Bazar)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Change over switch 400 Amps and fixing of LT Panel
(b) Alum bus bar (10mm x 60 mm) 600Amps TPN -01 Set
(iv) Indicating lamp LED type - 01 set of three
(B) Outgoing
(b) MCCB 4 pole, 200 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(b) MCCB 4 pole, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 04 Nos
( d ) MCB DP 40 Amps -04
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 300 Sq mm. complete all as specified and as directed.
-ditto- all as per Item No 09 above but 3.5 core 240 sqmm
-ditto- all as per Item No 09 above but 3.5 core 185 sqmm
-ditto- all as per Item No 09 above but 3.5 core 120 sqmm
-ditto- all as per Item No 09 above but 3.5 core 95 sqmm
-ditto- all as per Item No 09 above but 3.5 core 70 sqmm
-ditto- all as per Item No 09 above but 3.5 core 50 sqmm
-ditto- all as per Item No 09 above but 4 core 35 sqmm
-ditto- all as per Item No 09 above but 4 core 25 sqmm
-ditto- all as per Item No 09 above but 3 core 16 sqmm
Supply and laying in replacement of 40mm outer dia, double walled corrugated (DWC) duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying in replacement of 50mm outer dia, double walled corrugated (DWC) duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying in replacement of 63mm outer dia, double walled corrugated (DWC) duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying in replacement of 77mm outer dia, double walled corrugated (DWC) duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
S&F in replacement of MCCB 250 A with spider asper suitable site ,4 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
S&F in replacement of MCCB 200 A with spider asper suitable site ,4 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
S&F in replacement of MCCB 63/100 A with spider asper suitable site ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 25 to 30 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 50 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 95 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 120 to 150 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 185 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 240 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing kit in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 300 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Checking the Fault up to 11 KV from 95 sqmm to 185 sqmm of any size and length at any location with fault detector machine, including Supply and fixing in replacement of straight through cable joint kits / End joint kit of HT UG cable up to 185 sq mm as required length after determining the fault location including earth work at any strata as required depth and width and testing complete all as specified and as directed by Engr- in- charge. Note:- i) Fault detector machine & other equipment shall be arranged by the contractor within 1 hour of complaint received including 24/7.
Checking the Fault of LT Cable of any size and length at any location with fault detector machine and fixing only straight through cable joint kits any size (LT) and LT UG cable as required length after determining the fault location including earth work at any strata as required depth and width and testing complete all as specified and as directed by Engr- in- charge. Note:- i) Fault detector machine & other equipment shall be arranged by the contractor within 1 hour of complaint received including 24/7. ii) Cable jointing kit and LT UG cables shall be measured and paid seperatly as supply only under relevant item
S&F in replacement of MCCB 160A with suitable spider asper suitable site ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge
S&F in replacement of MCCB 200A with suitable spider asper suitable site ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge
Supply and fixing in replacement of MCB SP 5 To 32 AMP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) to fixing the external panel complete with connection testing and commissioning all as specified and directed
Supply and fixing in replacement of MCB SPN 32 AMP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) to fixing the external panel complete with connection testing and commissioning all as specified and directed
Supply and fixing in replacement of MCB TP 63 AMP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) to fixing the external panel complete with connection testing and commissioning all as specified and directed
Supply and fixing in replacement of MCB TPN 100 AMP rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) to fixing the external panel complete with connection testing and commissioning all as specified and directed
Supply and fix Nut bolts 6, 8 10 mm (1 Inch) and 12 mm ( 2 Inch )with washer as per site requirement all as directed by Engineer-in-charge
Supply and fix XLPE Cable ferrule Ferrule 16, 25,35,50 SQ MM as per site requirement all as directed by Engineer-in-charge
Welding of old LT panel door with hinges with handle lock as per site requirement all as directed by Engineer-in-charge
Excavation in trenches soft / disintegated rock not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick of soft/loose soil in trenches / pit complete all as specified and as directed.
Removal of surplus soil to a distance not exceeding 50 m and depositing where directed not exceeding 1.5 m above the starting point complete all as directed.
M & L Cement Concrete 1:4:8 (40mm graded aggregate) as Lean Concrete in Foundation of Poles etc, including Formwork (as if required), complete all as specified and as directed.
Note : 1. Rerformance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
TRINSIYA ASSOCIATE (BID ID -3473953)
SOURABH ENGINEERS (BID ID -3474615)
PROLINK COMPUTERS (BID ID -3474312)
K.K.Enterprises (BID ID -3474154)
D H L ENTERPRISES (BID ID -3474203)
Star Electrical (BID ID -3472479)
Chaulya Enterprises (BID ID -3474163)
Fine-Tech. Electricals (BID ID -3474272)
Sanjivani Electricals (BID ID -3474432)
SARATH ENTERPRISES (BID ID -3474396)
SHRI PLACEMENT AND CONSULTANCY SERVICES (BID ID -3474227)
KSP ENTERPRISES (BID ID -3474048)
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
BOQ_824837.xls
BOQ • 10.95 MB
tenderdocument56.pdf
Tender Documents • 0.84 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .