Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.8 LAccepted-AOC NO 18 BHARATHI STREET WEST GANDHI NAGAR AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | L1 | Accepted-AOC Rates quoted are reasonable | |
| 2 | L2₹18.2 L+₹42,700 (2.40%)Rejected-Finance | L2 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 | |
| 3 | L3₹18.4 L+₹69,200 (3.90%)Rejected-Finance | L3 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 | |
| 4 | L4₹20.3 L+₹2.6 L (14.6%)Rejected-Finance NO 15 PULAVAR GOVINDAN STREET GANDHI NAGAR AVADI CHENNAI 600 054 | AVADI | CHENNAI | TAMIL NADU | 600054 | L4 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
25 Apr 2022, 6:00 pmClosed
GARRISON ENGINEER AF THANJAVUR
GARRISON ENGINEER AF THANJAVUR
REPAIR,MAINTENANCE OF DG SET,AMF PANELS,SWITCH GEARS AND CONNECTED WORKS AT AIRFORCE STATION THANJAVUR
2022_MES_515335_1
8858/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
THANJAVUR
As per NIT
6 documents required · 6 mandatory
₹500
GARRISON ENGINEER AF THANJAVUR
₹40,000
Yes
1 Jun 2022
25 Mar 2022
26 Apr 2022
25 Mar 2022
25 Apr 2022
11 Apr 2022
Amount
Carrying out 'B'- check to 320 KVA generator set of Kirloskar make once in a period six months or 250 hrs of run whichever is earlier by authorized / OEM including replacement of Engine oil, oil filter fuel filter "O" ring, tappet valve adjustment replacing the tappet gasket water leakage rectification and testing commissioning recommended by OEM for smooth running, complete all as directed by the Engineer-in-Charge. Notes : (i) Engine oil, fuel filter and oil filter shall be measured and paid separately under relevant items.
All as per item No. 1 above but for 250 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 125 KVA DG set of Kirloskar/Cummins make.
All as per item No. 1 above but for 100 KVA DG set of Kirloskar/Cummins make.
All as per item No. 1 above but for 82.5 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 62.5 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 45 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 40 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 30 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 15/20 KVA DG set of Kirloskar make.
All as per item No. 1 above but for 7.5 KVA DG set of Kirloskar make.
Dismantling and taking out blocked / choked radiator assembly including dismantling of rubber hose, fan blade and V belt etc feeding the high pressure air mixed with water alternatively and applying cleaning chemical on the surfaces of radiator and cleaning thoroughly, brazing work for leakage and refixing the same in position complete all as specified.
Dismantling and taking out self starter assembly suitable for 125 KVA to 250 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
Dismantling and taking out self starter assembly suitable for 62.5 KVA to 100 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
Dismantling and taking out self starter assembly suitable for 20 KVA to 45 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, carbon brush, carbon brush assembly, clutch plate assembly and bushes including servicing and refixing to engine complete all as specified.
Dismantling and taking out battery charging alternater assembly suitable for 125 KVA to 250 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicing and refixing complete all as specified.
Dismantling and taking out battery charging alternater assembly suitable for 62.5 KVA to 100 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicing and refixing complete all as specified.
Dismantling and taking out battery charging alternater assembly suitable for 20 KVA to 45 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servicing and refixing complete all as specified.
Dismantling and taking out fuel injector pump assembly suitable for 125 KVA to 250 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector 'O' rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
Dismantling and taking out fuel injector pump assembly suitable for 62.5 KVA to 100 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector 'O' rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
Dismantling and taking out fuel injector pump assembly suitable for 20 KVA to 45 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector 'O' rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
Supply and fix in replacement Self starter assembly 12 Volt suitable for 82.5 KVA to 125 KVA DG Set complete all as Specified.
Supply and fix in replacement Self starter assembly 12 Volt suitable for 30 KVA to 62.5 KVA DG Set complete all as Specified.
Supply and fix in replacement Banded cogged belt (2JAX51-LP-1326) cat part No - 06.032.03.0.00 complete all as specified.
Supply and fix in replacement V Belt (A-47) 1227 length cat part No - 04.140.01.0.00 complete all as specified.
Supply and fix in replacement Fuel pipe (7.5, 14x14B, 700 PB) cat part No - 34.151.04.0.00 complete all as specified.
Supply and fix in replacement Fuel pipe (9.5I.D x 4000L) cat part No - 06.610.03.0.00 complete all as specified.
Supply and fix in replacement Leak off pipe 1000mm long cat part No - 48.112.01.0.00 complete all as specified.
Supply and fix in replacement Silencer assembly cat part No - 48.318.10.0.00 complete all as specified.
Supply and fix in replacement Rubber hose for air intake cat part No - 48.464.02.0.00 complete all as specified.
Supply and pouring KOEL care super genuine oil Cat part No - 82.050.10.0.20 complete all as specified.
Supply and pouring KOEL care Genuine coolant premix Cat part No - 82.020.35.1.01 complete all as specified.
Supply and fixing in replacement 1.1 litre fuel filter kit cat part No - 48.040.01.0.00 complete all as specified.
Supply and fixing in replacement Lub oil filter element cat part No - 06.040.01.0.00 complete all as specified.
Supply and fixing in replacement air filter element suitable for up to 45 KVA DG Set complete all as specified.
Supply and fixing in replacement air filter element suitable for up to 62.5 KVA to 82.5 KVA DG Set complete all as specified.
Supply and fixing in replacement air filter element suitable for up to 100 KVA to 125 KVA DG Set complete all as specified.
Supply and fixing in replacement air filter element suitable for up to 250 KVA DG Set complete all as specified.
Supply and fix in replacement stop solenoid 12V 10 amps single coil 75mm dia cat part No - 02.477.01.0.00 complete all as specified.
Supply and fix in replacement stop solenoid 24V 10 amps single coil complete all as specified.
Supply and fix in replacement generator control unit KG541 level-0 cat part No - D8.048.07.0.00 complete all as specified.
Supply and fix in replacement generator control unit KG934 level-1 cat part No - 2H.894.06.0.00 complete all as specified.
Supply and fix in replacement generator control unit KG545 level-2 cat part No - DV0.901.13.0.00 complete all as specified.
Supply and fix in replacement exhaust fan (450mm) with connector cat part No -D8.079.26.0.00 complete all as specified.
Supply and fix in replacement Kirloskar green AVR for alternator suitable up to 45 KVA DG Set complete all as specified.
Supply and fix in replacement Kirloskar green AVR for alternator suitable for 62.5 KVA to 125 KVA DG Set complete all as specified.
Supply and fix in replacement Kirloskar green AVR for alternator suitable for 250 KVA DG Set complete all as specified.
Supply and fix in replacement 4-20mA lube oil pressure sensor gems make 3100 series cat part No - Dvo.812.11.0.00 complete all as specified.
Supply and fix in replacement Fuel level sensor height 225mm cat part No- DV0.802.15.0.00 complete all as specified.
Supply and fix in replacement Expantion bellow assembly 3" cat part No - 06.602.10.0.00 complete all as specified.
Supply and fix in replacement Thermostat element (74 Deg) WTIL No.DEV358 cat part No - 39.040.09.0.00
Supply and fix in replacement Nozzele leak off pipe cat part No - 06.819.20.0.00 complete all as specified.
Supply and fix in replacement electronic battery charger 12 volt DC 10 amps NHP make cat part No 02.872.18.0.00 complete all as specified.
Supply and fix in replacement electronic battery charger 24 volt DC 10 amps NHP make cat part No 6H.849.09.0.00 complete all as specified.
Dismantling of existing defective Alternator any capacity any make from the foundation, disconnecting the electric connection, coupling pulley, and taking out to work shop cutting down and removing existing burnt out copper windings, cleaning of slots and rewinding with super enamelled solid copper conductor ( winding wire) complete including varnishing, drying, ovening, overhauling, greasing and fixing in the same position, making necessary electric connection and testing of Alternator complete all as specified.
Supply and fix in replacement ATS (automatic transfer switch) 4 pole (TPN) with enclosure with complete protection 100 amps 415 volts 50 HZ AC supply including mounting arrengement and disconnecting / connecting electrically with existing cable including matching with existing generator safety unit complete all as per Havells cat part No IHYFCDE100.
Battery 12V,180 AH mainteance free (replacement warranty period not less than 3 years) complete all as specified.
Battery 12V, 90 AH mainteance free ( replacement warranty period not less than 3 years)complete all as specified
Supply Only Battery Lead 0.5 mtr long.
Supply Only Battery terminal as per sample
Supply and Fix in replacement Indicating lamps 240V LED type for indication of RYB Phases complete all as specified.
Material and labour for Servicing /maint /repair of AMF panel by checking and replacing defective relays, timers, single phase preventer,panel control wiring with suitable size power contactor in AMF panel complete all as specified Note:- relays, timers, contactors single phasing preventor will be measured and paid for separately under relevent items.
Supply and fix in replacement KRB relay card 8 way 20 pin (PCB = relay card - 8 ATS - 12 V DC) cat part No 03.218.13.0.00 complete all as specified.
Supply and fix ion replacement ATS relay card 8 way 20 pin (PCB = relay card - 8 KRB - 12 V DC) cat part No 03.218.14.0.00 complete all as specified.
Supply and fix in replacement Contactor relay Unit of suitable DG Set 24 Volt DC complete all as specified.
Supply and fix in replacement Contactor relay 9/8 pin with base12 Volt DC complete all as specified.
Supply and fix in replacement timer relay ,relay assembly 220 Volt, 6 Terminals complete all as specified.
Supply and fix in replacement HBC fuse link 40 to 160 amps complete all as specified.
Supply and fix in replacement DN open type fuse bases fixed type 100 to 160 amps complete all as specified.
Supply and fix in replacement 400 amps 3.pole power contactor suitable for 250 KVA DG Set AMF panel complete all as specified.
Supply and fix in replacement 250 amps 3 pole power contactor suitable for 125 KVA DG Set AMF panel complete all as specified.
Supply and fix in replacement 200 amps 3 pole power contactor suitable for 82.5 KVA to 100 KVA DG Set AMF panel complete all as specified.
Supply and fix in replacement 95 amps 3 pole power contactor suitable for 30 KVA to 62.5 KVA DG Set AMF panel complete all as specified.
Supply and fix in replacement single phasing preventor (VMR) complete all as specified.
Supply and fix in replacement left / right hand lock with catcher complete all as specified.
Supply, Laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 95 sqmm 3.5 core with all fixing & connecting accessories including taking down old unserviceable cable complete all as specified. Make: Havell’s / Polycab / Finolex)
Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / laying under ground electric cable or for pole etc complete all as specified and as directed. Note :- Mechanical excavation is not allowed in this Stn only manual excavation allowed.
Returning and filling in two parts (i) using riddled soil obtain from excavated soil upto depth of 30 cm (8 cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and directed. Note:- Excavated soil shall be riddled by using sieve to separate composite partricles etc as per IS 1255 1983 and refilling in trenches as in cable cushioning.
Removing surplus soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point all complete as specified and as directed.
Sub class 'B' old size bricks, laid flat dry with width of the bricks laid to the axis of the cable complete all as specified.
Manoprabha Electricals
Ashwarya Enterprises
D Subramani and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .