Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹11.3 LAdmitted-Finance | -31.11% | ₹11.3 L | L1 | Admitted-Finance |
| 2 | L2₹11.9 LAdmitted-Finance WZ 66 SRI NAGAR RANI BAGH NORTH WEST DELHI DELHI 110034 | NORTH WEST DELHI | DELHI | 110034 | -27.10% | ₹11.9 L | L2 | Admitted-Finance |
| 3 | L3₹12.0 LAdmitted-Finance G 15 PKT 2 NARAINA VIHAR NEW DELHI 110028 | NEW DELHI | DELHI | 110028 | -26.88% | ₹12.0 L | L3 | Admitted-Finance |
| 4 | L4₹16.0 LAdmitted-Finance B 1124 SHASTRI NAGAR DELHI 110052 | NORTH | DELHI | 110052 | -2.40% | ₹16.0 L | L4 | Admitted-Finance |
| 5 | Rejected-Technical | - | - | - | Rejected-Technical Not submitted as per NIT |
Tender Value
₹16.4 L
EMD Value
₹32,712
Closing Date
13 Mar 2026, 3:00 pmClosed
EE(E)/ELD-13/DDA
Executive Engineer (E), ELD-13/DDA, Near Hasanpur Bus Depot. Delhi.110092
Operation and Maintenance of Electric Sub-Station, D.G. Set, Submersible pump sets, Sewage pump Sets at Millennium park under HD-I/DDA.
2026_DDA_901476_1
57/EE/ELD-13/DDA/2025-26 (SPLZ)
Open Tender
Electrical Works
365 days
As per NIT documents.
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹32,712
18 Mar 2026
6 Mar 2026
14 Mar 2026
6 Mar 2026
13 Mar 2026
6 Mar 2026
Running, operation and minor maintenance of 11 KV Substation, H.T/L.T. panel, 75 KVA D.G. set, submersible pump set, sewage pump sets and lighting system along with the underground cable, electric control panels and their accessories as per inventory and terms and conditions attached. etc. as reqd.
Providing and replacement of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board, disconnection of old MCCB, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. i/c rebate for dismantle material
4 pole MCCB, 125A, 36kA
4 pole MCCB,250A, 36kA
4 pole MCCB,400A, 50kA
Providing, replacement, testing & commissioning of FASD Motor starter confirming to IS/IEC 60947-4-1 suitable for up to 20 HP pump working on 3 phase 415 V, 50 HZ AC supply, relay range 6-10 A, Overload & Short Circuit Protection, single phase preventor etc complete as required. Dismantling old non-functional starter including rebate for dismantle material.
Providing, replacement, testing & commissioning 63A rating, 4P MCB, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load in the existing MCB DB/Panel complete with connections, testing and commissioning etc. as required. Dismantling old non-functional MCB including rebate for dismantle material.
Dehydration and filtration of 400 KVA 11 KV/415V oil type Transformer i /c Servicing, testing of insulation of HT & LT winding. cleaning of transformer, tightening of all HT & LT Cable, nut bolts etc, testing of transformer like voltage ratio, short circuit, magnetic balance test, oil testing, oil leakage testing and other required test & job etc complete as required as per relevant IS code.
Supply & replacement of following sizes of XLPE insulated & PVC sheathed armoured aluminium conductor power cable of 1.1 KV grade conforming to IS :7098 (Part 1) testing etc complete as reqd. i/c rebate for dismantle material. 3.5 core x 240 sq. mm
Supply & replacement of following sizes of XLPE insulated & PVC sheathed armoured aluminium conductor power cable of 11 KV grade conforming to IS :7098 (Part 2) testing etc complete as reqd. i/c rebate for dismantle material. 3 core 300 sq. mm
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.66 MB
Tendernotice_2.pdf
PDF • 5.59 MB
BOQ_947534.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid