Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.3 LAccepted-AOC 72 USMAN ENCAVE SECTOR O ALIGANJ LUCKNOW 226004 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226004 | L1 | Accepted-AOC L1 | |
| 2 | L2₹17.7 L+₹72,761.40 (4.28%)Rejected-Finance HN 2 PREETI NAGAR PHASE II FAIZULLAGANJ LUCKNOW UTTAR PRADESH 226020 | LUCKNOW | UTTAR PRADESH | 226020 | L2 | Rejected-Finance Being other than L1 |
Tender Value
₹18.9 L
EMD Value
₹37,800
Closing Date
22 Feb 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) BAREILLY
HQ Commander Works Engineers AF Military Engineer Services Bareilly 243002
REPAIR MAINT OF HT DISTRIBUTION SYSTEM AND OTHER ALLIED WORKS AT AF STATION MEMAURA
2024_MES_638429_1
81421/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
MEMAURA LUCKNOW
AS PER NIT
9 documents required · 9 mandatory
₹500
AGE (I) AF MEMAURA
₹37,800
27 Mar 2024
22 Jan 2024
26 Feb 2024
22 Jan 2024
22 Feb 2024
5 Feb 2024
Amount
M & L for periodical service, cleaning and testing various type equipment 33/11 KV equipments in switch yard and other connected works etc complete as specified and directed for the following :-
Line isolator, 33 KV (Horizontal type) :- Servicing of line isolator (Horizontal break outdoor type) including cleaning of contact (knife) by CTC liquid proper oiling greasing on contacts & moving rod / handle for proper function of moveable rod for smooth ON / OFF position and checking,tightining the incoming and outgoing connection (terminal lugs to be replaced if required as per existing size with GI nut bolts,washer) and testing with following (i) Meggar testing between phase to phase & phase to earth shall be carried out etc complete as specified and directed.
HT Potential Transformer (33 KV / 110 Volt) :- Cleaning of bushing and terminal of HT potential transformer 33000 / 110 volts (outdoor type) by CTC liquid and checking of oil level incl rectify the any leakage and proper connection checking and testing with following :- (i) Meggar testing between phase to phase& phase to earth (ii) Checking output voltage (iii) Testing the oil dielectric strength (BD test)
HT Vacuum Circuit Breaker (VCB) 33 KV :- Cleaning & servicing of HT 33 KV vacuum circuit breaker (VCB) 400/630/1250 Amp, 3 phase, outdoor type, checking of each moving parts, spring, charging system, closing & trip coil assembly and proper oiling, greasing and proper adjustment of trip bars, closing bar complete with the following testing :- (i) ON/OFF testing in local and remote position. (ii )Spring charge system testing shall be carried out. (iii) Tripping test in over and earth fault position by external current injecting Kit on Primary Secondary side. (iv) Meggar testing between phase to phase and phase to earth in ON / OFF position both.
HT 33 KV Current Transformer (CT) :- Cleaning of bushing and terminal by CTC solution of CT rating 100 / 5 + 5 + 1 Amp rating, 33 KV and checking of oil level , rectify the leakage if any and testing the oil strength (BD test) and proper connection checking and testing with following :- (i) Meggar testing between phase to phase& phase to earth
33 KV VCB Control & Relay Panel :- Cleaning of control & relay panel inside & outside by CTC solution and checking all the control cable connection of CT, PT, VCB, meters, trivector meter transformer complete all as specified and directed.
Transformer 33 / 11 KV, 2 MVA :- Cleaning of power transformer 33 /11 KV, 2 MVA, outdoor type externally including all accessories (such as conservator tank, marshaling box, bushings, bucholz relay Radiator, bushings oil level indicator,rectyfy the leakage if any) complete and checking the incoming and outgoing terminal connection complete with the following testing :- (i) Transformer oil dielectric strength (BD voltage) test. (ii) Buccholz relay Alarm & trip testing. (iii) Oil temperature Alarm & trip testing. (iv) Winding temperature Alarm & trip testing. (v) Meggar testing between HV to earth. (vi) Meggar testing between LV to earth. (vii) Meggar testing between HV to LV . (viii) Earth resistance test of transformer neutral. (ix) Earth resistance test for body earthing. (x) Replacement the all packing in marshalling box (if required)
Transformer 33/ 0.433 KV, 100 KVA (Station Transformer) :- Cleaning of station transformer (outdoor type) externally including all accessories and checking of all incoming & outgoing connection and rectify the leakave if any incl with the following testing :- (i) Transformer oil dielectric strength (BD) test. (ii) Meggar testing between HV to earth. (iii) Meggar testing between LV to earth. (iv) Meggar testing between HV to LV . (v) Earth resistance test of transformer neutral. (vi) Earth resistance test for body earthing.
D.O. Fuse :- Cleaning of HT insulators & checking the incoming & outgoing joint connection and testing with the following :- (i) Meggar testing between phase to phase& phase to earth.
M&L for painting of 33 /11 KV MRS switch yard MS structure with one coats of asian make aluminum paint after cleaning and making good surface for panting of the following structure:- (a) Bus bar Gantry:- Painting of busbarGantry of MS channel (I Section) size 150 mm x 75 mm x 5.5 mtr long - 12 Nos (b) Lightening arresters (LA):- Painting of lightening Arresters of MS channel (C-section) of size 100 mm x 50 mm x 3.0 mtr long -02 Nos with MS Angle iron 50x 50 x 2.65 mtr long -02 Nos complete - 03 Job (c) Line isolator (LI):- Painting Line isolator of MS channel ( C-section) of size (125 mm x 65mm x 2.50 mtr long -04 Nos) and ( 100 mm x 50 mm x 1.00 mtr -03 Nos) with MS flat bracing (50mm x 50mm x 0.30 mtr -6 Nos) and MS Angle iron ( 50 mm x 50 mm x 2.65 mtr long-02 Nos) complete -09 Job (d) Horn Gap fuse:- All as per item No 2 (c) here in before. Qty - 03 Job (e) Pin insulator supporting structure :- All as per item No 2 (c) here in before. Qty - 03 Job (f) PT supporting structure :- All as per item No 2 (c) here in before. Qty - 04 Job (g) VCB / CT stand :- Painting of CT VCB structure made out of MS channel ( C-section) of size ( 65 mm x 65 mm x 1.10 mtr long- 04 Nos) and ( 100 mm x 50 mm x 0.90 mtr long- 03 Nos) and ( 100 mm x 50 mm x 1.90 mtr long- 04 Nos) and Angle iron of size ( 50 mm x 50 mm x 1.10 mtr -04 No) ( 50 mm x 50 mm x 0.70 mtr long- 06 Nos) and (50 mm x 50mm x 0.25 Mtr long - 05 Nos) complete -03 Job complete
M & L for RCC cable duct cover with 8mm dia MS bar as required at site incl 12 mm dia MS bar moveable handle both side of cable cover for lifting etc as specified and directed.
Disconnecting the all electrical connection from battery bank and taking out unserviceable part & supply and fix new parts as required incl serviceing, connecting ,tighting,greasing,wiring & testing as required voltage including cleaning and painting with one coat of synthetic enamelled paint complete as directed .Note - if any parts not included in the specification of works, contractor will provide own cost and deem to quoated cost if requied for functioning of equipment :
Supply only voltmeter as per existing size and capcity
Supply only Ammeter as per existing size and capacity
Supply only slector switch as per existing make and capacity
Supply only 2 volt 100 AH maintenance free battery as per existing make/model/capacity etc
Supply and fix in repair battery charger suitable for 30 volt as per existing make/model/capacity etc complete as specified and directed
Supply and fix in replacement battery bank suitable for controlling 30 volts DC supply of VCB incl battery 100 AH 2 volts -15 Nos etc complete as specified and directed
Supply and fixing in repair hooter for announciator panel as per existing make/model/capacity complete all as specified and directed.
Supply and fix in repairs remote switch suitable for 33 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs heater switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
S&F Ammeter digital type 100A/5A or 60A/5A CTR of 150mm x 150mm including taking out of old unserviceable ammeter complete all as specified and directed.
S&F Voltmeter digital type 15 KV of 110/30 V PTR. Size 150mm x 150mm including taking out old unserviceable voltmeter complete all as specified and directed.
S&F indicator light (LED type) suitable to operate on 30 volts DC/110 V AC having two covers red/green/blue for HT VCB panel including taking down old complete all as specified and directed.
Servicing and calibration to 11KV HT VCB (SF-6 type) of RMU complete with the following:- Make of VCB/RMU: ABB/Siemens (a) Caliberation of relay any type/make/model on HT panel (2 Nos over current & 01 No earth fault relay) as per load or as directed by Engr-in-charge and cleaning the contact (NO+NC) by CTC solution and adjust the contact and testing the relay by testing kit etc complete all as specified and directed. (b) Opening the HT panel bus bar and cleaning the bus bar and closed the whole by putty and other material in all respect etc complete as specified and directed Note for (a) & (b):- (i) Replacing new items shall be measured and paid separately as supply only. (ii) Contractor shall submit the connected test report to Engr-in-charge
(a) Supply only S series Bushing
(b) Supply only O Ring for S series Bushing
(c) Supply only SF6 Gas Cylinder (3.75 kg/cyl)
Excavation in trenches/ foundation in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for HT under ground cable/pole foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed.
M&L for sand cushioning to U/G cable in layers of 23 cm thick ( 8 Cm before laying the cable and 15 Cm thick after laying the cable) in trenches complete all as specified and directed. Note :- Only Puned down volume shall be measured.
Supply and laying un-reinforced precast concrete cable cover, class HV, Type I, flat size 300 mm x 180 mm x 40 mm laid dry for protection of UG cable complete all as specified and directed
Dismantling / Taking out unserviceable HT cables for replacement of any size from any position i.e ground / walls / poles / culverts etc complete with protection pipe all as specified and directed . ( Note : Earth work shall be measured and paid separately)
Supply, laying, jointing and testing of HT XLPE cable 3 core, 11000 volt screened, PVC bedded "Earthed grade" insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system confirming to IS-7098(Part-I) 1977 and part-II of 1985 laid in pipe /ducts/trenches, under floor and road or fixedd to wall etc complete cross-sectional area of cable 240 sqmm 3 core, all as specified and directed .
Supply, laying, jointing and testing of HT XLPE cable 3 core, 11000 volt screened, PVC bedded "Earthed grade" insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system confirming to IS-7098(Part-I) 1977 and part-II of 1985 laid in pipe /ducts/trenches, under floor and road or fixedd to wall etc complete cross-sectional area of cable 185 sqmm 3 core, all as specified and directed .
Supply, laying, jointing and testing of HT XLPE cable 3 core, 11000 volt screened, PVC bedded "Earthed grade" insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system confirming to IS-7098(Part-I) 1977 and part-II of 1985 laid in pipe /ducts/trenches, under floor and road or fixedd to wall etc complete cross-sectional area of cable 95 sqmm 3 core, all as specified and directed
M & L in replacement of GI tubing light grade for passing through cables under the floor ,along the wall or along the pole of 80 mm bore and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified.
Material and labour for lightning arrester 11000 volts non linear resister type conforming to IS-3070 part-I, line discharge class-2, nominal discharge 10 KA and high discharge 65 KA assembly complete suitable for 11 KV including all clamps, nuts, bolts and washers and connecting to earth with 4 mm dia GI wire all as specified and directed.
M&L in replacement of indoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M&L in replacement of indoor end terminal joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 185 Sqmm, 3 Core, all as specified and directed. ( Make : 3M/Denson/Raychem )
M&L in replacement of indoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 240 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M&L in replacement of outdoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 185 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M&L in replacement of outdoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 240 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M&L in replacement of straight through joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95 Sqmm 3 Core all as specified and directed. (Make : 3M/Denson/Raychem
M&L in replacement of straight through joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 185 Sqmm 3 Core all as specified and directed. (Make : 3M/Denson/Raychem
M&L in replacement of straight through joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 240 Sqmm 3 Core all as specified and directed. (Make : 3M/Denson/Raychem
Boring holes horizontally under road without damaging the surface of road ( minimum 1.0 Metre below the road surface with the help of GI tubing not exc 80 mm bore(dia) for passing UG cable, complete all as specified and as directed.( Note : - GI Pipe laid will be measured and paid separately under appropriate item)
Supply, installation, commissioning and testing of outdoor type switch air break gang operated suitable for horizontal mounting rotating type, HT 33000 volts grade triple pole with 09 insulators, 400 amp capacity current rating complete having post insulator type on channel (two insulator for one phase) mounted on steel frame mechanically operated mechanism from ground level consisting of rod of 25 mm bore GI pipe, light grade of suitable length worked from ground level with locking arrangement fixed with flat iron clamp 50X6 mm and MS channel of suitable size & length for fixing GO/DO including bolts, nuts and washers complete all as specified and directed.
Supply, installation, commissioning and testing of outdoor type switch air break gang operated suitable for vertical mounting rotating type, HT 11000 volts grade triple pole with 09 insulators, 400 amp capacity current rating complete mounted on insulators and steel frame mechanically operated mechanism from ground level consisting of rod of 25 mm bore GI pipe, light grade of suitable length worked from ground level with locking arrangement fixed with flat iron clamp 50X6 mm and MS channel of suitable size & length for fixing GO/DO including bolts, nuts and washers complete all as specified and directed.
Supply & fixing DO fuse assembly, triple pole mounted on porcelain HT insulator 6 Nos and MS galvanised steel frame rating upto 400 Amp, 11000 Volt, post insulator type on channel (two insulator for one phase) complete with expulsion type fiberglass fuse carrier barral type and including DO fuze and electrical connections compleate all as specified and directed by Engineer-in-Charge. (Make : PACTAILLED/JAIPURIA/ RAYCHEM RPG).
Supply and fix earth continuity conductor or main earthing lead fixed to wall or on pole or any other indicated situation as GI strip of size 25x4 mm connected to test point complete all as specifie and as directed
Dehydration and filtration of existing transformer oil of transformers capacity ranging from 100 KVA to 500 KVA ( 1/0.433 KV ) on site at different locationswithout disturbing the power supply system with filtration machine and heating systemin order to achieve Di-electri strength of oil 40 KV minimum 2.5 mm gap complete all as specified and as directed. Note : (a) Testing of transformer HT switch gear oil before & after dehydration shall be carried out as directed (b) The unit of payment under this term shall be per liter of oil meant for all process to the entire completion of jobs
Supply and filling up of Transformer oil conforming to as per IS:335-1993 in topping up/replacement up to desired level of transformer oil capacity complete all as specified and directed. ( Note : Dielectric strength of oil should not be less than 50 KV complete all as specified and directed.) Make : Power Oil / Castrol/Savita/Gulf or as approved by AGE(I)
Supply and replacing silica gel in crystal form of breather assembly of transformer capacity upto 2000 KVA at installed site complete all as specified and directed.
Repair/servicing to transformer at site of capacity 100 to 250 KVA installed on plinth/pole mounted structur by opening top cover & replacing unserviceable spares/components of transformer ,without lifting core assembly reassembling after repair & testing complete all as specified and directed
Repair/servicing to transformer at site of capacity 315 to 500 KVA installed on plinth/floor mounted structur by opening top cover & replacing unserviceable spares/components of transformer ,without lifting core assembly reassembling after repair & testing complete all as specified and directed
Supply only ceramic Bush insulator on LT side as per existing size,shape and specification for capacity 200 to 300 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only cork sheet gasket ( set of four) for ceramic bushing on LT side as per existing size,shape and specification for capacity 200 to 300 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only cork sheet gasket ( set of four) for ceramic bushing on LT side as per existing size,shape and specification for capacity 200 to 315 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only ceramic Bush insulator on HT side as per existing size,shape and specification for capacity 200 to 300 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only top cover gasket as per existing size,shape and specification for capacity 200 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only top cover gasket as per existing size,shape and specification for capacity 315 to 500 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only breather assembly as per existing size,shape and specification for capacity 200 KVA ,11/0.433 KV transformer complete all as specified and directed
Supply only breather assembly as per existing size,shape and specification for capacity 315 to 500 KVA ,11/0.433 KV transformer complete all as specified and directed
Servicing of HT (11KV ) switchgear panel , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components, through authorized representative service centre of VCB manufacturer channel partner /OEM or UPPCL approved vendor for VCB repairing agency , Testing for smooth operation manual/ remote after caliberation of relay and resetting & generation of testing report by the primary injection set For 11KV VCB for OC/EF ,parameter of relay setting ,including writing of MES No. complete , all as specified and directed by Engr-in-Charge. Note: Worn out minor parts shall be deemed to be included in unit rate.
Servicing of HT (33 KV ) panel / VCB , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components, through authorized representative service centre of VCB manufacturer channel partner /OEM or UPPCL approved vendor for VCB repairing agency , Testing for smooth operation manual/ remote after caliberation of relay and resetting & generation of testing report by the primary injection set For 33 KV VCB for OC/EF ,parameter of relay setting ,,including writing of MES No. complete , all as specified and directed by Engr-in-Charge. Note: Worn out minor parts shall be deemed to be included in unit rate.
Supply only spring charging motor of 230 volts 0.25 HP, 8000 RPM of 11 KV VCB's type VE -12, 30/110 volts (Make - L&T/ Crompton Greaves or equivelant).
Supply & fixing in replacement of Current transformer (CT) of 11 KV , single phase indoor type, CT ratio 60/1 Amp , STC 26.3 KA or more for 1 sec ,Class PS, Insulation class B complete all as specified and as directed. Make: Jyoti/Pactailled or equivalent.
Supply and fixing in replacement of electronic 3 phase over current and earth fault (IDMT) relay installed on existing panel or separate enclosure, with connecting, internal control wiring , testing complete all as specified and directed ( MAKE :- L&T Model No- MC61A or equivalent )
Supply and fixing in replacement of electronic 3 phase over current and earth fault (IDMT) relay installed on existing panel or separate enclosure, with connecting, internal control wiring , testing complete all as specified and directed ( MAKE :- L&T Model No- MC61A-nX or equivalent )
Supply and fixing in replacement of electronic 3 phase over current and earth fault (IDMT) relay installed on existing panel or separate enclosure, with connecting, internal control wiring , testing complete all as specified and directed ( MAKE :- Secure Model No- Maxchek 400 or equivalent )
Supply and fixing in replacement of 3 phase trip circuit supervision relay type VAX MK. II installed on existing panel or separate enclosure, with connecting, internal control wiring , testing complete all as specified and directed ( MAKE :- AREVA or equivalent )
Supply and fixing in replacement of electronic auxiliary relay type AR114X2 voltage 24 V DC for 33 KV panel ( Make - EASUN or equvalent in Schnieder / L&T)
Supply and fixing in replacement of electronic auxiliary relay type B24 voltage 24 V DC for 33 KV panel ( Make: EASUN or equvalent in Schnieder / L&T)
Supply and fix in repairs relay suitable for earth,over current, differencial and bchholz Alarm, Winding & Oil temp alarm suitable for 2 MVA 33/11 KV Transformer as per existing make/model etc complete all as specified and directed.
Notes for Ser item No. 60 to 68 above:- (i) Tenderer shall be checked the existing VCB's and shall be taken all the details of existing defective one before order the materials. (ii) New items shall be match with the existing system in any cases. (iii) Any minor adjustment /modification for the fixing the item if required at site contractor shall be carried out at site without any extra cost.
Supply & fixing in replacement of Voltage transformer (VT) of rated voltage 11 KV , three phase indoor type, ratio 11000/110 volts , VA/PH : 200, IL : 12/28/75 kVp, class 1, Insulation class B, 50 Hz , complete all as specified and as directed. (Make: Pragati Electricals or equivalent)
Supply & fixing in replacement of Voltage transformer (VT) of rated voltage 33 KV , single phase outdoor type, ratio 33KV/√3/110V/√3 , Burden 100 VA, IL : 36/70/170KV (P), Class50 Hz , Star Star complete all as specified and as directed. (Make: Everest or equivalent)
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600x 6 mm thick buried in ground vertically to a depth n.less than 2.25 mtr below normal ground level connected to galvanized steel strip 25 x 4 mm earth lead by means of bolts, nuts and washers made of galavanised iron or steel earth strip protected by 40 mm bore light grade GI pipe and connected for body earthing of feeder pillar box all as specified and directed incl PCC work as per sketch No 3 of SSR Part -I (2009) pit cover slab of size 300x300x50 mm with handle as shown in drawing funnel, wire mesh 20 mm dia GI pipe medium grade for watering, charcoal and slat in alternate layers incl necessary earth pole and excavation in hard/dense soil and removal etc incl testing complete.
Surface excavation n.exc 30cm deep, averaging 15 cm deep and getting out in soft/loose soil, complete all as specified and as directed
Excavation in post holes (or similar holes) each not exc 0.5 cum , getting out, returning, filling in and ramming earth or broken rubble mixed with earth around , in layers not exceeding 25 cm watering and removing surplus soil to a distance not exc 50 m and making good surface in soft/loose soil complete all as specified and directed.
Demolition of concrete of any description and in any position or not other wise spccificly provided for complete all as specified and as directed
M&L for PCC 1:3:6 type C2 (using 40mm graded stone aggregates) as in foundation, filling and mass concrete complete all as specified and as directed..
Dismantling posts or struts (wood, steel or R.C.C.) any section, including taking out embedded portion and making good disturbed ground complete all as specified and as directed
S&F for angle or tee section, fixed independent without connecting plate etc made to shape required as in fencing post, conforming to Fe.290.Gde-E-165 complete all as specified and as directed
Dismantling structural steel work including doors, gates but excluding framed truss etc.complete all as specified and as directed
S&F mild steel framed work conforming to Fe.290.Gde-E-165 as in gates, including pintle hinges stops, hand made sliding bolt ,including grills, gratings etc with end of bars shouldered and/or riveted or gorged in to spikes, etc. complete all as specified and as directed.
Dismantling chain link fencing for mesh fixed with steel fillets all as specified and directed.
S&F chain link fencing of mesh size 100mm x 100mm (design of mesh ) made of GI wire not less than 4mm dia including line wire fixed to any type of standard rails, straining bolts etc, including provision of binding wire complete all as specified and as directed.
Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and as directed
S&F mild steel flat iron conforming to Fe-290 Gde E-165 as in band, straps, stiffeners, etc. including necessary making holes for fixing bolts, etc. for securing chain link fencing complete all as specified and as directed.
S&F 10 mm dia mild steel round bar ,cut to size bent to shape required, as in straining bars, etc. for securing chain link fencing, conforming to Fe-410 grade complete all as specified and as directed.
S&F mild steel bolts (machine made) with hexagonal or square heads at one end and screwed the other, to be fitted with washer and one hexagonal or square nuts of dia of shank 10mm and length exc. 5 cm and n.exc 10 cm long complete all as specified and as directed.
Mild steel plates, plain or chequered, Fe 410-W(Gde-E-250) quality-A 5mm thick or over inthickness in available sizes complete all as specified and as directed
M&L for preparation of new or previously untreated steel surfaces of any description, over 10cm width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for preparation of old painted steel or iron surfaces of transformers of 100 to 500 KVA ,11/0.433 KV capacity transformer by scrapping with steel wire brush /scrapper emery paper etc and applying one coat of synthetic enameled smoke grey/exising colour( painting shall be done by spray machine) including writing of SM No , MES No at prominent place/location of transformer with black synthetic enamel paint in white back ground complete all as specified and as directed.
Demolition of brick wall built in cement mortar including all quoins,arches,pillars etc excluding precast concreta articles complete all as specified and as directed
M&L Brick work with sub class 'B' bricks,old size brick, straight or curved on plan to any radius in half brick wall, built in CM 1:4 all as specified and as directed.
M & L for 15 mm thick rendering in cement morter (1:4) on fair face of brick or concrete surface finished even and fair all as specified and as directed.
M&L preparing surfaces on wall plastered new surafaces and applying two coats of white wash complete all as specified and as directed
S&F HT 11 KV insulation eiectrical rubber mat 2 mm thickness as per IS: 15652:2006 Class A complete all as specified and as directed
Detection of pin point fault in HT cable (burried in ground/under road/path up to depth of 1.5 m) by cable fault locating machine comprising impulse generator,acoustic fault locator and reflectometer (laptop based) complete all as specified and as directed by Engr-in-Charge. Notes- (i) Cable fault locating machine to be arranged at site with in 12 hrs after intimation (ii) Earth work will be measured seperatly. (iii) Cost of transpotation in unit rate is deemed to be included.
S&F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150 mm dia, Shank dia 25mm or more, min creepage distance 840mm suitable for 33000 volts grade complete all as specified and directed.
Ajanta Associates
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .