| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.5 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹32.0 L+₹4.1 L (14.9%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹35.8 L+₹8.0 L (28.7%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹36.5 L+₹8.7 L (31.2%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹39.1 L
EMD Value
₹78,200
Closing Date
4 Dec 2023, 6:00 pmClosed
GE BHOPAL
GE BHOPAL BAIRAGARH BHOPAL
REPAIR REWIRING OF INTERNAL ELECTRIC WIRING LIGHT FITTING MAINT OF SUMMER AND COOLING APPLIANCE AT TECH AREA AND REPAIR AND REPLACEMENT OF EXTERNAL WATER SUPPLY PUMP AND REWINDING OF MOTORS AT ADMIN AREA AND TECH AREA CPE ITARSI UNDER GE BHOPAL
2023_MES_627342_1
8223/E8
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
ITARSI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE BHOPAL
₹78,200
Yes
14 Feb 2024
7 Nov 2023
6 Dec 2023
7 Nov 2023
4 Dec 2023
22 Nov 2023
Amount
Note :(i) Please refer Sch A/ BOQ Notes before quoting the tender for all phases/ items mentioned below. (ii) Amount of Schedule of credit shall be deducted offline
Day to day maintenance of GI/CI/DI pipe line various sizes for minor reparing/rectifing and attending the complaint of pipeline leakage/ float valve repairs of followings dia by highly skilled tradesman as required at site to complete job with stuiplated time without hampering water supply and making it functional with and including all necessary T&P as required complete all as specified and directed. Note : - (i) The quoted rate are exclusive of excavation and new GI fittings of suitable size. (ii) The tradesman shall report to E/M complaint cell of concern JE/AGE ITARSI daily at 8.30 am to take complaints from concern JE E/M. The complaint must be attended on same day in stuiplated time period and the complaint slip duly singned by the user shall be returned back at the complaint cell. (iii) Urgent complaint will be required to be completed in holiday or sunday. (iv) New GI fittings of suitable size, yarn and safeda/ white lead measured and paid separetally.
15 mm dia
20 mm dia
25 mm dia.
40 mm dia.
50mm bore
80 mm bore
100 mm bore
150 mm bore
200 mm bore
S&F 25 mm GI socket complete alll as specified and directed.
S&F 25 mm GI Elbow complete alll as specified and directed.
S&F 25 mm GI Union complete alll as specified and directed.
S&F 25 mm GI Tee complete alll as specified and directed.
S&F GI reducer 25 x 20 mm complete alll as specified and directed.
S&F GI Nipple 25 x 100 mm complete alll as specified and directed.
S&F 25 mm tank Nipple complete alll as specified and directed.
S&F 20 mm GI Union complete alll as specified and directed.
S&F 20 mm GI Tee complete alll as specified and directed.
S&F GI reducer 15 x 20 mm complete alll as specified and directed.
S&F GI Nipple 20 x 100 mm complete alll as specified and directed.
S&F 20 mm tank Nipple complete alll as specified and directed.
S&F 15 mm GI Union complete alll as specified and directed.
S&F 15 mm GI Tee complete alll as specified and directed.
S&F GI reducer 15 x 25 mm complete alll as specified and directed.
S&F GI Nipple 15 x 100 mm complete alll as specified and directed.
S&F 15 mm tank Nipple complete alll as specified and directed.
S&F 20 mm NRV complete alll as specified and directed.
S&F 25 mm NRV complete alll as specified and directed.
S&F 15 mm NRV complete alll as specified and directed.
S&F teflon tap complete alll as specified and directed.
S&F Lead material complete alll as specified and directed.
S&F lead wool complete alll as specified and directed.
Testing of collected water sample from NABL /approved lab from as per IS 10500:2012 at main filter pump house Itarsi complete all as specified and directed.
Table 1 Organoleptic and physical parameters
Table 2 General parameters concerning subtancesundesirable in excessive amounts
Table 3 Parameters concering toxic substance
Table 4 Parameters concering radioactive substance
Table 5 Pesticide Residues limit and test method
M&L for taking out of defective submersible pump set of capacity 10HP/12.5 HP of any make with column assembly of any size/capacity including disconnecting electrical and water line connection, lifting in with the help of chain pulley, clamp, tripod etc., and repairing, lowring and refixing the same after making it serviceable, rethreading of column pipe and replacement of worn out nuts, bolts washers, transportation of same from site to workshop and back etc, including test and commisionnig complete all as specified and directed. Note: (i) Defective spares parts for pump and column assembly shall be measured and paid separetely under relavent item. (ii) Cost of detaching the pump and motor removed and refixing after carry out the necessary repair shall be deemed to be included in the unit quated rate. (iii) After taking out submersible pump set the bidders shall cover the tube well immediately wihout any delay with cover/cap to avoid any accident and cots of covering the tube well shall be deemed to be included in the unit quated rate.
M&L for rewinding the submersiable motor of any make of capacity 10 to 12.5 HP with PVC insulated water proof conductor copper wire of best quality of existing gauge and turn with minimum weight of 1.2 Kg of copper wire per HP of motor and reassembling after replacement of bush, bearing sleeves, grinding as required and polishing of rotor shaft, repair to starter etc., and refixing the same in existing position, test and commisionnig including dismantling defective submersiable motor of any make complete all as specified and directed. Note:- Bush/bearing/sleeves/thrust plate shall be measured and paid separately under relavant items.
Supply only bush/bearing (gun metal) of suitable size for 10/12.5 HP for the submersible motor complete all as specified and directed.
Supply only stainless steel sleeve of suitable size for 10/12.5 HP complete all as specified and directed.
Supply only thrust plate set 10/12.5 HP complete all as specified and directed.
Supply only thrust plate bearing housing complete all as speicified and directed.
Supply only rubber oil seal complete all as specified and directed.
M&L for taking out of defective submersible pump set of capacity 7.5 HP of any make with column assembly of any size / capacity including disconnecting electrical and waterline connection, lifting with the help of chain pulley, clamp, tripod etc., and repairing, lowering and refixing the same after making it serviceable, rethreading of column pipe and replacement of worn out nuts, bolts washers, transportation of same from site to workshop and back etc., including test and commisionnig complete all as specified and directed. Note: (i) Defective spares parts for pump and column assembly shall be measured and paid separetely under relavent item. (ii) Cost of detaching the pump and motor removed and refixing after carry out the necessary repair shall be deemed to be included in the unit quated rate. (iii) After taking out submersible pump set the bidders shall cover the tube well imediately wihout any delay with cover/cap to avoid any accident and cost of covering the tube well shall be deemed to be included in the unit quated rate.
M&L for rewinding the submersiable motor of any make of capacity 7.5HP with PVC insulated water proof conductor copper wire of best quality of existing gauge and turn with minimum weight of 1.2 Kg of copper wire per HP of motor and reassembling after replacement of bush, bearing sleeves, grinding as required and polishing of rotor shaft, repair to starter etc., and refixing the same in existing position, test and commisionnig including dismantling defective submersiable motor of any make complete all as specified and directed. Note:- Bush/bearing /sleeves/thrust plate shall be measured and paid separately under relavant items.
Supply only bush/bearing (gun metal) of suitable size for 7.5 HP for the submersible motor complete all as specified and directed.
Supply only stainless steel sleeve of suitable size for 7.5 HP complete all as specified and directed.
Supply only thrust plate set for 7.5 HP complete all as specified and directed.
Supply only thrust plate bearing housing for 7.5 HP complete all as specified and directed.
Supply only rubber oil seal for 7.5 HP complete all as specified and directed.
Dismantling and opening of defective submersible pumping set having capacity up to 12.5 HP any stage/discharge and dismantling all spare parts by opening studs with machine/lathe ork/grinding/polishing and fitting of all spare parts and re-assembling installation in position after necessary repair / replacement of studs, nuts, bolts etc., including refixing the same after making it serviceable in its existing position including test and commisioning complete all as specified and directed. Note:- Spareparts shall be measured and paid separately under respective items.
Supply only submiersible pump bowl assembly of gun metal impeller complete all as specified and directed.
Supply only submiersible intermediate bowl complete all as specified and directed.
Supply only submiersible bowl bush (rubber) complete all as specified and directed.
Supply only submiersible bowl bush (gun metal) complete all as specified and directed.
Supply only submiersible cast iron impeller seal ring (neck ring) complete all as specified and directed.
Supply only submiersible stainless steel running sleeves complete all as specified and directed.
Supply only submiersible impellor locking keys stainless steel complete all as specified and directed.
Supply only submiersible pump shaft 25.40 mm dia of any capacity complete all as specified and directed.
Supply only rinning strainer for pump complete all as specified and directed.
M&L for taking out monoblock/centrifugal/non clogging motor set of capacity 3 H.P to 7.5 HP from position and transportation of same from site to work shop and back, dismantling of cable/ pipe connection and re-installation of motor set after necessary repairing on the existing foundation and making electrical connections including necessary nuts, bolts, washers etc., required at site of work, complete all as specified and directed. Note : All spares parts required shall be measured and paid separately.
Supply only ball bearing of suitable size complete all as speicified and directed.
Supply only rubber washer of suitable size complete all as specified and directed.
Supply only packing sheet of suitable size complete all as specified and directed.
Supply only bush cover of suitable size complete all as specified and directed.
Supply only mechanical Seal of suitable size complete all as specified and directed.
Supply only circlips Clamp of suitable size complete all as specified and directed.
M&L for taking out centrifugal pump of capacity 3 HP to 7.5 H.P and transportation of same from site to workshop and back, dismantling of cable/ pipe connection and reinstallation of pumpset after repair on the existing foundation and making electrical connections complete all as specified and directed. Note : All spares parts required shall be measured and paid separately.
Supply only pump overhauling GM bushes ,shaft rematteling making key gland packing,including all engineering work complete all as specified and directed.
Supply only pump shaft stainless steel of same make and model duly grinded/polished complete all as specified and directed.
Supply only earing of suitable size of pump complete all as specified and directed.
Supply only plugging leaks in casing by welding the same incl grinding for smooth surface complete all as specified and directed.
M&L for rewinding of damaged/burnt motor of capacity 3 H.P to 7.5 H.P any type by using enamelled copper wire of superior quality of existing grade and same nos. of turns including varnishing ‘F’ class insulation and drying in heat chamber / oven including all other material / fittings and testing on completion, complete all as specified and directed.
S&F in replacement of CI non return valves ISI marked flanged class 1.0 PN with by-pass arrangement and necessary bolts and nuts of suitable size with and including rubber gasket for flanged joints and testing including taking out old unserveceable non-return valves complete all as specified and directed for following sizes :-
100mm bore
80mm bore
S&F in replacement of CI sluice valves ISI marked flanged class 1.0 PN with necessary bolts and nuts of suitable size with and including rubber gasket for flanged joints and testing including taking out old unserviceable sluice valves complete all as specified and directed for following sizes :-
200 mm bore
150 mm bore
100 mm bore
80 mm bore
S&F in replacement of gun metal globe, ball or gate valve class-2 with iron wheel head screwed both ends for pipes of following sizes including taking down old unserviceable gatevalves complete all as specified and directed:-
50 mm bore
40 mm bore
25 mm bore
20 mm bore
S&F in replacement of cast iron foot valve, conforming to IS-4038, suitable for pipes of following sizes including taking down old unserviceable foot valve complete all as specified and directed :-
63 mm bore
50 mm bore
Excavation in trenches not exceeding 1.5 mtr wide and n.exc 1.5 mtr in depth for soft/loose soil for laying of pipe lines and getting out old pipes complete all as specified and directed.
Returning and filling in, including spreading, levelling watering and well ramming in layers not exc 25 cm in soft / disintegrated rock complete all as specified and directed.
Removal of excavated surplus spoil at a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr from the starting point complete all as specified and directed.
Taking up or down GI tubing and connection including cleaning for refixing and removal to site of following sizes including taking down old unserviceable gate valves complete all as specified and directed :-
100 mm bore
80 mm bore
50 mm bre
40 mm bore
25 mm bore
20 mm bore
S&F in replacement of galavised iron tubing, medium grade, with all fittings such as sockets, bends, elbows, tees, short pieces, connectors, back nuts, diminshing pieces, caps, plugs and unions etc., laid in trenches / fixed to walls and ceilings or laid in floors, complete all as specified and directed of the following description :-
100 mm bore
80 mm bore
50 mm bre
40 mm bore
25 mm bore
20 mm bore
Taking up or down CI/DI water mains pipe (including all fitting) of following sizes with spigot and socket/both side flanged ends and lead joints including burning out joints and recovering lead complete all as specified and directed :-
200 mm bore
150 mm bore
100 mm bre
80 mm bore
Refixing CI pipe including fittings with spigot and socketed end/ flanged end, centrifugally cast laid in trenches after cleaning internally and externally, drawing out forigen material/rust complete up to satisfaction of Engr-in-Charge of following sizes with and including new titon joint for fixing of pipe:- Note :- (i) Earth work, joints and CI specials/fittings of the pipes shall be measured and paid separately under appropriate item.
80mm bore
100 mm bore
150 mm bore
200 mm bore
S&F in replacement of cast Iron pipe with the follwing sizes with spigot and socket/both ends flanged centrifugally cast class LA , in any length laid in trenches/over head tank with all fittings complete all as specified and directed of the following description:-
200 mm bore
150 mm bore
100 mm bre
80 mm bore
Supplying, laying and jointing DI iron pipes SS class K -7 of standard length, internal cement mortar coating an external surface with bituminious paint of the following sizes ISI marked including nut bolt, packing material etc and making the joint leak proof complete all as specified and directed.(Make : Tata/ Jindal/Electrosteel) Note : - (i) Earth work, joint and CI/DI specials/fittings of the pipes shall be measured and paid separately under appropriate items of schedule.
100 mm bore
150 mm bore
200 mm bore
M&L in replacement of lowering GI pipe heavy class of size 50mm dai bore with long GI socket in 3 meter length incudling taking down old GI Pipe complete all as specified and directed. Make- Jindal/Tata/Swasticcomplete. Note- All T&P required for execution will we arranged by Contractor.
M&L in replacement gland for pump set capacity 2 HP to 10 HP complete all as specified and directed.
S&F in repairs 15 mm dia stop valves, cast copper alloy, screwed down high pressure with crutch or buterfly handle, screwed both ends for iron pipe or union and fixed including taking down complete all as specified and directed.
S&F in repairs CI air release valve, 80 mm bore, ISI marked , rubber gasket , mild steel nuts, and washers including testing and taking down existing air release valve complete all as specified and directed.
M&L for cleaning RCC overhead water storage tank of capacity 50000 gallon, taking out sludge and depositing the same outside the cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation, remve honeycomb on the wall of OHT if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes and white wash to be carried out in inner side of the tank and also writing the date of cleaning and capacity of the tank using synthetic enamel paint on black ground and white paint complete all as specifed and directed. Note : The work will be completed within 24 hours after that the water will be supplied to the users.
M&L for cleaning RCC overhead water storage tank of capacity 30000 gallon taking out sludge and depositing the same outside the cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation, remove honeycomb on the wall of OHT if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes and white wash to be carried out in the inner side of the tank and also writing the date of cleaning and capacity of the tank using synthetic enamel paint on black ground and white paint complete all as specifed and directed. Note : The work will be completed within 24 hours after that the water will be supplied to the users.
M&L for cleaning RCC overhead water storage tank of capacity 48000 Gallon taking out sludge and depositing the same outside the cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation, remove honeycomb on the wall of OHT if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes and white wash to be carried out in the inner side of the tank and also writing the date of cleaning and capacity of the tank using synthetic enamel paint on black ground and white paint complete all as specifed and directed. Note : The work will be completed within 24 hours after that the water will be supplied to the users.
M&L for cleaning under ground sump of capacity 30000 Gallon taking out sludge and depositing the same outside the cantt area at a place meant for the purpose, removing all scale, dirt, algae, vegetation, remove honeycomb on the wall of OHT if any and flushing after cleaning with water and bleaching powder, cleaning walls and floors by scratching with wire brushes and white wash to be carried out in the inner side of the tank and also writing the date of cleaning and capacity of the tank using synthetic enamel paint on black ground and white paint complete all as specifed and directed. Note : The work will be completed within 24 hours after that the water will be supplied to the users.
Supplying, laying, connecting and testing for submersible flat cable PVC insulated and PVC sheathed LT 1100 volts grade with copper conductor of size 6 Sqmm 3 Core, complete all as specified and directed.
Supplying, laying, connecting and testing of XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor, 1100 volts with earthed system, 4 core, cross sectional area 25 sqmm complete all as specified and directed.
M&L for well burnt brick sub class B old size brick laying in trenches perpendicular to axis of cable complete all as specified and directed.
M&L for sand filling in trenches for cable cushioning with clean, dry and unwashed sand free from sharp particles including gently punning around cable complete all as specified and directed. Note : Only punned thickness will be measured.
M&L for run lead joint in wet/dry soil including removing necessary existing lead from the fittings of following sizes of pipes complete all as specified and directed. Note: Bidder should be ensure that any demages/casualities occured during removing the lead, bidder is the only responsible and no extra cost shall be deemed to quoted rate.
80 mm bore
100 mm bore
150 mm bore
200 mm bore
Supply and replacement of mild steel flange with rubber gasket suitable for following sizes pipes to the existing make and system including nuts, bolts and washers complete all as specified and directed.
50 mm dia pipe
80 mm dia pipe
100 mm dia pipe
S&F of D joint alonwith rubber packing for CI pipe line for the following sizes including necessary excavation in wet condition cutting of pipes, stoping of water removing water and providing necessary extra fitting complete all as specified and directed. Note: Earth work and D joint shall deemed to be included in the quoted rate and nothing extra shall be paid on this account.
80mm dia
100 mm dia
150mm dia
M&L for cleaning the vegetation, rooting etc by spraying the water mixed chemical used for cultivation to avoid the grown up of vegetation etc complete all as specified and directed. Note- Contractor shall ensure that on spraying of chemical vegetation shall be dried if not the same has to be carried out with out any extra cost to deperatment.
M&L for construction of valve pit chambers of size 600 X 600 X 600mm (internal dimensions) as under provided with 10 cm thick PCC 1:4:8 type D2 as in foundation over 15 cm thick hardcore, 23 cm thick brick walls built in cement mortar 1:4, 15 mm thick internal plaster including top of floor, externally upto 150 mm below GL in CM 1:3 finished even and smooth without using extra cement, 3.00 mm thick MS sheet cover with 40 x 40 x 6 mm MS angle frame fixed in PCC 1:2:4 type B1, 50 mm thick coping with 25 x 6 mm flat iron hold fasts, hinges, handles, locking arrangements and applying 2 coats of synthetic enamel paint over a coat of red oxide primer to all steel surfaces and 3 coats of white wash to internal surfaces of chamber including excavation and earth work in any type of soil and removing of surplus soil to a distance not exceeding 50 m complete all as specified and directed.
All as per item No. 94.00 here-in-before but size 900 X 900 X 900mm.
M&L in repairs CI fittings confirming to IS for spigot socket end pipes up to 200mm bore such as bends (any type, radius angle) tapers any type (straight, bend, increasing, descreasing or double socket etc) T pieces, single branch, `Y` junction, double branch cross (all sockets or socket and spigot) collars, caps and plugs etc. complete all as specified and directed.
M&L for High strength calcium based granular chlorination chemical containing appropriate quantities of dispersants / corrosion inhibitors to prevent encrustation / scaling in distribution systems. The brand and make of the chlorination chemical must be stated and certified by All India Institute of Hygiene & Public Health (Govt. of India), confirming compliance to all the above specifications with a declaration from the laboratory that from the technical, strength, stability, health, safety, and operational point of view, as well as the fact that this product is used for drinking water applications for consumption by humans, the brand and make of calcium based granular chlorination chemical is suitable for drinking water chlorination and is recommended for use. The report must indicate that the sample has been drawn by All India Institute of Hygiene & Public Health complete all as specified and directed.
S&F in repairs to sluice valve with new accessories as per requirement like spindle and check nuts of sluice valve including nuts, bolts and rubber sheet suitable for 80 mm to 100 mm sluice valves complete all as specified and directed.
S&F in repairs to sluice valve with new accessories as per requirement like spindle and check nuts of sluice valve including nuts, bolts and rubber sheet suitable for 150 mm to 200 mm sluice valves complete all as specified and directed.
S&F of mild steel nuts, bolts, washers and clamps suitable for CI, GI and DI pipes suitable for 40 mm dia to 200 mm dia flanged joints as per site requirement complete all as specified and directed.
M&L for earthing with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick and burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to a GI wire of size 4 mm dia by means of bolts , nuts, check nuts and washers connected to test poing or as directed including excavation and earth work in any type of strata, disposal of surplus soil to a distance not exc 50 mtrs, filling of adequate quantity of charcoal and common salt in alternate layers of 150mm each making PCC chamber by PCC 1:3:6 type C-1 and cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate 50mm thick duly reinforced with 8mm dia TMT bars 150 c/c and providing 20mm dia light grade GI pipe with funnel and wiremesh, necessary 15mm bore GI tube light grade for protection of GI earth wire 4mm upto test point etc all as shown in electrical plate No.3 of MES SSR Part-1 complete all as specified and directed. Note:- GI wire and protection pipe upto 7.5 mtrs deemed including in the rate quoted.
Taking down old unserviceable mild steel angle iron and matereal and labour for fabricaion and fixing, bracings, supports, clamps and back plates fabricated from structural steel sections i.e mild steel channel or angle sections etc. including new nuts, bolts, washers as required dia/length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of black paint (1st quality ) as required complete as specified and directed.
M&L for replacement of mild steel sheet covers of valve pit as per existing thickness, duly painted with one coat of red oxide paint as primer and two coats of synthetic enamel black paint over a red oxide paint including fixing arragement with existing angle iron frame (hinges, welding, nut and bolts) complete all as specified and directed.
Supply, fixing and commisioing of chemical dosing pump plunger type model RMPS-11 capacity 30 ltr /hr against 15 Kg back pressure with all accessories like injection, check valve , Y strainer, PRV, suction/discharge tubing etc sutiable for chlorine and liquid dosing alongwith 100 Ltr FRP solution preparation cum settling tank with lid, port hole, inlet/outlet/drain connection, sludge collection facility, level gauge etc and fitted with speed reducing motor and SS-316 agitator (FRP Coated for extra protection) CDS-100 Model RMCO including taking down of existing dosing pump complete all as specifed and directed.
Development of tube well by means of pumping by air compressor of minimum pressure 10Kg/cm2 (compressor to be arranged by the contractor at his own cost) until sand free clean water is obtained at optimum yield complete all specified and directed. Note :- Development of bore well (150 feet to 300 feet long),
M&L for painting of water supply main pipe line of size up to 200 mm bore as per colour coding etc with 2 coat of synthetic enamel paint complete all specified and directed.
M&L for replacement of water level indicator at over head water tank of capacity upto Gallon at CPE Itarsi items like Iron/Wooden Board with marking with leveling, float valve, wire and indicating level etc complete all as specified and directed.
Chlorine test kit with coloured sample with all testing fitments and OT solution in rexene finish box complete all as specified and directed.
OT solution for chlorine test (500 ml pack)
Phenol Red solution for PH test (500ml pack)
Iron test soultion (3 bottlesx500 ml each)
Hardness test solution (3 bottles x500 ml each)
Taking out, sluice valve top cover, repiaring of unserviceable spindle and check nut by grinding, machining and putting extra material including lathe work and refixing of sluice valve parts after servicing including replacment of gland packing, rubber sheet, nut, bolt, spindle, check nut and washer of existing size complete all as specified and directed for following size:-
80 mm bore
100 mm bore
150mm bore
200mm bore
S&F of 3 layer PP-R poly propylene random copolymer concealed pipes (outer diameter of pipe ) SDR 7.4 (PN-16) UV stablized and antimicrobial fusion welded having thermal stability for hot and cold water supply including all PP-R plain & Brass threaded polypropylene random fittings laid in trenches for following sizes complete all as specified and directed:-
90 mm outer dia
63 mm outer dia
50 mm outer dia
S&F of push on flexible rubber gasket (Tyton) joint suitable for following sizes complete all as specified and directed:-
100 mm bore
150 mm bore
200 mm bore
M&L for framed work for valve pit chamber cover made of mild steel equal angle and mild steel shee,t 3 mm thick including welding, cutting, hinges, locking arrangments including painting complete all as specified and directed.
Taking out of hand pump from bore well for repair and replacement of damaged parts refitting /fixing and lowering and testing complete all specified and directed. Note :- Defective spares parts shall be measured and paid separetely under relavent items.
Supply only of pump cylinder assembly complete all as specified and directed.
Supply only of GI socket heavy duty, long type 32 mm dia complete all as specified and directed.
Supply only of hand pump water tank assembly rubber gasket complete all as specified and directed.
Supply only of hand pump head and handle assembly complete all as specified and directed.
S&F of connecting rod mild steel 12 mm thick 3 mtrs long suitable for hand pump complete all as specified and directed.
S&F of earth continuity conductor or main earthing lead of 32 x 6 mm galvanized iron strip, buried in ground or fixed to wall complete all as specified and directed.
S&F in repair of earthing pit cover with fixing of funnel of required size in PCC 1:2:4 type B1 and RCC cover with frame as shown in electrical plate No-03 of SSR Part-I 2020 complete all as specified and directed.
S&F of MCCB, 160 Amp, 3 Pole, breaking capacity 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting, with thermal release range 125-160 Amp including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. Make Legrand cat part No-4200 17 or equivelent in Schinder/ Seimens as approved by GE.
S&F of MCCB, 100 Amp, 3 Pole, breaking capacity 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting, with thermal release range 100-125 Amp including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. Make: Legrand cat part No-4200 16or equivelent in Schinder/ Seimens as approved by GE.
S&F in repairs LED indication lamps (RGY) (set of three) complete all as specified and directed.
S&F in repairs on load change over switch of 63 Amps, 4 pole, 415 volts, 50 Hz capasity with SS Enclosure including taking down unserviceable complete all as specified and directed.
All as per ser item no 130.00 here-in-before but 100 Amp , 4 Pole, 415 volt 50 Hz
M&L for brick work with fly ash modular bricks in CM 1:6 straight or curved on plan to any radius complete all as specified and directed.
M&L for 15mm thick rendering in CM 1:6 on fair face of brick walls/ concrete surfaces finished even and smooth without using extra cement complete all as specified and directed.
Labour only for attending day to day complain of internal electrification such as no light , unserviseable tube lights, bulk head fittings, recess lights, mirror lights, building security lights, LED bulbs, switches, sockets, lamp holder, fan regulator, bell push, ceiling rose , plug top, MCBs for minor reparing/rectified including regarging flame proof light and fixture and making functional by skilled trades man with necessary T&P as required at site to complete job with stuiplated time and user satifaction incl small piece of copper conductor single core multistranded up to 1 Mtr of size up to 4 Sqmm complete all as specified and directed at site. Note : - (i) Complaint shall be done within 24 hrs after intimation or receiving reciept of complain slip by JE/ AGE otherwise penalty of Rs 250.00 per day per complaint will be levied on contractor. (ii) Complaints will be reported on daily basis with complaint register. (iii) Other minor items such as insulating tape, screws, small pieces of electrical cables PVC insulated copper multistranded conductor of size 2.5 Sqmm three core upto length of 1.5 m etc as required to attend the complaint is included in quoted rates. (iv) The quoted rate deems to exclude for all chasing of wall and plaster for making good of disturbed surfaces as per existing colour on wall.
Taking down carefully aluminium / copper point wiring with surface/ concealed PVC conduit or wooden batten ( light, fan, socket, bell or power ) including sunk in cast iron / pressed steel terminal boxes except fitting such as switches, ceiling roses, lamp holders, sockets, regulators, call bells, light fittings of any sketch etc and making good disturbed surfaces of walls, floors etc complete all as specified and directed by Engr-in-Charge.
M & L for point wiring with PVC insulated FRLS 1.5 sq mm multi stranded copper conductor cable 1100 Volts grade ISI marked drawn into and including concealed rigid non mettalic PVC conduit medium grade (Make of conduit : Presto Plast/Pressfit) not less than 20 mm ( ISI marked ) with all fitting and fixing accessories including sunk in pressed steel chromium plated terminal boxes, concealed in wall and making & maching the existing surface ) with 2.8 mm thick hylam brand laminated white bakelite sheet cover for mounting switches, Sockets, Fan regulators etc or modular cover plate with frame including sunken boxes suitable to fix modular cover plate with frame , concealed in wall or 1.5 sq mm multi stranded copper conductor cable as continuous earth wire drawn with wiring and connected to common earth dolly for One light point/fan point controlled by one switch complete all as specified and directed.
All as per ser Item no 136.00 here-in-before but One socket outlet 5 Amps controlled by one switch on the same board.
All as per ser Item no 136.00 here-in-before but One socket outlet 5 Amps controlled by one switch on independent board.
All as per ser Item no 136.00 here-in-before but One bell / buzzer controlled by one bell push.
All as per ser Item no 136.00 here-in-before but with 2.5 Sq mm multi stranded copper conductor cable for one 15 Amps socket outlet controlled by one switch on independent board and 1.5 Sq mm PVC insulated multistranded copper conductor cable as continuous earth wire complete all as specified and directed by Engr-in-Charge.
M & L for point wiring for one light point/fan point controlled by one switch with PVC insulated FRLS 1.5 sq mm multi stranded copper conductor cable 1100 Volts grade ISI mark drawn into and including surface PVC Casing Caping medium grade not less than 19/20 mm ( ISI marked ) with all fitting and fixing accessories including sunk in cast iron / pressed steel terminal boxes (duly painted with two coats of anti corrosive paint out side and two coats of aluminium paint inside ) with 2.8 mm thick hylum brand laminated white bakelite sheet cover for mounting switches, sockets, fans regulators etc and 1.5 sq mm multi stranded copper conductor cable as continuous earth wire complete for the following make of copper conductor cable- Havells/KEI/Polycab
All as per ser Item no 141.00 here-in-before but one socket outlet 5 Amps controlled by one switch on the same board.
All as per ser Item no 141.00 here-in-before but one socket outlet 5 Amps controlled by one switch on independent board.
All as per item No.141.00 above but with 2.5 Sq mm multi stranded copper conductor cable for one 15 Amps socket outlet controlled by one switch on independent board and 1.5 Sq mm PVC insulated multi stranded copper conductor cable as continuous earth wire complete all as specified and directed by Engr-in-Charge.
Material and labour in repairs for Sub Main wiring with two single core 4 Sqmm multi stranded copper conductor, FRLS, PVC insulated, unsheathed cable including rigid non metallic PVC conduit medium grade, ISI marked, 20 mm dia for sub main wiring including 4.0 sqmm FRLS PVC insulated and unsheathed stranded copper conductor as earth wire in surface/recess and making good to the disturbed surfaces to match the existing surfaces complete including taking down existing unserviceable sub main of any type and size all as specified and directed. Note:- Two runs of 4.0 Sq mm copper conductor cable, one run of 4.0 Sq mm copper conductor and one run of PVC conduit will be measured as one unit.
Material and labour in repairs for Sub Main wiring with two single core 6.0 Sqmm multi stranded copper conductor, FRLS PVC insulated, unsheathed cable including rigid non metallic PVC conduit medium grade, ISI marked, 20 mm dia for sub main wiring including 6.0 sqmm FRLS PVC insulated and unsheathed stranded copper conductor as earth wire in surface/recess and making good to the disturbed surfaces to match the existing surfaces complete including taking down existing unserviceable sub main of any type and size all as specified and directed. Note:- Two runs of 6.0 Sqmm copper conductor cable, one run of 6.0 Sq mm copper conductor and one run of PVC conduit will be measured as one unit.
S&F switch piano, flush type, single pole, one way, 5 Amps, 240 V complete all as specified and directed.
S&F socket outlet 3 pin 5 Amps, 240 V flush type complete all as specified and directed.
S&F Switch piano, flush type, single pole, one way, 15 Amps, 240 V complete all as specified and directed.
S&F socket outlet, flush type, multi purpose, 2 in 1, 3 pin 5 and 15 Amp, 230 Volts complete as directed.
S&F ceiling rose surface bakelight two to three terminal complete all as specified and directed.
S&F lamp holder, insulated body, with back plate for batten fitting complete complete all as specified and directed.
S & F in repair switch socket combination, outlet flush type, multi purpose 2 in 1, 3 pin 5 and 15 Amp, 230 Volts complete all as specified and directed.
S&F for electronic step type fan regulator/Mini switch type dimmer 120/280 Watt capacity including connecting up complete all as specified and as directed.
S & F 09 Watt LED bulb, in white colour with maximum Lumen output (850 lm) and colour temp 3000 K, all as specified and directed.
S & F for 1 x 20 Watt LED tube light fitting polycarbonated housing prewired with all accessories and including LED tube rod 20 Watt 4 feet long inlcuding connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable 3 core of size 0.50 Sqmm complete all as specified and directed.
Supply and fixing LED light fitting mirror type polycarbonated housing with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.Make- Orient/Wipro/Philips
S & F in repair of existing make Modular switch1 way 6A, 240 Volts 1 module complete.
S & F in repair of existing make Modular switch 1 way 16A, 240 Volts 1 module complete.
S & F in repair of existing make Modular Socket, 6A - 5 pin combined 2 module complete.
S & F in repair of existing make Modular Socket 6A/16A - 2/3 pin combined 2 module complete.
S & F in repair of existing make Modular Fan step regulator 120W, 240 Volts 1/2 module complete.
S&F in repair 3 Pin, Plug Top 5/6 Amp, 220 volt complete all as specified and directed by Engr-in-charge.
S&F in repair for 3 Pin, Plug Top 15/16 Amp, 220 volt complete all as specified and directed by Engr-in-charge.
Supply only for replacement of unserviceable wire of size 1.5 sqmm ISI marked single core FRLSH insulated multistranded copper conductor for working voltage 1100 volts complete all as specified and directed
All as per srl item No 165 here in before but of size 2.5 sqmm.
All as per srl item No 165 here in before but of size 4.0 sqmm.
S&F in replacement of PVC insulated multistranded aluminium conductor twin core of size 6 sq mm, 1100 Volts grade heavy duty service cable, served with inner sheathing of PVC tape and over all PVC sheathed in service connections complete all as directed by Engr-in-charge
S & F in repairs and replacement of building security light fitting LED 35 Watt energy saving & environmental friendly long life versatile pressure die-cast aluminium IP-66 roadway luminaire with high power LED as light source with toughened glass and impact resistance PF IK08 and GI pipe 40 mm dia, light grade for mounting bracket bent to shape 1.50 RM and fixing arrangement with two Nos of MS clamps set, nut bolts, washers of suitable size and fixing on wall/pole complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing repair and replacement of recess mounted adjustable for LED 15W Watt downlights made of extruded aluminium housing and high power LED light source with driver clear diffuser with separate electronic driver with complete accessories all as specified and directed by Engr in Charge as per site requirement. (Ceiling cutout size 180mm dia)
Supply and fixing repair and replacement of Surface LED 15W Watt downlighter with white powder coated aluminium housing with integrated electronic driver h complete accessories all as specified and directed by Engr in Charge as per site requirement.
Material and labour in repairs and repacement of HEXA 10 W, IP-66 Bulk Head luminaries, with lamp holders, including one 1X 10W LED etc. complete with all accessories and including connecting up with twin core twisted flexible copper conductor cable with suitable size of 230V, 50 HZ including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
Supply and fixing post top lantern LED type, 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make- Havells/Philips,Bajaj /Orient
S & F in repair and replacement of sheet metal enclosure MCB, DB 4 way tripple pole and neutral 415 Volts complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
Supply and fix in repair and replacement of sheet metal enclosures for SPN, DB's 240 volts, factory made double door flush type, IP-43 protection and all as per IS-8623, made from sheet metal, 8 way 200 amps rated bus bar to be fixed with wall all accessories complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
S & F in repair and replacement of sheet metal enclosure single pole and neutral with a two pin and earth plug and socket with and including one single pole MCB, 20 Amps 240 volts complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
S & F in repair and replacement of MCB, single pole 240 volts 6 to 40 Amps complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
S & F MCB in repair and replacement of SPN, 240 volts 16 to 40 Amps complete including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
S & F MCB in repair and replacement of TPN, 63 Amp, 440 Volts including taking down unserviceable fitting complete all as specified and as directed by Engr-in-Charge.
S & F in repair and replacement MCB, double pole, 240 Volts, 40 Amps complete. Note for item No 178 to 181 :- MCB shall be of 10 kA breaking capacity having 'C' characteristics as per IS-8828 with air circulating channels, bicontact terminals, dual position DIN rail clamps with IP-20 degree of protection, insulating sliding shutter wiring cable shall be connected to MCB's with suitable lugs (Copper lugs for copper cable and aluminium lugs for aluminium cable)
S&F in repair of earthing pit cover such as damage RCC cover, water funnel, PCC chamber including testing of earth resistivity test with earth tester and T&P required at site by deploying sufficient manpower by the contractor and made entry in register and put up to Conerned JE and Engr-in-Charge
M&L for earthing complete with glavanised steel earth plate elactrode 600x600x6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr deep below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of nut, bolt, check nut and washer of galvanised iron or of steel, earth lead protected by 15 mm dia GI pipe, light grade, watering pipe 20 mm dia GI light grade GI wire meshed funnel alternate layer of charcoal and salt PCC chamber, reassed for and including RCC cover including all necessary excavation and earth work, earth wire connected to main switch board, testing the earthing after completion all as specified and shown in electric plate No 3 of MES SSR Pt-I 1991 print and as directed.
Taking down carefully AC ceiling fan 1200mm/1400mm sweep, exhaust fan 300mm to 450mm sweep and wall moundted bracket fan 300/450mm sweep from their position complete for servicing such as removing dust and dirt from fan motor, washing blades with detergent powder including greasing to bearing, checking & replacing worn out screws with spring washers, rubber, washers of fan blades, fan motor body, spilt pin/screw for fan down rod/check nuts as required for different makes of ceiling/exhaust fans to put fans fans to smooth and satisfactory working and refixing ceiling fan/exhaust fan after executing necessary servicing to their position connecting to electric system with suitable size of cable and testing, complete all as specified & directed. Note :- Rates quoted by contractor shall deemed to be inclusive all minor items and no extra payment shall be admissible except for the items which are to be replaced which shall be measured and paid separately under respective item of Schedule 'A'.
Material & labour for preparation of old painted surfaces of ceiling fan, exhaust fan & wall mounting fan by scrubbing, cleaning with sand paper/wire brush etc making good surfaces and painting by applying synthetic enamelled first quality paint using spray gun in situ including filling cavities with filler and marking Srl No / MES No with black paint, complete all as specified & directed.
Material and labour for rewinding of AC ceiling fan, 230 volts, 50 Hz, 1200mm/1400mm sweep of any make with appropriate gauge super enamelled copper winding wire including allied insulation material such as air drying insulation varnish, cotton tapes, lathered film paper, spacers, sleeves etc re-assembling at its position after repair, testing and commissioning, complete all as specified & directed.
Material and labour for rewinding of exhaust fan/wall mounted fan, 230 volts, 50 Hz, 300/450mm sweep of any make with appropriate gauge super enamelled copper winding wire including allied insulation material such as air drying insulation varnish, cotton tapes, lathered film paper, spacers, sleeves etc re-assembling at its position after repair, testing and commissioning, complete all as specified & directed.
Supply & fixing ball bearing no 6202/6203 in replacement suitable for AC ceiling fan of 1200/1400mm sweep/ exhaust fan/ air circulation fan of any make to replace the unserviceable bearing including greasing as required, complete all as specified & directed.
Supply & fixing in replacement capacitor, 4.0 mfd, 230 volts, AC, 50 Hz, complete all as specified & directed.
Supply & fixing in replacement capacitor, 2.5 mfd, 230 volts, AC, 50 Hz, complete all as specified & directed.
Supply and fix in repair of split pin with hook, rubber and nut bolt of suitable for ceiling fan/exhaust fan of any sweep and make complete all as directed.
Supply and fix in repair of shaft of approved quality for ceiling fan/exhaust fan any make, type and size complete all as directed.
Supply and fix in repair of self lubricating bush of gun metal as per ceiling fan/exhaust fan complete all as directed.
Supply & fixing in replacement fan canopy, complete all as specified & directed.
Supply and fix repair of hanging rod 1ft/2 ft complete all as specified and directed
Supply and fix in repair and replacement of fan blade 1200/1400 mm complete all as specified and directed
Supply and fix in repair of PVC insulated, unsheathed three core copper flexible cable of size 1.5 sqmm including connection complete all as directed.
Taking down carefully Geyser of capacity 25/35 ltrs from its position for repair/servicing such as removal of dust, checking, replacing worn out parts, rubber etc, re-assembling at its position after repair, testing & commissioning & connecting to electric system with suitable size cable, complete all as specified & directed. Note :- Rates quoted by contractor shall deemed to be inclusive all minor items and no extra payment shall be admissible except for the items which are to be replaced which shall be measured and paid separately under respective item of Schedule 'A'.
Supply & fixing galvanized iron water tubing, medium grade, 15mm bore with all fittings such as sockets, bends, elbows, tees, short pieces, connectors, back nuts, diminishing pieces, caps, plugs and unions etc. fixed complete to walls and ceilings or laid in floors, complete including taking down all as specified and directed.
All as per srl item No 199.00 here in before but of size 20mm.
Supply & fixing geyser tank of capacity 25 ltrs, complete all as specified & directed.
Supply & fixing geyser tank of capacity 35/50 ltrs, complete all as specified & directed.
Supply & fixing heating element for geyser, 1500 watt, ISI marked , round type, complete all as specified & directed.
Supply & fixing heating element for geyser, 2000 watt, ISI marked,round type, complete all as specified & directed.
Supply & fixing thermostat suitable for geyser of any capacity 25/35 Ltrs, complete all as specified & directed.
Supply & fixing angle stop valves, 15mm bore, fancy type, chromium plated with long shank and cup (concealed type), cast copper alloy, screwed down, high pressure with crutch or butterfly handle, both ends screwed for iron pipe or for union etc., fixed in repair, complete all as specifed & directed.
Supply & fixing bib tap, 15mm bore, fancy type, chromium plated , cast copper alloy with crutch or butterfly handle screwed down, screwed for iron pipe or for brass ferrule, fixed in repair, complete all as specified & directed.
Supply & fixing stainless steel connection 15mm dia, 900mm long with brass CP nuts and washers at both ends for hot water & Cold Water, fixed in repair, complete all as specified & directed.
Taking down/out Deep freezer/Refrigerator 320/265 ltr transporting to contractor's workshop for carrying out repairs, taking out assembly, welding/brazing after detecting the leakage, as mentioned in respective items of Schedule including transporting back after repair, re-fixing at site, making it functional after replacement of worn out nuts, bolts, washer etc. including re-connecting electrical connection and testing, complete all as specified & directed. Note :- Material and labour for providing by the contractor and cost of new items shall be measured and paid for separately under relevant items of Sch 'A'.
Taking down/out Water Cooler of 40/80 ltrs and 60/120 ltr capacity transporting to approved workshop for carrying out repairs, taking out assembly, welding/brazing after detecting the leakage, as mentioned in respective items of Schedule including transporting back after repair, refixing at site, making it functional after replacement of worn out nuts, bolts, washer etc. including re-connecting electrical connection testing complete all as specified & directed. Note :- Material and labour for providing by the contractor and cost of new items shall be measured and paid for separately under relevant items of Sch 'A'.
Material & labour for preparation of old painted of Deep Freezer/Refrigerator/water cooler of capacity up to 320 Litres, surfaces by scrubbing, cleaning with sand paper/wire brush etc making good surfaces and repainting by applying two coats of synthetic enamelled first quality paint using spray gun over over one coat of red oxide zinc chrome primer and marking Srl No SM No / MES No with black paint of following items :-
Supply and fixing in replacement of following unserviceable items of Deepfreezer/refrigerator of 300/310/320 litres as required at site including testing of the same, complete all as specified & directed :-
Supply only MS condensing coil with fixing arrangement for 300/310/320 litres capacity complete with gas charging.
Supply only over load protector.
Supply only Thermostat switch (Auto defrost).
Supply only temp control knob with defrost push button.
Supply only electrical lamp pin/threaded type 15 watt, 240 volts AC supply.
Supply only PVC ice tray of superior quality.
Supply only relay as per existing capacity.
Supply, fixing and testing new compressor of compressor of Deepfreezer/Refrigerator of cap 300/310 Ltr, single phase, 240 Volts, AC supply in replacement including cost of rubber bushes, bolts, nuts washers, copper tubing capillary tube, dryer filter terminal cover, thimbles, electrical wiring oil and gas charging (R-134 or as recommended by manufacture) and testing complete for the following including transportion etc :-
All as per item No. 213.00 here-in-before but compressor of Water Cooler of capacaity 300/310 Litres.
Supply and fixing in replacement of following unserviceable items by opening of water cooler of 40/80 or 60/120 Ltrs capacity frost free for following replacement of unserviceable accessories and refixing, connecting and testing complete all as specified & directed :-
Copper Condensing coil complete with fixing arrangement.
Fan motor 1/2 HP, 240 volts, single phase AC supply.
Aluminium Blade for fan motor complete blower.
Thermostat.
Relay as per existing make.
Over load protector.
Float Valve brass 15 MM bore.
Push type tap 15mm bore, brass chromium plated
M&L for charging of following water collers/Deepfreezer with refrigerant R-22A/R-134 or as recommended by manufacturer including flushing out oil, vacuming, top up oil, brazing, leak detection, testing etc for following cooling appliances including replacement of capillary tube and dryer filter :- Note:-. The type of refrigerant gas shall be charged as per manufacturer recommendation.
Water cooler 60/120 litres capacity.
Deep Freezer/Refrigerator of capacity up to 320 Litres.
Supply and replacement of water lifting pump (water immersed) for desert cooler with model - HM - 09, 240 volts, 50 Hz, 40 watts, 1.5 metre max head and output 800 LPH complete all as directed.
Supply and fix in replacement of khas pads/wood wool pad of required size for desert cooler of any make complete all as specified and directed.
Supply and fix in repair of blower motor, 230 volts, single phase, 50 Hz, suitable for desert cooler /Exhaust fan size 350/450 mm as per site requirement including kit consists of mounting clamps, blades, speed contol switch, nut, bolts and washers complete all as specified and directed.
Supply & fix in replacement of exhaust fan louver of any size complete all as specified and directed
S&F in repair of voltage stabilizer of capacity 5 KVA installing and testing complete all as specified and directed.
Taking down defective Split/Window AC of 1.5 Ton capacity from any height and any places for repair and refixing at its original place after replacement of defective/wornout parts & making serviceable, complete all as specified & directed. Note:- Worn out spares parts required for making AC serviceable/functional shall be measured and paid separately under appropriate item as 'Supply only'.
Supply only fan motor for 1.5 ton AC.
Supply only AC compressor for 1.5 ton AC.
Supply and charging gas 22 R for 1.5 ton AC.
Supply only AC copper pipe of size 8mm and 15 mm for 1.5 ton AC.
Supply only 45 Mfd capacitor for 1.5 ton AC. Make.
Supply only contactor, single phase, 30 Amp for 1.5 ton AC.
Supply only fan belt for 1.5 Ton AC.
Supply only printed circuit board of split AC/Window AC 1.5 ton
Over load protector.
Maintenance for operationaly fit of RO based aqua guard installed for water cooler , with replacement of candle, Replacement of Membrane, Replacement of Pree filter candle, Replacement of Diaphragm Pump 24 volt DC and open flow minimum 2.0 Ltr/min checking of AC supply circuitary of aqua guard and made functional, replacement of step down transformer 230 volt to 12/24 volts, as per sample, incl servicig of RO complete all as directed at site.
Taking down defective items/spares in replacement for solar heaters of various capacities and refixing at its original place after replacement of defective/wornout parts & making serviceable, complete all as specified & directed. Note:- Worn out spares parts required for making solar heaters shall be measured and paid separately under appropriate item as 'Supply only'.
Supply only heating element of capacity upto 2 KW (Electric rod) having rubber washer of size 1 ¼” or 1 ½” complete all as specified.
Supply only heating element of capacity upto 1.5 KW (Electric rod) having rubber washer of size 1 ¼” or 1 ½” complete all as specified.
Supply only glycol (Anti freezing solution) for filling in copper tubes complete all as specified.
Supply only dead flange with nut, bolts and washers complete all as specified.
Supply only float valve assembly 15mm dia complete all as specified.
Supply only thermostat suitable for solar heater complete all as specified
Supply only hot water steel tank non stick 2mm thick with ceramic lining of capacity 500 Ltrs each including making necessary connections complete all as specified.
Taking down existing unserviceable light point wiring, fitting and fixtures and M&L for flame proof point wiring on wall surface wiring on ceiling with necessary fixing arrangements for one light point controlled by one switch with stranded PVC, FRLS insulated and unsheathed copper multistranded conductor of size 2.5 sqmm, 1100 volts grade drawn in and including 14 gauge ERW rigid steel conduit (metallic) not less than 20 mm dia with all MS conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc., including PVC-FRLS insulated and unsheathed copper stranded conductor of size 2.5 sqmm, 1100 volts grade for continuous earthing making good the distrubed surface either by means of plaster of paris/ putti or distemper/ colour wash with same existing colour surfaces complete all as specfified and directed. Note:- (i) Junction box flame proof shall be measured and paid under relavent item. (ii) Earth wire shall be of green colour (iii) Colour code should be maintined
All as per item No.225.00 here-in-before but for fan point wiring complete
All as per item No.225.00 here-in-before but two light point controlled by one flame proof switch.
All as per item No.225.00 here-in-before but power point wiring using 4 sqmm copper conductor cable and 4.0 sqmm as earth wire.
M&L for sub main wiring with two single core 4 sqmm multi stranded copper conductor, FRLS PVC insulated, unsheathed cable, including ERW rigid metallic steel conduit medium grade, ISI marked, 19/20 mm dia for sub main wiring including 4.0 sqmm FRLS PVC insulated and unsheathed stranded copper conductor as earth wire in surface/ recess with all MS conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc and making good to the disturbed surfaces to match the existing surfaces complete including taking down existing unserviceable sub main wiring all as specified and directed. Note:- (i) three runs of 4 sqmm copper conductor cable, and one run of ERW rigid metallic conduit will be measured as one unit.
S&F flame proof junction box with spigotted cover in LM-6, three way/terminal block 4 way strip type cable entry, 20 mm dia hole aluminium constructed, internal dimension 80 mm dia and 40 mm depth, duly approved by CMRI Dhanbad complete including taking down existing unserviceable junction boxes of any type and size all as specified and directed.
S&F flame proof bend any radius of CI/MS with brass nickle threaded of size 20mm complete including taking down existing unserviceable flame proof bend of any type and size all as specified and directed incl taking out old unsv complete all as specified and directed.
S&F flame proof union brass of size 20 mm complete including taking down existing unserviceable flame proof union brass of any type and size all as specified and directed incl taking out old unsv complete all as specified and directed.
S&F flame proof plug brass of size 20 mm complete including taking down existing unserviceable flame proof plug brass of any type and size all as specified and directed incl taking out old unsv complete all as specified and directed.
S&F flame proof flexible metalic hose conduit of size 3/4" dia and 300 mm long suitable for explosive atmosphere with explosive dustproof complete including taking down existing unserviceable metallic hose conduit of any type and size all as specified and directed.
S&F flame proof rotary switch in LM6, 10/16 amps, single pole, 250 volts and enclosed cast aluminium body with threaded cover with switch operated by a sigle pole knob with double entries suitable for 20 mm dia ERW threaded steel conduit duly approved by CMRI dhanbad and as manufacturers intructions including taking down existing unserviceable rotary switches of any type and size all as specified and directed.
S&F flame proof switch socket outlet with plug combination in LM-6, 16 Amps, 250 Volts, two pin and earth with no spare plug complete all as per manufacturer's instruction complete including taking down existing unserviceable switch sockets of any type and size all as specified and directed.
S&F flame proof LED light fitting 2X20 Watts, epoxy finish LM-6 aluminium housing with heat resistant tubular glass cover held in two aluminium cups, with built-in control gear accessories, prewired including complete including taking down existing unserviceable light fittings all as specified and directed.
S&F flame proof Bulk head flat type glass fittings, 30 Watts LED ceiling/wall mounted complete including taking down existing unserviceable bulk head fittings of any type and size all as specified and directed. : (with point wiring)
Taking out old unsv well glass light fitting and S&F flame proof well glass light fittings, 30 Watts LED ceiling/wall mounted complete including taking down existing unserviceable bulk head fittings of any type and size all as specified and directed.
M&L for rewinding of burnt out copper winding of flame proof ceiling fans of any make, size 1200 mm/1400mm sweep, rewinding with super enamelled copper wire of approved quality of existing gauge and size including necessary insulation with leathoroid sheet varnishing of winding of coil, packing, proper insulation, gasket etc including cleaning the rotor & the stator, overhauling, lubricating with fresh graese, etc and re-hanging the same and testing and commissioning, including taking out old unsv complete all as specified and directed by Engineer-in-Charge.
All as per item No.240.00 here in before but flame proof Exhaust fan of any size.
S&F flame proof ceiling fan regulator etc. including taking down existing unserviceable ceiling fan regulator of any type and size all as specified and directed.
S&F fix flame proof cast iron enclosure distribution board 415 volts, 4 way, TPN with ELCB and MCB suitable for explosive atmosphere with explosive including necessary panel board for required connection from busbar to different outgoing and including making good to the disturbed surfaces of walls, floors etc.complete all as approved by CMRI Dhanbad with following incoming and outgoing controls including taking down existing unserviceable MCBs of any type and size all as specified and directed:- (i) Incoming:- ELCB 4 pole, 415 volts, 63 Amps - 01 No. (ii) Outgoing:- MCB 16 amps - 8 Nos.
S&F flame proof cast iron enclosure Main Switch Rotary Type 63 Amp 4 Pole, 415 Volt with all fixing arrangement and making good to the disturbed surfaces of walls, floors etc complete including taking down existing unserviceable main switches of any type and size all as specified and directed as approvedd by CMRI Dhanbad.
M&L for Earthing connected with Bldg main Lightining arrestor etc. with galvanised iron earth plate of size 600 x 600 x 6 mm thick burried directly in ground not less than 2.5 mtr below grond level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150 mm connected by GI earth strip of size 32 x 6 mm thick soldered and revetted to earth plate attesters. GI earth strip will be protected by using 50mm bore GI pipe (light grade) earth plate to the including flat iron clamp 25 x 3 mm including bolts, nuts & washers complete. The earthing includes necessary excavation, PCC pit, CI cover with frame duly groted with PCC, watering pipe 20 mm bore, funnel with wire mess etc. all as specified and shown in electrical plate No 5 of SSR Part - I. Note: The unit rate shall also including earth work in any type of soil, PCC 1:3:6, type C1 for chamber, CI cover with frame duly groted with PCC with locking system, funnel with GI watering pipe 20mm dia light grade, GI protection pipe light grade 40mm dia and wire mesh complete as directed by Engr-in-Charge.
M&L for Air termination single pointed aluminium rod 12mm dia, 300mm long fixed on GI Pipe complete including taking down unserviceable air termination point all as specified & directed.
M&L GI Pipe 40mm dia, medium grade, for air termination rod fixing, including fitting supported with GI Flange 40 mm bore, incl taking down unserviceable GI pipe all as specified & directed. Note: GI Flange will be measured and paid seperately under relevent item
M&L for GI reducer of size 40x12 mm dia medium grade with threaded type suitable to fit air termination complete all as directed by Engr-in-Charge.
M&L for providing cement concrete on roof of type B1 1:2:4 20 mm graded stone aggregate for foundation of GI pipe fo lightning protection /as per existing at site all specified and directed.
Taking down and refixing the old removed aluminium/GI strip any size on roof/wall incl replacement of 'T' type insulators complete all as directed by Engr-in-Charge. Note: 'T' type porcelain insulators shall be measured and paid separately under relvent item
S&F 'T' type heavy duty insulators made of DMC material suitable for supporting 25 x 3 mm / 32 x 6 mm strip on roof or as down conductor on wall/surface including all fixing accessories required complete all as specified and directed.
S&F aluminium strip 25X3.15mm with saddler and drilled holes, nut bolt washers and fixing srewed on wall/ roof etc for roof conductor down conductors on roof/wall run on porcelain insulators between suitable distance including taking down unserviceable aluminum strip all as specified & directed. Note :- Necessary nut, bolt and washer for fixing alongwith drilled holes are included in coated rate.
Taking out old unsv tube rod and supply and fix in replacement of LED tube rod 20 Watt cap single side connection (for flame proof fitting)complete all as directed by Engr-in-Charge
All as per item No 253.00 but double side connection.
Taking out old unsv static handle discharge copper tube any size, supply and fix static handle discharge copper tube of size 25 mm dia and 600 mm long complete all as directed by Engr-in-Charge
M&L for test point terminal block made of gunmetal or phasphorus bronze of size 75x75x25mm drilled and srewed including 03 Nos 8mm dia 25mm long hexagonal head screwed including taking down unserviceable terminal block all as specified and directed.
M&L for repair of earthing pit cover such as damage RCC cover, water funnel , PCC chamber incl testing of earth resistivity test with earth tester and T&P required at site by deploying sufficient manpower by the contractor and made entry in register and put up to Conerned JE and Engr-in-Charge
Deduct Schedule of credit (calculation will be done off line) Rs. 138918.70
M/s SHIVRATAN CONSTRUCTION
TANUJ CONST. CO.
pyarelal galar
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .