| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.6 LAccepted-AOC NOT SPECIFIED | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹1.1 Cr+₹10.4 L (10.7%)Rejected-Finance | L2 | Rejected-Finance Rejected, being not L1 | |
| 3 | L3₹1.1 Cr+₹11.6 L (11.9%)Rejected-Finance 252 22 NEAR SOCITY BUS STAND INDRA COLONY PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-Finance Rejected, being not L1 | |
| 4 | L4₹1.1 Cr+₹15.2 L (15.6%)Rejected-Finance A 102 GOLDEN SAND APARTMENTS GAZIPUR DHAKOLI ZIRAKPUR PB 160104 | ZIRAKPUR | S A S NAGAR | PUNJAB | 160104 | L4 | Rejected-Finance Rejected, being not L1 | |
| 5 | L5₹1.1 Cr+₹16.1 L (16.5%)Rejected-Finance 11 GURU NANAK MARKET AMBALA ROAD SAHARANPUR 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | L5 | Rejected-Finance Rejected, being not L1 |
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
15 Jul 2024, 6:00 pmClosed
CELZ
HQ CE Leh Zone c/o 56 APO
PROVISION OF LED SECURITY LIGHT AROUND SECURITY WALL AND 04 X HIGH MAST LIGHT ALONGWITH POWER BACKUP UNDER GE (I) (P) NO. 1, LEH
2024_MES_657338_1
180121/E8
Open Tender
Electrical and Maintenance Works
Item Rate
500 days
LEH
Please refer tender documents
9 documents required · 9 mandatory
₹1,000
Yes
GE (I) (P) No. 1, Leh
₹1.9 L
Yes
14 Oct 2024
1 Jun 2024
22 Jul 2024
1 Jun 2024
15 Jul 2024
8 Jul 2024
1 Jun 2024 - 9 Jun 2024
Amount
Material and labour for Steel Tubular Swaged pole, type 410 SP -31(9.00 Metre long) complete with & including cast iron base plate, final taper plug, bolts, nuts screws, drilling work, painting & numbering to poles complete all as specified and as directed. Notes:- (i) Excavation & earth work, PCC for foundation and coping shall be measured and paid for seperatelly under relevant items of schedule 'A' (ii) Provn of painting and numbering i.e applying one coat of black bitumenous paint on embedded portion, making five numbers alternate yellow & black strips 30cm height each (upto 1.50 metre height from top of PCC coping) with two coats of synthetic enamal paint over a coat of red oxide primer and painting the remaining external surface with two coats of aluminium paint over a coat of red oxide primer and numbering to the poles with synthetic enamel paint etc shall be deemed to be including in the quoted rate of above item.
S&F in repairs, installation, commissioning and testing Junction boxes made of Lid PC and base is polystyrene Hensel reference : KG series suitable . Junction Boxes Size 217 x 253 x 115 mm in Grey RAL 7035 colour. Junction Box IP 65 Thermoplastic PS Polystyrene weatherproof Junction Box with multi level knockouts for cable glands in different sizes. The pre-moulded knockouts shall be available on top and bottom of the junction box to enable cable entries from both direction. The junction box shall have an optional cable entry at the bottom up Cable Size 25 Sq mm of the box via pre-moulded knockout to enable pole mounting option. Lid fasteners self closed will be tool operated. it will be sealable with accessories. The junction box shall have elongated holes inside them for wall/pole mounting provision. The junction box with 4 Pole Terminal Strip and MCB SP 6 Amp 10 KA C Curve for LED light. In the event of formation of condensed water, the junction box shall have a minimum of two condensation knock-outs inside to ensure optimum safe performance.
The junction box shall fulfill the following standards Weatherproof : Rainwater proof, temperature resistant. IEC 60670-22 : Particular requirements for connecting boxes and enclosures. IEC 60695 – 2 – 11 : Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 750 deg C. IEC 60529 : IP 65 degree of protection. UV Resistant in accordance with IEC 61 439-1, Clause no 8.4.4 The Junction Box with Suitable Glands 3 Nos with each and chromium plated clamps, nut bolts complete all as per manufacturer’s instructions. Make : Cat Part :- KG 9003 of Hensel/Siemens/GE Power/Schneider/ L&T/ABB. Manufacturer should submit routine test certificate of CJB/PJB
M&L Plain cement concrete (1:3:6) type C-1 using 20 mm graded store aggregate as in foundation of poles, stays , etc including provision of necessary form work complete all as specified.
M&L Plain cement concrete (1:2:4), type B-1, using 20 mm graded stone aggregate for coping around poles, including provision of necessary form work, finishing and smooth without using extra cement, complete all as specified .
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figuresand conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts ofapproved size, for HT, 25x20cm size complete all as specified.
Supply and Fixing of 60W LED Street Light with System Lumen Efficacy ≥120 Lm/W operating Voltage between 120-270Vac, multistage isolated potted driver, Driver will comply for 440Vac operation (will sustain for 4 - 6 hrs continuously), Driver will have cut off at > 300 Vac, IP66 Protection, Power Factor more than 0.95, of rated maximum forward current, Luminaire intergal driver with 5KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), fixed on a bracket made out of 1.5 mtr long Med grade GI pipe 40 mm dia bend to shape as directed fitted on pole at a height not less than 5 mtr from ground with MS clamp, nuts and bolts and washers as required at site without any condition, driver and LED of the same manufacturer will be provided complete all as specified and directed. Note : Copper cable of size 1.5 sqmm x 3 core from junction boz to light fitting should be measured and paid separately in relevant item of BOQ.
Suppying, laying jointing and testing of LT cable XLPE insulated, screened, PVC sheathed aluminium conductor multistranded heavy duty 1100 volts grade electric cable of cross section area 95 Sqmm, 3.5 core making connection with suitable size of eyelet on both side laid in trenches/crossings/panels/walls etc.complete all as specified and directed Engr-in-Charge.
Suppying, laying jointing and testing of LT cable XLPE insulated, screened, PVC sheathed aluminium conductor multistranded heavy duty 1100 volts grade armarred electric cable of cross section area 50 Sqmm, 3.5 core making connection with suitable size of eyelet on both side laid in trenches/crossings/panels/walls etc.complete all as specified and directed Engr-in-Charge.
Suppying, laying jointing and testing of LT cable XLPE insulated, screened, PVC sheathed aluminium conductor multistranded heavy duty 1100 volts grade armarred electric cable of cross section area 16 Sqmm, 4 core making connection with suitable size of eyelet on both side laid in trenches/crossings/panels/walls etc.complete all as specified and directed Engr-in-Charge.
Suppying, laying jointing and testing of LT cable XLPE insulated, screened, PVC sheathed aluminium conductor multistranded heavy duty 1100 volts grade armarred electric cable of cross section area 10 Sqmm, 4 core making connection with suitable size of eyelet on both side laid in trenches/crossings/panels/walls etc.complete all as specified and directed Engr-in-Charge. Note : From Item No 07 to 10 Excavation & earth work shall be measured and paid separately. This cable shall be supplied suitable for (-) 35 degree C of local prevailing conditions. A certificate shall be submitted from the cable manufacturer for design condition /serviceablility of cables at (-) 35 degree C
Supply and laying cable PVC insulated copper coductor with stranded conductor of size 1.5 sqmm 3 core. (From Pole light to Junction Box)
M&L for tubes, light grade, ISI marked, galvanized, with all fitting and fixed complete to walls and ceilings or laid in floors of size 50mm dia complete all as specified and directed.
Supply, Installation, Testing & Commissioning of High galvanized mast light suitable for 9 luminaries symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 97/19 guage and double drum winch with luminaire mounting arm, pully assembly, aviation obstruction light, lightning arrester spike including RCC foundation suitable for 20 Mtr height completed all as directed. The minimum dimension of RCC foundation shall be designed as per IS 456:2000 & 1513920:2016 considering wing speed 55mm/s and seismic zone -iv. The structure and foundation drg will be approved by GE as per manufacturer recommendations specified as under mentioned specifications. Necessary excavation, removing and returning filling shall be included in quoted rate. (A) High Mast Structure 1. Material of Construction: - S 355 grade steel conforms to IS 2062/BS EN 10025 or Equivalent 2. Base Dia. and top diameter (A/F) (i). Top Section - 150 mm (ii). Bottom Section - 410 mm
3. Plate thickness: - Top - 3mm, Bottom - 4 mm 4. Cross Section of Mast (Number of Slides) - 20 Sided Polygon 5. Standard of galvanisation - As per BS EN ISO 1461 6. Size of opening and door at base - 1200 x 250 mm 7. Diameter of base plate - 570 mm 8. Thickness of base plate - 25 mm 9. Lighting protection finial - G.I single spike 10. Max. wind speed - 55 m/s as per IS : 875 (Part -III) 11. Number of foundation bolts - 8 nos
12. Type/ diameter/ length of foundation bolts - TS 600/ 30 mm dia/ 850 mm long 13. PCD of foundation bolts - 850 mm (B) Luminaires Carriage:- 1. Material of construction - 50 NB ERW Class B - M.S. pipe 2. Diameter of carriage ring (mm) - 535 mm (ID) 3. Construction - 8 Arm, welded, 2 sections 4. Load Carrying capacity - 16 Luminaires (C) Trailing Cable :- 1. Conductor - Copper, 5 core, 2.5 Sqmm 2. Insulation - PVC insulated 3. No of circuits per mast - One no. cable per mast (D) Winch/ Power Tool 1. Type /SWL of winch - Double drum, SWL 750 Kg 2. Method of seperation - Integral Motor 3. Motor capacity - 1.0 HP 4. No of speeds - 6 pole, single speed 5. Torque limitor - with mechanical tripping facility (E) Stainless steel wire rope 1. Grade/ Construction - AISI 304, 7/19 construction 2. No of ropes - Two continuous 3. Diameter (mm) - 6 mm 4. Breaking load capacity - 2350 Kg x 2
Supply and Fixing of 150 W LED flood Light with System Lumen Efficacy ≥120 Lm/W operating Voltage between 120-270Vac, multistage isolated potted driver, Driver will comply for 440Vac operation (will sustain for 4 - 6 hrs continuously), Driver will have cut off at > 300 Vac, IP66 Protection, Power Factor more than 0.95 of rated maximum forward current, Luminaire intergal driver with 5KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), fixed on a bracket as directed fitted on high mast pole at a height not less than 12.5 mtr from ground with MS clamp, nuts and bolts and washers as required at site, connecting with PVC copper cable of size 1.5x3 sqmm as per IS 10322 without any condition, driver and LED of the same manufacturer will be provided complete all as specified and directed.
M&L earthing complete with and including galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected to galvanised iton steel earth lead wire 4 mm dia by means of nuts, bolts, checknuts and washers made out of galvanised iron, 15 mm bore (light grade) GI pipe for protection of earthing lead, 20 mm bore (light grade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC M-25(Design mix) reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and comman salt filling in alternate layers, complete all as shown and specified in electrical plate No. 5 of SI Part-I.
Earthing complete with GI earthplate electrode 600mm x 600mm and not less than 6 mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to GI strip of size 32x6mm by means of bolts, nuts, check nuts and washers of GI/steel all as shown in electric plate No 3 connected to equipments all as specified and indicated complete and including char coal dust & salt filling in alternate layers (each layer shall be 15 cm thick) and GI protection pipe, medium grade 40mm dia and GI watering pipe 20mm, medium grade with funnel and wire mesh, 40mm thick pre-cast RCC, M-15 (nominal mix) cover reinforced with XPM weight not less than 4kg/sqm with suitable handle of 6mm dia MS bar and angle iron 40 x 40 x 3mm frame for cover, PCC M-15 (nominal mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed by Engr-In-Charge.
Supply and fix 4P, MCCB 32 A, with rupturing capacity 25 KA (for Existing Panel)
Supply, installation, testing and commissioning LT panel of suitable size, factory made dust and vermin proof outdoor type made out of 3.15 mm thick CRCA sheet double door including seperate compartment for each MCCB & for cable and busbar, mounted on frame of MS angle iron 40mmx40mmx6 mm with front and back openable door with lock & powder coated with 7 tank process made enclosure three phase 50 Hz AC Key including necessary grouting and double coat powder coated of grey colour painting complete with following accessories.The degree of protection of panel shall be IP-54 including foundation all as specified and directed.:- (LT Panel for street light)
INCOMING: (i) 4 pole MCCB 32 Amps with rupuring capacity 25 KA ,- 01 No (ii) Change over 40 Amps -01 (iii) Aluminium bus bar 3 phase 4 strip suitable for 100 Amps current carrying capacity complete with post insulators and heat shrinkable sleeves- 01 No.. OUTGOING (i) TPN 10 Amps - 03 No (For Street light Circuit 1&2, spare) (ii) RYB indication lamp -01 No. (iii) Voltmeter digital type with range 0-500 Volts -01 No. (iv) Ammeter digital type with range 0-100 Amp . (v) LDR based timer switch 20 Amp -01
Supply, installation, testing and commissioning LT panel of suitable size as per IE rule and latest IS, factory made dust and vermin proof outdoor type made out of 3.15 mm thick CRCA sheet double door including seperate compartment for each MCCB & for cable and busbar, mounted on frame of MS angle iron 40mmx40mmx6 mm with front and back openable door with lock & powder coated with 7 tank process made enclosure three phase 50 Hz AC Key including necessary grouting and double coat powder coated of grey colour painting complete with following accessories.The degree of protection of panel shall be IP-54 including foundation all as specified and directed.:- (LT Panel for high mast)
INCOMING: [i] 4 pole MCCB 32 Amps with rupuring capacity 25 KA ,- 01 No (ii) Aluminium bus bar 3 phase 4 strip suitable for 100 Amps current carrying capacity complete with post insulators and heat shrinkable sleeves- 01 No.. OUTGOING [i] TPN 20 Amps B curve - 02 No (For Motor 1&2, spare) [ii] TPN 16 Amps - 01 No (For Flood lights ) (iii) RYB indication lamp -01 No. (iv) Voltmeter digital type with range 0-500 Volts -01 No. (v) Ammeter digital type with range 0-100 Amp .
Supply, install, test and commission factory made 63 Amps aluminium bus bar 6 way outdoor type CRCA sheet steel duly phosphatized and powder coated with 7 tank process made enclosure three phase 50 Hz AC feeder pillar box having degree of protection IP 54, door locking by panel lock and provision for pad lock, pre-wired ready to use, liberal termination space, louvers provided on both sides for proper heat dissipation, testing and commissioning of the panel complete all as per directions and specifications of Engineer-in-Charge.
Labour for boring underground upto 100 mm bore for road crossing 3 mtr to 10 mtr not exceeding 1.5 mtr in depth for laying of electric cable and GI tubing in soft/loose soil complete all as specified.
M&L for tubes, light grade, ISI marked, galvanized, with all fitting and fixed complete to walls and ceilings or laid in floors of size 100mm dia complete all as specified and directed.
Excavation in trenches in any type of soil not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying for laying GI tubing /UG cable etc complete all as specified and as directed.
All as per description of Srl No 27 above but depth exc 1.5m but n. exc 3.00 mtr
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick excavated soft/loose soil in trenches after the pipe have been laid and tested complete all as specified and directed by Engineer-in-charge.
Removal excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge.
M&L sand filling in trenches for cushioning of HT/LT/JFC UG cable 8 cm before laying of cable and 15 cm after laying of cable including compacting after filling complete all as specified and directed. Note : Only punned thickness shall be measured and paid.
M&L precast concrete cable cover, class LV, type 1, size 250mm x 150mm x 40mm of ISI marked all as specified and as directed by Engr-in-Charge.
Supply & installation of silent CPCB approved 15 KVA NTP Diesel Generating Set having diesel engine Liquid/Air cooled, Electric start, four stroke, Three/Four cylinders cold starting, TCI Aspirated, compression ignition, totally enclosed diesel engine with electronic governor generating minimum 21 BHP @ 1500 RPM, direct coupled with 15 KVA Three Phase alternator at 1500 RPM, 0.8 lagging power factor, providing Three Phase 415Volts suitable for 50 Hz, H class insulated winding, Close-direct-coupled, Self-excited and self-regulated type, screen protected, mounted on rigid MS sheet channel base-frame. The alternator shall confirm to IS: 13364, IS: 4722, BS5000, IEC: 34 and suitable for tropical condition. having fitted inside Canopy, fabricated out of 1.6 mm CRCA Sheet, cubical type, totally enclosed, Powder Coated, Control Panel and all accessories in- housed in a acoustic enclosure – sound proof canopy. Make: Cummins/ Kirloskar Green/Greaves cotton/Sudhir/jackson.
NOTE : - (i) The capacity of Generator set shall be net after all due derating factors as per relevant ISI design. (ii) Rate quoted shall be deemed to be inclusive of cable size 50 sqm 3.5 core and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to distrbed surfaces so as to match with the existing finishes all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test. (iv) The quoted rate shall be deemed to be inclusive of 12 hours test run at site including of half an hour on 10% overhead in presence of representative detailed by accepting Officer; all arrangements are to be made by the contractor for tests.
(A). Alternator :- Standard design alternator rated at 15 KVA, 21 BHP net output at site after considering derating as per site conditions at 0.8 (lag) power factor AC, 3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class 'H' and voltage regulation of + 1% at rated voltage from no load to full load. The alternator shall be confirming to BS 2613/5000 and shall be inposition to generate supply with frequecy regulation with in + 1% tolerace. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613/5000/ IS - 4722. i) Insualation class - 'H' ii) Temparature rise Class - 'H' iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with + 1%, manual voltage adjustment within + 5% . v) Frequency regulation + 1%
(B) Diesel Engine: - Adquate capacity of Diesel engine as accepted by the accepting officer based on manufacturers technical details water cooled to drive independently above alternator and after considering derating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexiable coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under:- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of 100mm dia with MS pipe light grade upto & outside and 1meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclousre. Exhaust gas turbo charger type, Exhaust manifold, Silecer : Residual type, Bellows
iv) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governer for 1% speed /frequecy regulation. Fuel filters, Fuel hoses v) Lub oil System :- Lubricating oil filter, Lubricating oil pump vi) Air Intake System :- Air intake Manifold, Air cleaner dry type vii) Governer :- Mechanical Governer viii) Starting System :- Electric Self starter with maintenace free battary including battary charging alternator. C) Batteries :- Batteries of maintenece free of capacity as recommended by the manufacturer complete with copper conductor multistrnded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolyte all as specified of Make as per OEM and :- Starter gear ring, Start and stop push button, Ignition key / Switch, Handling and operation : Slient features of accessories shall be as under: Radiator with blower fan, Corrosion inhibitor coolant, Paper element filters for fuel, lub oil and by pass. mechanical governer controlled direct fuel injection system, Fly wheel housing and fly wheel.
D) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or asper standard practice iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battary volt display. xi) Safety Controls : - Engine low lube oil pressure high water temparature and over speeding of engine. xii) Coupling arrngement : - Flexiable coupling, fly wheel to suit flexiable coupling. xiii) Accessories :- AVM Pads built or separtely mounted to manufactrer base frames. xiv) Base Frame : - Made out of ISMC 250 of sturdy design made of MS channel with necessary reinforcement and predetermined holes. xv) Fuel Tank :- Daily service fuel tank made out of 3mm thick (10G) HR sheet top and bottom with caliberated level indicating arrangement, stop cock, drain plug, fuel pump of 100-150 ltr capacity complete on a common base out side the accoustic enclosure in the sub staion building. xvi) MS pipe line to and from the fuel tank to the DG Set.
Note:- The contractor shall arrange for artificial load for testing for final testing of DG Set at site and the cost is deemed to be including in above offer. G) Accoustic Enclosure:- Manufactured by OEM suitable for 15 KVA DG Set. (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battaries and control panel should be inside the enclosure. (iv) Fuel tank should be out side the enclosure in the sub station building. (v) Construction Details/specification are as follows : - a) Outer body :- CRCA Sheet of 1.6mm thick. b) Doors :- CRCA sheet of 1.6 mm thick c) Sound Insulation :- 100 mm thick rock wool (64kg/Cum) vi) The accoustic should be composite in construction and fully assembled integral unit.
vii) The battaries should be placed inside the enclosure beside the DG Set on a suitable inlsulated plat form. ix) The DG Set should be provided with external Emergency stop push button. x) The enclosure should be suitably illuminated by CFL/FTL Lamp fittings. xi) The noise level should be 75 db at 1m under free field conditions. xii) The accoustic enclosure parts shall be of powder coated after pre treat ment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade.
KHAJURIA ENGINEERS (BID ID -3062491)
VIMAL TRADERS AND SUPPLIERS (BID ID -3062214)
AP BUILDERS (BID ID -3060999)
Rajan Traders (BID ID -3062533)
national engineering (BID ID -3062548)
Intrernational Engineers (BID ID -3061965)
SUMEET TRADING CORPORATION (BID ID -3062376)
FANGALIA TRADERS (BID ID -3054943)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .