Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.7 LAccepted-AOC | L1 | Accepted-AOC REASONABLE | |
| 2 | L2₹43.7 L+₹1.1 L (2.70%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L2 | Rejected-Finance Quoted High rates | |
| 3 | L3₹48.6 L+₹6.1 L (14.3%)Rejected-Finance | L3 | Rejected-Finance Quoted High rates | |
| 4 | L4₹49.2 L+₹6.6 L (15.6%)Rejected-Finance 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L4 | Rejected-Finance Quoted High rates | |
| 5 | L5₹50.4 L+₹7.9 L (18.5%)Rejected-Finance | L5 | Rejected-Finance Quoted High rates |
Tender Value
₹48.5 L
EMD Value
₹97,000
Closing Date
1 Feb 2022, 6:00 pmClosed
GE NDA KHADAKWASLA
GE NDA KHADAKWASLA
SPECIAL REPAIR AND REPLACEMENT OF OVERHEAD TO UG CABLE IN SAMTA VIHAR OFFICERS MESS SERVANT QTRS OC TPS OFFICE TO SAINIK MESS AND 45 MVH AT NDA KHADAKWASLA
2022_MES_499775_1
8579/E8
Open Tender
Civil Works
Item Rate
180 days
GE NDA KHADAKWASLA
As per Tender documents
9 documents required · 9 mandatory
₹500
Yes
₹97,000
Yes
1 Apr 2022
6 Jan 2022
3 Feb 2022
6 Jan 2022
1 Feb 2022
19 Jan 2022
7 Jan 2022 - 18 Jan 2022
Amount
Dismantling cross-arms of MS channel or angle section etc. complete
Dismantling and taking down of ACSR Conductors of any type any size from the existing LT Pole.
Dismantling insulators any type, any size from LT pole cross arms.
Dismantling stay assembly complete from existing LT Pole including earthwork etc.
Dismantling old/US steel pole/ strut poles, any size including earthwork etc.
Dismantling old U/S GI Protection Pipe of 50mm dia from any position.
Supply & Laying, testing and commissioning in trenches LT UG power cables, XLPE Insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) 1100 Volts grade with Multi-stranded aluminium conductor including termination on both side of LT Panel/Feeder Pillar/Street Light Junction Box etc with suitable size of AL Lugs, Cadmium plated high tensile nuts, bolts and washers etc of following sizes :- Make : Polycab/Gloster/Havells/RPG Cables 3.5 Core 120 Sqmm
Ditto all as per item No. 7 above but 3.5 Core 95 Sqmm
Ditto all as per item No. 7 above but 3.5 Core 70 Sqmm
Ditto all as per item No. 7 above but 3.5 Core 50 Sqmm
Ditto all as per item No. 7 above but 3.5 Core 35 Sqmm
Ditto all as per item No. 7 above but 3.5 Core 25 Sqmm
Ditto all as per item No. 7 above but 4 Core 16 Sqmm
Ditto all as per item No. 7 above but 4 Core 10 Sqmm
Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out in for foundation of pole, stay, laying of cable and pipe etc : Hard/Dense soil
Ditto all as per item No. 15 above but soft/disintegrated rocks
Ditto all as per item No. 15 above but hard rocks
Returning and filling in, including spreading and well ramming in layers n exc 25 cm complete all as specified and directed
Removing excavated material a distance n. exc 50 m & depositing where directed at a level n. exc 1.5 m above the starting point.
M & L for laying of half round unreinforced precast concrete pipe, inner dia 150 mm and outer dia 200mm, half round for bottom and half round for top and before laying excavated area/trench shall be leveled, complete all as specified and directed. Note : 01 Half round top and 01 half round bottom together will be considered as one running meter. Make as per sample approved by Engr-In-Charge.
M & L for taking down carefully service connection cable of any size from LT Pole/V-TPN DB etc and re-terminated the same service cable with new LT Panel/feeder Piller /Bus bar Panel etc with and including suitable size of AL Lugs, GI Nut-bolts etc after taking proper shutdown for humen safety complete all as specified and directed
Demolation of Strut Pole and Pole Cooping of any description and in any position.
M & L for earthing complete with galvanized steel earth plate electrode 600 X 600 X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 25 x 4mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to LT Panel/ Feeder Pillars etc. as required including necessary excavation and earth work, in any type of soil concrete pit & chamber in PCC (1:2:4) type B1 & pit cover with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc complete all as specified and directed
M & L in replacement of earthing complete with galvanized steel earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized earth lead wire of 4 mm dia by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to LT Poles /DBs etc. as required including necessary excavation and earth work, in any type of soil concrete pit chamber, cover of PCC 1:2:4 type B1 with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and directed by Engr-in-Charge including testing on completion.
S&F danger notice plate of GI sheet of approved size 200 x 150 mm x 1.6 mm thickness for LT Supply, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed on pole, sub stn yard gate, transformer etc with GI clamps, bolts and nuts etc including taking down existing one complete all as specified and directed.
Supply & Installation including testing and commissioning LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 250 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 2000mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 03 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 320 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 100 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved byGE. (a) MCCB 4 Pole, 415 Volts, 40 Amp, 25 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. (Outgoing) - 04 Nos. Make : L&T/Legrand/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 200 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 2100mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No. (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 03 No (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. (Outgoing) - 02 Nos. Make : L&T/Legrand/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 200 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved byGE. (a) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 63 Amp, 25 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. (Outgoing) - 02 Nos. Make : L&T/Legrand/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 200 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 2100mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 63 Amp, 25 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 03 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. (Outgoing) - 03 Nos. Make : L&T/Legrand/Havells
Supply & Installation including testing and commissioning LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 320 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 2100mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 0 3 Nos (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 250 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The Panel shall be provided manufacturer's name plate, skull and bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T (b) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 100 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (e) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 250 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 2400mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 125 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 03 Nos (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 200 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 500 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 250 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 200 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 400 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE.. (a) MCCB 4 Pole, 415 Volts, 200 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 320 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 200 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by GE. (a) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu suitable for Isolation with both side of spreader links and phase separater and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 63 Amp, 25 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells (d) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 Nos (Outgoing). Make : Legrand/L&T/Havells
Supply & Installation including testing and commissioning Sub Feeder Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front side and nut-bolted for back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminum bus bars, electrolytic grade of 160 Amp current capacity. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side, suitable extended rotary handles, LED Indicating lamps for RYB, ON, OFF & Trip and name plate for all Incoming/Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for each MCCB Incoming and Outgoing Cable with suitable size of SS Cable Glands including 2 Nos of GI Earthing Terminals one on each side of the Panel including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved byGE. (a) MCCB 4 Pole, 415 Volts, 63 Amp, 25 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 01 No (Incomer). Make : Legrand/L&T/Havells (b) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 No (Outgoing). Make : Legrand/L&T/Havells (c) MCCB 4 Pole, 415 Volts, 25 Amp, 16 KA Breaking capacity, thermal adjustable type with Ics = 100% of Icu suitable for Isolation including suitable size of spreader links and phase separator on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed. - 02 No (Outgoing). Make : Legrand/L&T/Havells
S & F of LT Busbar panel weather proof outdoor type single door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7032 ( Siemens Gray) shade with matt finish with seven tank pre treatment process. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-43, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable. The panel shall be provided with aluminium bus bars electrolytic grade of 200 Amps current rating including required size of nut bolts for fixing of cables upto 120 Sqmm. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding and fix horizontally. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment. All joints and connection shall be done with galvanised or cadmium plated high tensile nuts, bolts, washers and AL Lugs etc. The panel shall be provided with 04 Nos 50mmx50mmx5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint including earth work and grouted in PCC 1:3:6 at suitable depth as per site requirement including taking down existing one. The overall size of the Busbar panel shall not be less than 500mmx300mmx700mm (LxWxH) including 4 Nos cable entry holes suitable for cable entry up 3.5 C 150 Sqmm at bottom complete all as specified and directed Engr in Chrage.
M&L for preparation of existing surface of steel tubular pole by srapping down peeled off old paint, cleaning etc of length 8.5/9/11 mtrs and cross arms etc and applying one coat of aluminium coat paint including rewriting pole Nos as directed with black paint complete all as specified and directed
M&L for 4 Way TPN DB-VTPN 160 Amp MCCB DB's, as per IEC 61439-3, suitable for flush mounting and surface mounting with 250 Amp copper busbar for each phase, 2 neutrals bar, 2 earth busbar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, improved Pan assembly for installation, IP-30 with and including 1 x 3P, 63 Amp, 16 KA, MCCB as incomer and 04 x 3P, 40 Amp, 10 KA, MCB's as outgoing complete all as specified and directed. Make : Legrand/L&T/Havells
S&F including commissioning digital automatic timer switch distribution panel board, factory assembled in powder coated steel sheet enclosure, comprising of 4P MCCB, 40 Amps, 16 KA and 3 Pole, 40 Amps power contactor and 230V digital time switch for controlling LED street lights, including earth work for fixing Timer switch distribution panel board and shall be provided 4 Nos 25x25x4mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth complete all as specified and directed at site. Make : Legrand/L&T/Havells
S&F on pole, SMC Junction box inner dimensions (300 x 200 x 105)mm (LxBxD), 3 phase 4 wire system, including cable connecting base, 6 Amp DP MCB with mounting SS railing, Cable lugs suitable to 10/16 Sqmm 4 core cable, connection for incoming and outgoing cables including suitable fixing arrangement on pole etc complete all as specified and directed by Engr-in-Charge.
S&F of cable route Marker made up of Cast Iron of dia 100 mm and thickness 4.65 mm with supporting angle iron of size 20 x 20 x 3 mm and height 0.6 mtr for stand including priming, painting and wirting of "LT CABLE" with Arrow Direction in suitable size of letter including necessary earthwork and grouted at suitable depth in PCC 1:3:6 Type C2 using 40 mm graded aggregate in mass concrete complete all as specified and directed at site by Engr-in-Charge.
M&L for PCC (1:3:6) type C2 (Using 40 mm graded stone aggregate ) for base and foundation, filling & mass concrete for existing Pole Cooping, approach path way etc complete all as specified and directed at site by Engr-in-Charge.
M&L for core cutting from 50 to 80 mm dia in any type of wall and any thickness of wall complete all as speciified and directed at site by Engr-in-Charge.
S & F 2.5 Sqmm 3 core Weather proof AL stranded cable PVC insulated not less then 7 mtr on existing street lights and properly drawn through existing street light bracket and hole of street light pole including making of two 20mm hole on existing street light pole and taking down existing 2.5 Sqmm aluminium twin core cable complete all as specified and directed at site. Note : The contractor shall be responsible for any damage due to the existing street light and the damaged parts of street light shall be replaced by the contractor without any extra cost to the Deptt.
S&F in replacement LED street light fiitting 35 Watt, 230V, AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impect and corrosion resistant including thermal management in multiple optics complete with IP 65 protection including complete fixing to pole/wall with necessary nut, bolts and washers etc complete all as specified and directed. Make: Luker/Crompton/Bajaj
M & L for road cutting of size (0.45 x 0.45) mtr as required for laying pipe/cable etc including earthwork and necessary excavation including making good with required material to match with the existing one or with PCC (1:2:4) type B1 complete all as specified and as directed.
M&L for PCC Cutting of size (0.45 x 0.45) mtr as required for laying pipe/cable etc including earthwork and necessary excavation including making good with required material to match with the existing one or with PCC (1:2:4) type B1 complete all as specified and as directed at site.
M&L for GI tubes, light Grade, galvanised with all fittings, laid in trenches or with pole for protection by bending and grouted in cooping including fixing on wall/sufrace with suitable size of GI shaddle, screws, etc of following sizes complete all as specified and directed :- 50mm bore complete all as directed.
Ditto all as per item No. 53 above but 80mm bore
Ditto all as per item No. 53 above bu 100mm bore
M&L of GI strip 25 x 4 mm earth as earth continuity conductor or main earthing lead fixed to wall batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation etc.
Adinath Technical Services
SHREE VAIBHAV ELECTRICALS
KESARI AND SONS
SONU ENTERPRISES
A.S.ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .