| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹32.4 CrAdmitted-Finance | -10.32% | ₹32.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹32.9 CrAdmitted-Finance | -9.14% | ₹32.9 Cr | L2 | Admitted-Finance |
| 3 | L3₹33.3 CrAdmitted-Finance | -7.86% | ₹33.3 Cr | L3 | Admitted-Finance |
| 4 | L4₹38.8 CrAdmitted-Finance N 29 ADINATH NAGAR OPP WORLD TRADE PARK JAI JAWAN COLONY III MALVIYA NAGAR JAIPUR 302034 RAJ | JAIPUR | JAIPUR | RAJASTHAN | 302034 | +7.29% | ₹38.8 Cr | L4 | Admitted-Finance |
| 5 | L5₹43.8 CrAdmitted-Finance | +21.07% | ₹43.8 Cr | L5 | Admitted-Finance |
Tender Value
₹36.2 Cr
EMD Value
₹72.3 L
Closing Date
12 Feb 2026, 6:00 pmClosed
EXECUTIVE ENGINEER BDA BIKANER
BDA CAMPUS BIKANER
E-NIT-51-II-2025-26 WORK NO 01 Construction of New Office Building In Jodbeed Scheme Area of BDA, Bikaner Development Authority (BDA) PHASE-I
2026_UITBK_528045_1
E-NIT-51-II-2025-26
Open Tender
Civil Works
730 days
BIKANER
E-NIT-51-II-2025-26 WORK NO 01 Construction of New Office Building In Jodbeed Scheme Area of BDA, Bikaner Development Authority (BDA) PHASE-I
2 documents required · 2 mandatory
₹10,000
SECRETARY BDA BIKANER
₹72.3 L
Yes
BDA BIKANER
7 Mar 2026
15 Jan 2026
13 Feb 2026
15 Jan 2026
12 Feb 2026
15 Jan 2026
15 Jan 2026 - 12 Feb 2026
29 Jan 2026
Building Civil Work
Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish lead up to 50 Mtr. and lift up to 1.5 Mtr. : All kinds of soil
Carriage of Materials: Earth, Sand, Lime, Morrum manure or sludge and Building Rubbish Stone metal (Grit and ballast etc.) For 5 Km.
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m , disposed earth to be levelled and neatly dressed : All kinds of soil
Add extra for foundation/trenches/drains for every additional lift of 1.5 Mtr. or part thereof in. All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidating each deposited layer by ramming and watering including lead up to 50 meter and with all lift.
Diluting and injection Chloropyrifos Emulsifiable concentrate 20% with 1% concentration for PRE-CONSTRUCTIONAL Anti termite treatment as per IS 6313 part III as amended from time to time and creating a continuous chemical barrier under and around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor along the external perimeter of building expansion joints, over the top surface of consolidated earth of which aproch is to be laid surrounding of pipes and conduits etc. complete as per specification (Plinth floor area only shall be measured for payment and excluding the cost of chemical emulsion) .
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/Lindane emulsifiable concentrate of 20%
Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. . M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).
Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix
Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. M20 grade Nominal Mix / Design Mix
Providing and laying in position Ready mix concrete manufactured in fully automatic Batching Plant and transported to site in transit mixer for having continous agitated mixer, manufactured as per approved mix design of specified grade of RCC work including pumping of R.M.C. from transit mixer to site of laying , exculding the cost of centering, shuttering and reinforcement with all lead and lift including cost of admixtures in recommended portion as per IS 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge. All works upto floor V floor M20 grade Design Mix by using cement as per codal provision.
Add extra for providing richer mixes respectively at all floor levels Providing M-25 grade concrete by using cement as per codal provision instead of M-20 grade design mix.
Providing, hoisting and fixing up to floor five level precast reinforced concrete work in Nominal M20 grade mix including cost of required centering, shuttering, finishing, smooth with 6 mm thick cement plaster 1:3 (1 cement: 3 fine sand) on exposed surface complete excluding cost of reinforcement . String courses, copings, bed plates, anchor blocks, plain window sills etc
Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc.
Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : Columns, pillars, posts and struts etc.
Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : Walls (any thickness) including attached pilasters, buttresses plinth and string course.
Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc.
Add extra for additional height in centring, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan are is to be measured)
Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. ('Original producers' who manufacture billet directly from iron ores and roll the bilets to produce steel conforming to IS:1786). Thermo-mechanically Treated bars (Conforming of relevent IS code)
Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: Cement Mortar 1:4 ( 1-Cement : 4-Sand).
Random Rubble stone masonry with hard stone in superstructure above plinth level and upto five level above 30cm. thick walls in : Cement Mortar 1:4 ( 1-Cement : 4-Sand).
Plaster on new surface on walls in cement sand mortar 1:4 including racking of joints etc. complete fine finish : 25mm thick .
Random rubble dry stone Kharanja under floor.
Supplying and applying bituminous solution primer on roofs or on wall surface at 0.24 litre per sqm.
Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand)
Half brick masonry in Superstructure , above plinth level upto floor V level using bricks of designation 75 Cement mortar 1 : 4 (1 cement : 4 coarse sand)
Add extra providing and placing in position 2 Nos. ,6mm Ø M.S. bar at every third course of half brick masonry .
Providing and fixing 50mm thick extruded polystyrene rigid insulation board of required size between cavity wall, complying with ISO 4898:2008 & ASTM C 578-08b - type VI having thermal conductivity of 0.0289 W/m K as per ASTM C 578 (measured as per IS 3346), compressive strength of >350 kPa listed as per ASTM D 1621, density of 34-36 kg/m3 as per ASTM D 1622, water absorptions =< 1% by volume as per ASTM D 2842, oxygen index of 24.1 to 28.1 listed as per ASTM D 2863, cell size 0.4 mm of dia (max) as per ASTM D 3576. Fire retardent property as per DIN 4102, part 1 of class B2 and as per ASTm E84 class A, fixed with suitable water based adhesive and fastener, complete in all respect as per the diretion of Engineer-in-Charge.
Add extra over item of brick work with class designation 100 in substitution of class designation 75 : Quantity in Sqm.
Add extra over item of brick work with class designation 100 in substitution of class designation 75 : Quantity in Cum.
Add extra for Square or Rectangular Pillars in Superstructre brick work up to five storey Upto 90 cm length and all sides are free
Nano technology water proofing or anti stain protection coating 5-7 layer process for increasing life of all stone fascia/facades/flooring or stone building and damage control protection, life 7-9 years, warranty 5 years-- before coating washing of stone and degreasing of that area is done 1 coat. (Removing of algae/moss/blackness/stains/rust etc. is extra) then after drying doing 1 coat of Nono technology hydrophobic prime. After this on dry area Nano technology water proofing treatment in 3 coats wet on wet. In case of anti stain treatment 2 top coats of anti stain, anti slippery, natural transparent high shine or matt chemical treatment is done.
Providing & Fixing of ward robe shutters made out of 19mm thick BWP block board ISI of superior quality make with following details :- Front side finishing with 1mm thick superior quality mica approved make and 0.8mm thick approved shade mica in the inner side. Covering with teak wood beading 25x12mm all the sides of shutter & 35x12mm on outer frame for making good the wall joint including heavy brass S.S. fittings (Handle 200mm 2 Nos., Tower Bolt 150mm 2 Nos., Brass Lock 1 Nos., Magnetic Catcher 2 Nos., Brass Hinges 75x40x2.5 mm 6 Nos., SS Hanger Rod 20mm dia) complete as per drawing and design approved by Engineer in Charge.
Supplying and fixing in walls machine cut and polished stone shelves, tands and in CM 1:3 with machine cut edges : Kota stone minimum 30mm thick.
Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish : 20mm thick.
6 mm thick cement plaster to ceiling of mix 1:3 (1cement : 3-fine sand)
Providing and Applying ACRYLIC emulsion polymer waterproofing chemical coating, on over roof on over roof slabs/terrace/balconies/parapet wall etc.with following method/specification: Paint the surface with regular paint brush so as to obtain approximately 0.3mm thickness coating. apply the 2nd coat next day at right angles to the 1st coat so that total thickness of the coating should be approximately 0.6mm coverage by using above formulation will be 40 ft2/ litre of chemical. painted surface does not require any external water curing since chemical will hold sufficient water for curing.After the primer coat Apply 2 coats of modified acrylic emulsion polymer water proofing compound having solar heat reduction properties coating @ 0.330 KG/SQM on the surface of the interval of 3-4 hours. Undulation on the surface is repair before the waterproofing work.
Grading roof for water proofing treatment with water proffing compound .Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
P & F 1st quality Heavy Duty Vitrified glazed MAT tiles on floor, skirting and steps etc.in different sizes (thickness minimum 10mm) with water absortion less than or equal 0.08% and conforming to IS 15622 of approved make in all colour and shade, laid with 20 mm thick CM 1: 4 including grounting the joints with white cement and matching pigment etc complete. size 600 mm X 600 mm
Precast terrazzo tiles of approved make 20mm thick with marble chips of size upto 6mm in skirting & risers, treads of steps and dados 12mm thick cement plaster 1:3 (1 cement : 3 coarse sand) jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete with tiles of :. Light shade using white cement.
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10mm and down gauge) including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of : Ist course of applying cement slurry @ 4.4 Kg/sum mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. IInd course of 20mm cement plaster 1:3 (1 cement: 3 coarse sand) mixed with water. proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface.. IIIrd course of applying blown or residual bitumen applied hot at 1.7 Kg per sqm. of area. IVth course of 400 micron thick PVC sheet .(Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 Kg/sqm.)
Providing and fixing 1st quality standard Marble printed/ Granite Shade or Light/dark shad glazed tiles confirming to IS : 13753 & IS :15622 of size 300mm x 600mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).
Providing and fixing 1st quality MAT finished ceremic tile size 300x300mm confirming to IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4).
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete
Providing and applying white cement based putty over plastered surface to prepare the surface even and smooth complete New Plastered Surface (three or more coats)
Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade including all scaffolding: Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect.
Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specifications including primer coat and protecting coat including scaffolding and safety. Trowel Finish av. thickness 2000 to 2500 microns.
Providing and fixing at all height false ceiling including providing and fixing of frame work made of special sections power pressed from M.S. sheet and galvanised in accordance with zinc coating of grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm thick with flanges of 22mm and 37mm at 1200mm centre to centre one flange fixed to the ceiling with dash fastener 12.5mm diax40mm long with 6mm dia bolts to the angle hangers of 25x25x0.55mm of required length, and other end of angle hanger being fixed with nut and bolts to G.I. channels 45x15x0.9mm running at the rate of 1200mm centre to centre to which the ceiling section 0.5mm thick button wedge of 80mm with tapered flanges of 26mm each having clips of 10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to G.I. channel with connecting clips made out of 2.64mm diax230mm long G.I. wire at every junction including fixing the gypsum board with ceiling section and perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450mm centre to centre with 25mm long drive-all screws @ 230mm interval including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes, finisher and two coats of primer suitable for board as per manufactures specification and also including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in-charge but excluding the cost of painting with POP.
Kota stone slab flooring 25 mm thick over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) For area of each slab from 2001 to 5000 Sq.Cm
Providing and fixing pressed steel door frames confirming to IS 4351 manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.25mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb including steel butt hinges 2.5mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface including filling with CC 1:2:4(M15 grade) complete as directed by Engineer-in-charge : Profile B
Providing and fixing of uPVC Sliding windows: Frame Made from the Extruded uPVC Window Profile Section of size 106w x 50h mm having outer wall thickness of 2.5mm (+/- 0.2mm) and 3 box multi-chamber construction, White in finish, duly reinforced with 1.2 mm thick GI section. Frame shall have three track configuration, two for sliding of window shutter and one for mosquito mesh shutter. Vertical member of frame which bears the sliding shutter load shall have aluminium rail/track for smooth sliding of shutter rollers. All the four corners shall be mitered cut & thermal welded so as to form window frame. Frame shall be milled with drain and air equalizer hole in order to be water tight and for drainage of accumulated water, if any, to outer side. Shutter : The shutter of sliding window shall be made of 39w x 69h mm Extruded 3 box multi- chamber uPVC Window Profile Section of white colour having outer wall thickness of 2.5mm (+/- 0.2mm) provided with reinforcement of 1.5mm thick GI section duly mitered cut & thermal welded at all corners and fitted with uPVC glazing bead of size 22 x 20 mm with inner and outer co-extruded EPDM/TPE-E weather seal gaskets alongwith 6mm thick ISI make plain float glass. Mesh shutter shall be made of 39w x 69h mm Extruded 3 box multi-chamber UPVC Window profile section of white colour having outer wall thickness of 2.5mm (+/- 0.2mm) provided with reinforcement of 1.5 mm thick GI section duly mitered cut & thermal welded at all corners and fitted with nylon/polymer mesh and rollers/pully.
Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure 'A' :.35 mm thick . Commercial Veneer both side
Extra for providing external lipping with 2nd class teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured) Over item no. 8.13.
Providing & Fixing mica of approved make for inner/outer side of shutters with fevicol & nails complete as per approved by engineer in charge. 0.8mm thick mica
Extra for cutting rebate in flush door shutters for making double leaf shutter(Total area of the shutter to be measured).
Providing and fixing Granite stone slab mirror polished and machine edge cut in walls, pillars, steps, Shelves, Sills Counters, Floors etc. laid on 12mm (Av.) thick base of cement mortar 1:3 (1 cement : 3 coarse sand) jointing with white cement mortar 1:2 (1white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. South Zed Black. Above 3601 Cm2 Slabs
Providing and fixing stone slabs table rubbed, 15-18 mm thick in Walls, Steps, Pillars, Counters, Jambs, Shelves, Sills etc. laid on 12mm (Av.) thick base of CM 1:3 (1 cement : 3 coarse sand) jointing with white cement mortar 1:2 (1white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. Keseriaji/ Abu Ambaji (Green Marble)Above 3601 Cm2 Slabs
Extra for providing edge moulding to 15-18mm thick marble/ Granite/Kota stone counters, Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite/Kota Stone Work. Full Edge moulding
Providing & Laying Tactile tile (for vision impaired persons is standard of size 300x300x20mm and confirming to IS 1231 of 1980 (Re affirmed in 2006) in all colours & sheds further product should confirm ASTM 303 for shad resistance and DIN51099 for colour fastness etc. laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 course sand) in all shapes & patterns including grouting the joint which white cement mixer) will matching pigments etc complete is per direction of Engineer-in-charges. Grade M 30
Add extra for Fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick-set tile adhesive (Water based) conforming to IS: 15477 , using 5kg. adhesive per sqm of tile area, in average 3mm thickness instead of cement mortar.
Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide
Providing and fixing in position collapsible steel shutters with vertical M.S. Channels 20 x 10 x 2mm and bracket with flat iron diagonals 20 x 5mm. size with top and bottom rail of T-iron 40 x 40 x 6mm. with 40mm dia steel pulleys/ball bearing complete with bolts, nuts locking arrangements inside and outside stoppers, handles etc. as per specification including applying a priming coat of approved steel primer. (To be measured and paid as per outer dimension).
Providing and fixing 1mm thick M.S. sheet sliding-shutters with frame & diagonals braces of 40 x 40 x 6mm. angle iron 3mm M.S. gusset plates at the junction and corners, 25mm dia pulley 40x40x6mm angle and T-iron guide at the top and bottom respectively including applying a priming coat of approved steel primer.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
Making khurras 450 x 450mm with average minimum thickness 50mm cement concrete 1 : 2:4 over P.V.C. Sheet 1 Mtr. x 1 Mtr. x 40micron finished with 12mm cement plaster 1 : 3 and one coat of neat cement, rounding edges and making and finishing the out let complete.
For shutters builtup standard tubular sections of openable doors ,windows & ventilators including providing & fixing hinges / rollers etc. and making provision for fixing of fittings wherever required (lockes shall be paid for separately). Polyester Powder coating aluminum ( minimum thickness of powder coating 50 micron)
10 mm thick glass
Providing and fixing 12 mm thick prelaminated three layer medium density (exterior grade ) particle board Grade I, Type II conforming to IS : 12823 bonded formaldehyde synthetic resin ,of approved brand and manufacture in paneling fixed in aluminium doors ,windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and direction of engineer-in-charge.Prelaminated particle board with decorative lamination on both sides.
Providing and fixing stainless steel railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). Grade 304
Providing and fixing Glass Brick with adhesive in line and length complete as per drawing and design and asapproved by Engineer-in-Charge.
Extra for providing toughened glass panes instead of ordinary float glass panes in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).
Providing and fixing IS : 3564 marked aluminium extruded section body tubular type universal hydraulic door closer with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing glazing in aluminium door, window ,ventilator shutters and partitions etc. with PVS / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge.(Cost of aluminium snap beading shall be paid in basic item.) With float glass panes of 5.0 mm thickness ( weight not less than 13.50 kg/sqm)
Providing and fixing Structural glazing work with toughened glass of 6mm thick and reflective colour as approved in dark shade like Blue/Dark Blue etc. with frame work of curtain section 65x60mm (Weight 1.64 kg/m min.) made of aluminium with chrome plating. Internal frame work will also be of curtain section 65x60mm of chrome plated aluminium section with20x20mm aluminium tube section and structural spacer made of rubber. The aluminium frame work size as per instruction of Engineer-in-charge and including openable panels with all necesary sections and fitting.The work include silicon structural adhesive for complete gripping of glass with framing members and silicon weather seal sealant to prevent moisture/water through joints. Glass will be fixed in plumb and with uniform spacing of 10-12mm wide duly filled with silicon weather seal sealant. The work includes all labour,scaffolding , structural aluminium work, toughened glasses,silicon weather seal sealant, silicon structural adhesive structural spacer, all accessories like handles, peg stays, M-15 grade cement concrete for fixing holdfast .(Face area of glass shall be measured)
Providing and laying structural reinforced/ prestressed cement concrete (design mix) of specified grade using batching plant, transit mixer, concrete pump and vibrator in superstructure at all levels including cost of steel form work complete as per clause 1500, 1600 and 1700 of MoRT&H specification including all scaffolding, material, labour, machinery etc. including Providing /mixing of synthetic fibers compulsorily complying with IS 16481:2022 of 06 mm/12 mm length to be mixed @ 0.25% by weight of Cement i.e. 125 gms per 50 kg Cement up to 900 gms per cum of Concrete/ mortar. For T-beam & slab
Providing and laying High tensile steel wires/ strands at any level including all accessories for stressing, stressing operations and grouting complete as per drawing, technical specification and as per clause 1800 of MoRT&H Specification.
Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: Cement Mortar 1:6 ( 1-Cement : 6-Sand).
Random Rubble stone masonry with hard stone in superstructure above plinth level and upto five level above 30cm. thick walls in : Cement Mortar 1:6 ( 1-Cement : 6-Sand).
Pointing on stone masonry in cement sand mortar 1:3 (1 cement : 3 sand) :Deep groove pointing
Supplying and fixing machine cut fine dressed Red/Pink sand stone dasa or coping, with full moulding if required laid on cement mortar 1:4 including pointing with admixture of pigment matching with the stone shade. 50 mm thick
Extra if square,rectangular hollow tubelar sections are used or grill made by flats only
Painting exterior surface of Wall with 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty, etc complete in all respect including scaffolding and safety provision New Work
Earth work in rough excavation, banking excavated earth in layers not exceeding 20cm in depth, breaking clods watering, rolling each layer with 1/2 tonne roller, or stone or steel rammers and rolling every 3rd and top- most layer with power roller of minimum 8-10 tonne capacity and dressing up in embankment for roads, flood banks marginal banks and guide banks or filling up ground depressions, lead up to 50 Mtr. and lift up to 1.5 Mtr.: All kinds of soil
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter. All kinds of soils
Granular Sub-Base with Close Graded Material (Table:- 400-1). Plant Mix Method. Providing laying spreadingand compacting specifiedgraded sand, gravel (crushed stone) asper Table 400-1,400-2 or any other course material as per design mix,as per CBR in sub base course including premixing thematerial atOMC inwetmixplant, carriageofmixed material spreading in uniform layers with motor grader F.E loader on a prepared base and compacting with vibratory roller to achieve desired density (as per I.S.2720) including all material, labor, machinery, lighting guarding, barricading and maintenance of diversion complete.[MoRTH specification : Clause 401]. By mechanical means.
Dry Lean Cement Concrete Sub- base. Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 150 kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, laid with a paver with electronic sensor, compacting with 8-10 tonnes vibratory roller, finishing and curing.
Cement Concrete Pavement. Construction of un-reinforced, dowel jointed at expansion and construction joint only, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 602.2.2 M30 (Grade), coarse and fine aggregates conforming to IS:383, maximum size of coarse aggregate not exceeding 25 mm, mixed in a concrete mixer of not less than 0.2 cum capacity and appropriate weigh batcher using approved mix design, laid in approved fixed side formwork (steel channel, laying and fixing of 125 micron thick polythene film, wedges, steel plates including levelling the formwork as per drawing), spreading the concrete with shovels, rakes, compacted using needle, screed and plate vibrators and finished in continuous operation including provision of contraction and expansion, construction joints, applying debonding strips, primer, sealant, dowel bars, near approaches to bridge/culvert and construction joints, admixtures as approved, curing of concrete slabs for 14-days, using water finishing to lines and grade as per drawing and MoRTH Specification Clause 602 including vaccum dewatering process with all required equipments
Construction of Embankment with Material Obtained from Borrow Pits. i.Construction of embankment with approved material obtained from borrow pits with a lift upto 1.5 m, transporting to site, spreading, grading to required slope and compacting to meet requirement of Tables 300-1 and 300-2 with a lead upto 50 m as per MoRTH Specification Clause 305.3
M-50 100mm thick to be used in heavy-traffic ( Heavy traffic is defined as a daily traffic of 450-1500 commercial vehicles exceeding 30 KN laden weight, or an equivalent of 2.0 to 5.0 MSA for a design life of 20 years.) like Bus terminals, industrial complexes, mandi houses roads on expansive soils, factory floor , service station, industrial pavements.etc. Category A Denated units to key into each other on four faces zigzag shape as per IRC SP 63:2004
Providing and laying of paver block as per IS 15658 : 2006 (Indian standard for precast concrete block for paving- specification) and IRC : SP:63-2004 (guidelines for the use of interlocking concrete block pavement) M-30, 60 mm thick to be used in non traffic areas like building premises, monument premises, land scapes, public gardens/ park, domestic drives, paths and patios, Embankment slopes, sand stabilization Area etc.( As per table 1 of IS 15658:2006. Category A Denated units to key into each other on four faces zigzag shape as per IRC SP 63:2004
Add extra over rates of item No. 11.38, A to C if colored paver blocks are useds
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement in position to the required line, level and curvature jointed with cement mortar 1:3 (1 cement : 3 coarse sand ) including making joints with without grooves (thickness of joints except at sharp curve shall not to more than 5mm) including making drainage opening wherever required complete including painting etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineerin- charge).
Brick masonry with F.P.S. bricks of class designation 75 in foundation and plinth with bricks Cement mortar 1 : 4 (1 cement : 4 coarse sand)
Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: New work (Two or more coats applied @ 3.84 kg/10 sqm).
Supplying and applying bituminous solution primer on roofs or on wall surface at 0.24 litre per sqm.
Random rubble dry stone Kharanja under floor.
Marking Centre Line and stop lines etc. on road as per IRC pattern with thermoplastic paint of approved quality and make without glass beads laid on the road surface at temperature 160" C with a special applicator machine complete with a special applicator machine complete with labour material and traffic diversion arrangements.
Raised Payment Marker (Cats Eye) : Supplying and Fixing of Molded Shank Raised Pavement Markers made of ABS Moulded body and Polycarbonate Reflective panel swith Micro Prismatic Lens capable of providing total internal reflection of the light enter ing the lens face and shall support a load of 35000 Kilogram tested in accordance to ASIMD 4280 & ASTMD 788. The Height of Road Studis 20mm, Width 100mm, Length 100mm and minimum reflective are a of 13 sqcm one ach side.The Strength of detachment of the integrated cylender shank not less than 14+/-2mm (Thickness) and height not less than 30+2 mm from the body. Fixing will beby drilling holes on the road for the shanks to go inside, without nails and using epoxy resin based adhesive
Providing and fixing PVC Bump Speed Breakers size 350 mm x 250 mm x 50 mm fitted with key hooks complete with labour material and traffic diversion arrangements.
Earth work in surface excavation not exceeding 30cm. in depth butexceeding 1.5 meter in width as well as10 Sqm on plan including disposal of excavated earth up to 50 Mtr. and lift up to 1.5 Mtr. disposed soil to be levelled and neatly dressed: All kinds of soil
Supply & Stacking good soil of earth at site complete including loading unloading & Transportation etc. Good soil of earth
Supply of dry manure including loading unloading,transportation & stacking at site. Compost
Supply of dry manure including loading unloading,transportation & stacking at site. Goat dungmanure.
Supply of Chemical Fertilizers at store in bags weighing not less than 50 kg each including loading unloading & transportation DAP
Spreading of manure , good earth in required thickness (cost of manure and good earth to be separately )
Laying of lawns including ploughing leveling breaking of clods manuring and removal of stones etc. (cost of manure or extra good earth to be paid separately )maintenance of lawn foe 30 days or more till the grass forms a thick lawns free from weeds and fit for moving in the duration of planting if lawn die some where the contractor will replant it at his own cost in rows 5 cm apart in either direction
Supply & Planting of shady plants ( Neem. Peepal, Goolar, Jamun, Imli or other specified) along road side including the following activities:- 1. Preparation of soil including cleaning & removing of unwanted shrubs removal of stones & garbage. 2. Supply of plant at site of two years of age & height more than 1.50 Mtr. 3. Supply of dry manure(Farm yard manure organic) 4. Supply of Insecticides. 5. Digging of pits size 60x60x60 cms. Including removal of stones. Manuring application of insecticides & watering at least 1.5 Liter per plant after planting 6. Half brick Circular tree guard in second class bricks, internal dia 1.25 meter and height 1.20 meter above ground and 0.20 meter above ground and 0.20 meterr below ground. Bottom two courses laid dry and top three couses in cement mortar 1:6 ( 1 Cement : 6 Sand) and the intermediate courseses being in dry honey comb masonry. As per design complete. 7. Watering to plants 8. Maintance of plants by the contractor including pits, preparation of Thavala Hoeing weeding etc & application of insecticiedes etc. & security. If the plant die during maintence contractor has to rplace same heingh plant at his own cost.
Supply & Panting of ornamental plants ( Kachnar, Amaltas, Gulmohar, Arjun, Kala, Siris, Jacranda etc. or other specified) along road side including the following activities :- 1.Preparation of soil including cleaning & removing of unwanted shrubs removal of stones & garbage 2.Supply of plant at site of two years of age & height more than 1.50 Mtr. 3. Supply of dry manure( Farm yard manure organic) 4. Supply of Insecticides 5. Digging of pits size 60x60x60 cms. Including removal of stones. Manuring application of insecticides & watering at least 1.5 liter per plant after planting. 6. Half brick Circular tree guard in second class bricks. Internal dia 1.25 meter and height 1.20 meter above ground and 0.20 meter below ground. Bottom two courses laid dry and top three courses in cement morter 1:6(1 Cement : 6 Sand) and the intermediate courses being in dry honey comb masonry. As per design complete. 7. Waterring to Plants. 8. Maintenance of plants by the contractor including pits. Preparation of Thavala Hoeing weeding etc. & application of insecticides etc. & security. If the plant die during maintencance contractor has to replace same height plant at his own cos
Construction of tubewell up to 100m depth and above to accomodate housing and assembly pipe in all types of alluvium strata by rotay drilling method with "code of practice for construction and testing of tubewells (IS:2800 (Part-II) : 1991 and IS:2800 (Part-II) :1979 both amended up to date) with supply of bail plug if necessary.The work will not include cost of housing pipe and strainer pipe assembly cost, gravel and development work. Work would be deemed completed only after obtaining sound free water during pumping. 200 mm nominal bore
Supply of strainer pipes made of ERW M.S. black pipe ISI mark of following sizes at the site of work including required size of slotting as per IS:8110-1985. 200mm-do-.
Construction of Recharge Shaft in filter pit including Earth work Excavation , lifting excavted earth with all lift and 50 m lead and centering & shuttering evenever required. Diameter 900 mm
Supply & fixing Pre-cast RCC Rinngs at the mouth of recharge shaft of M20 mix with 40 mm thickness. Diameter 900 mm
Supply & lowering air line of 25mm dia, G.I. pipe 'B' class having perforation 3 to 5mm size all arrow of G.I. pipe in Zig-Zag fashion & making air vent at top including the cost of Tee-Nipples, Elbow, Socket etc.
Supply & lying River-gravels of following sizes in recharge shaft, filter pit after screening & washing from kachha shift without deduction of voids . Size 9 to 12 mm
Size 3 to 5 mm
Supply & laying of clean, clear sharp river sand of size 1 to 2mm coarse, without deduction of voids.
S & F tube well cover of M.S.sheet (6mm thick) with nuts and bolts complete for casing size: 200mm dia
Inside depth upto 0.5 M to 1.0 M –do-
P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /make including joining the pipe with solvent cement rubber ring and lubricant. 160 mm dia
Providing & Laying C.C. 1:3:6 (Stone Agreegate 20mm nominal size) all around PVC Pipe including 7.5 cm thick bed concerte [Width & Height = Dia of Pipe in CM+15CM] excluding cost of Pipe & Excavation of trenches etc. PVC pipe 160 mm dia
P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: Coupler (socket). 160 mm dia
P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: Bend 87 .5 160 mm dia
Supplying and fixing Ferro- cement cover with C.I. frame for chambers & man holes of size. 500mm dia 22 Kg.-do-22 MT centre point load (Heavy duty).
Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete : Serrated with central bulb (225 mm wide, 8-11 mm wide)
P & F M.S. Foot Rests in with C.M.,1:3, standard design in 20mm square M.S. bar 50 mm embedded in wall & 10 cms. projected out complete.
Supplying and fixing C.I. Cover with frame, C.I. gratings for chambers & man holes.
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer-in-charge. 1: 3: 6 or richer mix.
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar.
Demolishing stone rubble masonry manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge: In cement mortar.
Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50metres lead.
Dismantling old plaster or skirting, raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 meter lead.
Wiring
WIRING: Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Short point (up to 3 mtr.)
Medium point (up to 6 mtr.)
Long point (up to 10 mtr.)
Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Medium point (up to 6 mtr.)
Long point (up to 10 mtr.)
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.On board
Long point (up to 10 mtr..)
S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 20 mm
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 3x 1.5 sq.mm
2 x 2.5 sq. mm. + 1x1.5sqmm
4 x 4.0 sq.mm
2 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
4 x 6.0 sq.mm
2 x 6.0 sq. mm. + 1 x 4.0 sq. mm.
4 x 10.0 sq.mm
4 x 16.0 sq.mm
ELECTRICAL ACCESSORIES.
P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 1.2 mm thick M. S. Sheet boxes 75mm x 75mm x 60mm
150mm x 75mm x 60mm
175mm x 100mm x 60mm
225mm x 100mm x 60mm
200mm x 150mm x 60mm
P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 10 A one way switch
10 A two way switch
10 A bell push
16 A one way switch With Led Indicator
25 Amp. 2 Module switch With Led Indicator
Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.6 A 3/5 pin shuttered socket
6/16 A shuttered socket
25 Amp. 2 Module Socket
Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR5 step fan regulator 2 Module 360 dgree rotating
Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRBlanking plate
25 Amp. 2 Module Motor Starter with on / off Push button
LED Skirting /Foot Light 2 Module
Electronic Chime/Buzzer 2M
Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 1/2 Module
3 Module
4 Module
6 Module
8 Module
12 Module
Providing & Fixing of ISO certified company made virgin material PVC trunking system as per PWD specification for electrical Works, with double lock feature for cable management including finishing accessories like corners, tees, adjustable angles, junction etc. as required . The trunking system shall have adaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover. OEM shall have submit NABL accrediated /CPET lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 32mm X 20mm
100/105mm X 50mm
150/160mm X 50mm
DB & MCB.
Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Metal door (single phase) IK-09 and IP-43 with Metal end box. 6 Way (6+2)
Metal door (Three phase) IK-09 and IP-43 with Metal end box. 6 Way
Providing & Fixing of Recessed/surface mounting heavy duty Flexi / Row type Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted with reversible door (metal or Glazed) complete with 100 Amp. copper shorting link , neutral link, earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, ferrules detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR .Metal door IK-09 & IP-43 with Metal end box. 2 Row 28 Module(14 module per row)
4 Row 56 Module(14 module per row)
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Single pole MCB (With B/C curve tripping Characteristics).. 6 A to 32 A rating
Double pole MCB(With B/C curve tripping Characteristics). 40 A rating
Triple pole MCB (With B/C curve trippingCharacteristics). 50/63 A rating
Four pole MCB (With B/C curve tripping Characteristics). 50/63 A rating
Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 35 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Two pole 100/300mA sensitivity 40 A rating
Four pole 100/300 mA sensitivity. 63 A rating
P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter including making connection etc as reqd. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. IP -67 Surface/Wall mounted socket.. 16 A 3 pin(2P+E)
32 A 5 pin(3P+N+E)
63 A 5 pin(3P+N+E)
Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 160 (upto 160 A Incomer) / 250 Amp. copper bus bar, neutral bars with shrouds, earth bar , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal end box. 6 Way
Double door IP-43 & IK-09 with Provision of Incomer MCCB 250 A Rating with Metal end box 6 Way
4 pole MCCB With Thermal Magnetic release. 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
250 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
FAN & LIGHT FIXTURES
Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85 , air delivery minimun 220 CMM, speed minimum 330 RPM ( tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Without Remote
Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .. 300 mm sweep(900/1400 RPM)
Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. . OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .. Recessed Mounting.Minimum lumen output 1300 lm
Minimum lumen output 1600 lm
Minimum lumen output 1950 lm
Surface Mounting (with extruded alumn. Housing ) Minimum lumen output 1300 lm
Minimum lumen output 1950 lm
Minimum lumen output 2400 lm
Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy ≥100 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .. Minimum lumen output 1000 lm
Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Poles with Octagonal Cross Section.. 6 Mtr.
Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Single arm overhang
Double arm overhang
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
LED Street Light fixture with Minimum lumen output 5600 lm
Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . A) Excavation of Pit for Foundation Size upto required depth from Ground level B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.
Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr.
LT PANELS
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- (a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ). (d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. (f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Electrolytic grade Aluminium bus bar 6010 grade
Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS
Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Resin cast wound type CT C T Class 1, Ratio upto 150/5, Burden 5 VA
C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA
C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA
C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA
Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Red/yellow/Green colour
Blue / white Colour
Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms)
11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage 45 KV AC (rms)
Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs (temp class - 25 D) in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D) including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor (Bank)
Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phase sensing compensation power factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5 Cast Resin CT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
12 to 14 stage
Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 3 pole Power contactors with following AC 3 Rating.. 300 Amp
4 pole Power contactors with following AC 1 Rating.40 Amp
Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works, IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
upto 6 KVAR
SITC of Draw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, Instantaneous , earth fault (LSIG) with separate LED indication for each type of fault shall confirm to EMI/ EMC test , LCD/LED display, last 10 trip history, provision of ZSI, Communication, Power metering module, Thermal memory , trip free mechanisum , suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping feature , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electrical operation 10000 upto 2000 A rating and 5,000 for 2500 A to 4000 A. including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Microprocessor based release Draw out type ( Motorised charging type ) 4 Pole
800 A Rating ,50 kA
1000 A Rating , 50 kA
1250 A Rating ,50 kA
2000 A Rating ,50 kA
Supply and fixing of following accessories for Air circuit breaker (ACB) compatible with MAin ACB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Shunt Trip Release
Under voltage Release
Microswitch for Indication
Auxiliary Contact 4 NO + 4 NC
Breaker Control Switch (TNC)
Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Extended Rotary Handle
Spreaders for 160A, 4 Pole MCCB
Spreaders for 250A, 4 Pole MCCB
Spreaders for 400A, 4Pole MCCB
Spreaders for 630A, 4Pole MCCB
Spreaders for 800A, 4Pole MCCB
Phase Barriers up to 630A, 3/4Pole MCCB
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
4 pole MCCB With Thermal Magnetic release
125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
250 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
630 Amp ,50 kA, adjustable O/L & adjustable S/C setting,
800 Amp , 50 kA, adjustable O/L & adjustable S/C setting,
4 pole MCCB With Microprocessor based release with adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection.
630 Amp , 50 kA
LT CABLES
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
6.0 Sq. mm. 4 core
10.0 Sq. mm. 4 core
16.0 Sq. mm. 4 core
25.0 Sq. mm. 3.5 core
70.0 Sq. mm. 3.5 core
95.0 Sq. mm. 3.5 core
120.0 Sq. mm. 3.5 core
150.0 Sq. mm. 3.5 core
185.0 Sq. mm. 3.5 core
240.0 Sq. mm. 3.5 core
300.0 Sq. mm. 3.5 core
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 6.0 Sq. mm
10.0 Sq. mm 4 core
16.0 Sq. mm. 4 core
25.0 Sq. mm.4 core
CABLE TERMINATION
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
3.5 x 25.0 sq.mm
3.5 x 70.0 sq.mm
3.5 x 95.0 sq.mm
3.5 x 120.0 sq.mm
3.5 x 150.0 sq.mm
3.5 x 185.0 sq.mm
3.5 x 240.0 sq.mm
3.5 x 300.0 sq.mm
4 x 6.0 sq.mm
4 x 10.0 sq.mm
4 x 16.0 sq.mm
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty Copper lugs (IS 8337- 1976) duly crimped with crimping tool, PVC tape for following size of PVC insulated & PVC sheathed/ XLPE copper conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
3 x 6.0 sq.mm
4 x 6.0 sq.mm
4 x 10.0 sq.mm
4 x 16.0 sq.mm
4 x 25.0 sq.mm
Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100mm x 50mm x 1.6mm
150mm x 50mm x 1.6mm
300mm x 50mm x 1.6mm
450mm x 50mm x 2.0mm
Supply and fixing following size of Hot dipped Galvanized (275 GSM) floor raceways / Under floor trunking with/ without partion, including common cover, joint sleeve, cross over junction Box etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100 mm x 38 mm x 1.5 mm
150 mm x 38 mm x 1.5 mm
300 mm x 38 mm x 1.5 mm
LANDSCAPE
DB & MCB
Providing & Fixing of Recessed/surface mounting heavy duty Flexi / Row type Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted with reversible door (metal or Glazed) complete with 100 Amp. copper shorting link , neutral link, earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, ferrules detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Metal door IK-09 & IP-43 with Metal end box
3 Row 42 Module(14 module per row)
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Single pole MCB (With B/C curve tripping Characteristics)
6 A to 32 A rating
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 4 pole MCCB With Thermal Magnetic release
125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
2 x 2.5 sq. mm. + 1x1.5sqmm
TRANSFORMERS
Supply installation testing & Commissioning of Copper wound distribution Transformer of following rating and % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core design including standard accessories like conservator with prismatic oil level gauge , silica gel breather, Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box, LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ), temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test in OEM's own lab shall be witnessed by Department engineer Physically. Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
1250 KVA with % Impedance 5
HT SIDE EQUIPMENTS
SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR
Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch
Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
3 core 185.0 Sq.mm
Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 11 KV End Termination Kit Indoor type
3 core 120/150/185 Sq.mm
11 KV End Termination Kit Outdoor type. 3 core 120/150/185 Sq.mm
11 KV Straight Through Joint Kit .3 core 120/150/185 Sq.mm
Providing, Laying & Jointing R.C.C. class NP-2 Non-Pressure pipes (IS : 458mark) of approved make with collars, jointed with C.M. 1:2 or having Spigot and socket ends with flexible rubber rings joint including testing of joints etc. complete :
200 mm dia Internal
300mm dia Internal
SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm having provision for Following: (i)Provision for fixing Trivector / Import - Export Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections, etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
EARTHING
Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
25mm x 3mm copper strip
30mm x 5 mm copper strip
25mm x 3mm G.I. ( Hot Dipped ) Strip
25mm x 6mm G.I. ( Hot Dipped ) Strip
8 SWG copper Wire
8 SWG G.I. ( Hot Dipped ) Wire
WATER CLOSETS
P & F European type white glazed vitreous china 1st quality W.C. (IS : 2556 Mark) including cutting and making good the wall and floor
Wall Mounting
P & F water closet Seat Covers with brass hinges complete :
Solid PVC (IS 2548 marked) grade-I White. for EWC.
P & F C.P. lugs for toilet seat cover.
P & F White glazed Conversion Bend for W.C. from P trap to S trap. .
URINALS:
P & F lst quality WVC Urinal (IS:2556 mark) with 25mm dia G.I. waste pipe, dome waste couplings, concealed iron brackets or screws etc complete.
Flat Back (large) or half stall size 610x400x80mm.
P & F W.V.C. Urinal Partition Plate of approved standard make of size 630x315mm including making good the wall.
P & F Automatic Flushing Cistern of first quality (IS : 774 mark) of approved make fitting, siphon with copper tube, C.I. brackets complete including cutting and making good the wall. WVC (as per IS : 2556) 10 litres.
P & F Flush Pipe of approved make with complete fittings for high level flushing cistern:G.I. `B` class (Concealed) 32 mm.
WASH BASINS:
P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make, P.V.C Waste pipe with PVC nut 32 mm complete including cutting & making good the wall :
Size 610 mm x 510 mm
KITCHEN & LAB. SINKS:
ELECTRICAL ACCESSORIES.
P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 1.2 mm thick M. S. Sheet boxes 75mm x 75mm x 60mm
Mosaic fine polished kitchen sink size 450 x 450 x 200mm.
P & F Bevelled edge Mirror/mirror with teak wood lipping around of special glass of approved make as per direction of Engineer-in-charge complete with 6mm thick commercial ply base fixed to wooden screws & washers.
Size 600 x 450mm x 4 mm thick
WVC (1stquality, IS2556 Marked) of approved make. Recessed towel Hanger size 108 x 108mm. C.P. Brass Towel Ring revolving type
P & F Liquid Soap Container with brackets complete of approved make:C.P. brass
P & F Toilet Paper Holder with rod of approved quality/make:
C.P. brass heavy & Superior quality.
P & F Jet spray for water closet with C.P. Copper Tube flange of approved make.
Providing & fixing C.P.flange for 15mm dia taps.
P & F C.P. Health Faucet with 1Mtr. Long Tube & Hook of approved make and heavy as per direction of Enginner-in-Charge
P & F C.P. brass Urinal Spreader for Large Urinal of heavy duty of approved make as per direction of Enginner-in-Charge
Providing & Fixing Concealed cistern with Floor mounting frame and flush plate of superior quality and approved sample by Engineer-in-charge.
Providing & Fixing Premium quality Bottle trap internal portion 32mm, size 250mm long wall connection pipe & wall flange as per approved by Engineer in Charge.
P & F Bib Cock (IS : 8931 Mark), Superior quality of approved make:
C.P. Brass Long body, 15mm nominal bore weight not less than 690 gm
P & F Stop Cock (IS :8931 Mark), superior quality & of approved make:
C.P. Brass 1350gm. 25 mm nominal bore.
P & F Sink Cocks of superior quality & approved made :
C.P. Sink cock swinging spout 15mm.
P & F Inlet Connection (Angle Valves) Superior quality, of approved make, for Wash basin, Gyser etc.
C.P. Inlet connection 15mm.Brass (IS : 8931 marked)
P & F 15 mm. Dia Connection Pipe of approved quality/make :
P & F Flush Cock / Flush Valve (IS : 9758 Mark) for WC of approved quality make :
(-do-) concealed 25mm nominal bore.
P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make :
(-do-) 25mm nominal bore.
(-do-) 32mm nominal bore.
(-do-) 40mm nominal bore.
(-do-) 50mm nominal bore.
(-do-) 65mm nominal bore.
P & F Gun-metal Non-return Valve or Check Valve (IS : 778 Make) of approved make, superior quality:
40mm nominal bore.
Horizontal
Vertical
50mm nominal bore.
Horizontal
Vertical
P & F foot valve of superior quality and approved make with fittings :
Brass 25 mm.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1 metre spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. (Internal work Exposed on wall)
20mm nominal size
25 mm nominal size
32mm nominal size
40 mm nominal size
50 mm nominal size
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. (Concealed work including cutting chases and making good the walls etc.,)
20mm nominal size
25 mm nominal size
Providing & fixing C.I. Saddle pieces 100mm dia with nut & bolt & washer & Rubber Gasket complete as per direction of engineer in charge
Providing and Fixing Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes Type B for sciland waste discharge system (IS:13592 : 1992 Marked) of approved quality /make
75 mm dia
110 mm dia
Providing and Fixing Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes fittings type B for sciland waste discharge system (IS:13592 : 1992 Marked) of approved quality /make
Coupler
75mm dia
110mm dia
Repair Coupler
75mm dia
110mm dia
Single Push Fit Coupler
75mm dia
110mm dia
Bend 87.5 Dg.
75mm dia
110mm dia
Bend 45 Dg.
75mm dia
110mm dia
Door Bend 87.5 Dg.
75mm dia
110mm dia
Single 'Y'
75mm dia
110mm dia
Single 'Y' with Door
75mm dia
110mm dia
Double 'Y'
75mm dia
110mm dia
Double 'Y' with Door
75mm dia
110mm dia
Socket Plug
75mm dia
110mm dia
Pipe Clip
75mm dia
110mm dia
Double tee with Door
75mm dia
110mm dia
W.C. Connector
110mm dia
W.C. Connector (Bend) with ring
110mm dia
Single Tee
75mm dia
110mm dia
Single Tee with Door
75mm dia
110mm dia
Double Tee (4 Ways)
75mm dia
110mm dia
Multi floor trap
110mm dia
Offset
110mm dia
Extra Square Jali
110mm dia
Extra Round Jali
110mm dia
Extra 4 SWR Ring
75mm dia
110mm dia
Gully Trap
110mm dia
Nahni Trap with Jali 4”
110mm dia
Nahni Trap without Jali 4”
110mm dia
Nahni Trap with Jali 3”
75 mm dia
Nahni Trap without Jali 3”
75 mm dia
Vent Cowel
Vent Cowel
110mm dia
Providing, Laying & Jointing R.C.C. class NP-2 Non-Pressure pipes (IS : 458mark) of approved make with collars, jointed with C.M. 1:2 or having Spigot and socket ends with flexible rubber rings joint including testing of joints etc. complete :
150 mm dia Internal
200 mm dia Internal
250 mm dia Internal
300mm dia Internal
Construction of manhole in all type of soil inner size 90 X 60 Cm. 300 mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20 mm thick inside plaster in CM 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring, making channels, 80mm thick stone slab covering with 40mm thick M-15 grade C.C. flooring,ferro Cement cover with frame of 450mm dia, earthwork etc. complete as per design including disposal of surplus earth within 50 mtr. lead.
Depth up to 0.5 M
Add extra over item 3.19.1 for every additional 0.10m depth above 0.5 m depth.
Construction of Man hole, in all types of soil, inner size 1.5 x 1.2 M, with 450mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20mm thick inside plaster in CM 1:6, finished with floating neat cement, 50 mm thick M-15 grade C.C. flooring making channels, 80 mm thick stone slab covering with 40 mm thick M-15 grade C.C. flooring, Ferro Cement cover with frame of 450mm dia, earthwork etc. complete including disposal of surplus earth within 50 mtr. lead as per design :
Depth up to 1.5 M
Inside size 450 x 450mm depth upto 0.5 M Cement cover with frame
Inside size 600 x 450mm depth upto 0.5 M to 1.0 M Cement cover with frame.
P & F M.S. Foot Rests in with C.M.,1:3, standard design in 20mm square M.S. bar 50 mm embedded in wall & 10 cms. projected out complete
Supplying and fixing Ferro- cement cover with C.I. frame for chambers & man holes of size.
Rectangular shape 600 x 450 mm, to withstand 3 MT center point load & minimum unfractured load of 1 MT. (Light duty)
Supplying & Fixing R.C.C. Manholes covers with frame of approved make (Light duty).
Size 450 X 450mm
P & F Square-mouth gully trap `A` grade (IS 651-1992 :marked) of approved make complete with C.I. grating, frame & Cover masonary chamber in C.M. 1:6, 100mm thick C.C. 1:5:10 base concrete, 40mm thick C.C.M-15 grade coping, 12mm thick cement plaster in CM 1:3 complete as per approved design & type
Trap size 150 X 100mm, ferrow cement cover with frame, Internal Chamber size 300 X 300mm
Trap size 225 X 150 mm, ferrow cement cover with frame Internal Chamber size 450 X 450mm.
Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.
Fixing water meter (IS: 779 mark) and stop cock in G.I. pipe line including making chamber of approved size excluding cost of water meter & stop cock.
Making khurras 450 x 450mm with average minimum thickness 50mm cement concrete 1 : 2:4 over P.V.C. Sheet 1 Mtr. x 1 Mtr. x 40micron finished with 12mm cement plaster 1 : 3 and one coat of neat cement, rounding edges and making and finishing the out let complete
Fire Fighting
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H. (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal. (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head. (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM. (H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
1620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage, 2900 RPM
Supplying, Installation, Testing & Commissioning of Diesel Engine Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.
(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal
(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
(D) Heat Exchanger cooled Diesel Engine as per NFPA 20 developing suitable BHP for the below mentioned discharge at 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank.
(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives.
(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
(H) Pump to be placed on Suitable size Existing Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
1620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage, 1800 / 2300 RPM
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Jockey pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E,F and G
(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
(D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.
(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
(G)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
180 LPM suitable for 70 Mtr Single Stage
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Terrace pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.
(A) Horizontal End suction Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
(D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.
(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
(G) Suitable size Reinforced cement concreat (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra )
(H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to protect it from weather All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
900 LPM with 35 mtr head
Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve confirming to IS - 14845 : 2000 with Double Flange isolating valve (pressure rating PN 1.6) complete with 1 no. Matching Flanges (Minimum 10 mm thick), nuts, bolts, washers, gaskets etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Static pressure rating up to 250 PSI in cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
150 mm Dia.
SITC of UL listed / FM Approved Brass Test and drain valve assembly for sprinkler system comprising of 3-position ( off, test and Drain ) ball valves with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI and Inbuilt sight glass etc. as required of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
25 mm Dia.
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of required shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C' class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supports including cutting, welding etc & forged steel fittings like elbows, tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100 mm dia
150 mm dia
Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100 mm dia
150 mm dia
Supplying and Fixing of PN 16 Flanged sluice valve with non rising spindle, bronze /gun metal seat confirming to IS:14846 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
150 mm dia
Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100 mm dia
150 mm dia
Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
50 mm dia
100 mm dia
150 mm dia
200 mm dia Gear Operated
Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
25 mm dia.
SITC of installation control valve of cast iron body and brass/bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continous alarm when the wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Single Headed with 75 mm Dia. Flanged Inlet
Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A) 63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304 male and female couplings (IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.
Supplying & fixing SS-304 Short Branch Pipe conforming to IS: 903:93 fitted with 20mm (nominal internal diameter) bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required. (A) Thermoplastic / Rubber Hose (B)20 mm dia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall. (D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1 through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969 and Bursting pressure 42 Kg/sqcm
Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valve complete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Ways. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection) for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply and Fixing of Cast iron body one side Flanged and other side strainer ball type foot valve with Reinforced rubber Nitrile rubber coated Ball including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
150 mm Dia.
Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
100 mm Dia. x 150 mm Oal
150 mm Dia. x 150 mm Oal
Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red color externally and white internally with 6 mm thick glazed doors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and fixing of Fire / Electrical Shaft Door made from powder coated (50 Micron) aluminium partialy glazed with 6 mm thick glass and Partialy / Fully Louvered with Outer frame of Aluminium Section of Size 100 mm x 45 mm x 1.5 mm and Shutter's Top, Middle & side Section of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mm Complete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler heads with Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Pendant/ Upright type
Supply & Fixing of Fire Man's Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Capacity 3.0 Kg.
Capacity 4.5 Kg.
Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Double mounted handle as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & Fixing of Ceiling mounted Dry Powder Agent (as per IS 4308:2019), Modular stored pressure type ABC Fire Extinguisher , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Fixed Bulb with Temerature 68 deg C, QR code for Product Traceability including Fixing on Ceiling with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
5 Kg Capacity
10 Kg Capacity
Supplying and Fixing of Galvanized Mild Steel fire bucket Confirming to IS: 2546 : 1974 with one coat of primer and two coat of enamel paint of approved shade on Angle Iron ( 50 x 50 x 5 mm) Stand of Size 800 x 1240 x 400 mm with MS 22 SWG Galvanized Canopy, 4 Hooks for Buckets including associated civil works etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and fixing signages as per required content printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating with suitable colour combination (Glow in dark) with high intensity properties for indoor surface glow visibility not less than 6 hrs. in total darkness and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Single sided signage board
Double sided signage board
Providing and fixing of Aluminium housing body self contained Rechargeable LED Emergency Light with required content and Size Approx. 300 mm x 180 mm, confirming to IS:9583 :1981with Ni-Mh / Ni - Cd Battery, 3 Hrs Back Up, Constant Current Charger, Input Voltage 230 V , 50 Hz including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Single sided signage
Double sided signage
CCTV SYSTEM, NETWORKING & EPABX
Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtr.s channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . (For CCTV & Telephone)
Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with HDPE, Category 6A/Class Ea, U/FTP (Unscreened/Foiled Twisted Pair), 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 C.2 & ISO/IEC 11801 2nd Ed, The copper conductors should be balanced twisted in pairs, Unscreened and Aluminum Foil Sheilding of Individual pairs protected by a Low Smoke Zero Halogen (LSZH)(IEC 60332-1) Jacket. Certified performance in a 4-connector configuration upto 100 Mtr.s channel requirements & transmission frequencies up to 500 Mhz. Should meet IEEE 802.3af & IEEE 802.3at for POE applications. Cable Should support Ethernet 10GBASE-T according to the standards. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Cat 6, Un-sheilded Information Outlet
Cat 6A, Sheilded Information Outlet
Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture , material should be PC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Dual Aperture
Supply, Installation, Testing and Comissioning of Rack mounted 19" 1U, Cat6 24 Port loaded, 1.5-1.6 MM CRS chasis, powder coated, sheet steel, made of plastic (ABS), Modular Patch Panels with Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Modular Patch Panel Loaded with Cat -6 I/O
Modular Patch Panel Loaded with Cat -6A I/O
Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Cat 6A, U/FTP (Unscreened/Foiled Twisted Pair) Patch Cord
Supply, Drawing and Testing, of stranded Multi mode (50/125 µm) glass optic fiber cable, as per latest ammendments of TIA/EIA 568/ISO/IEC 11801:2011/ IEC 60794-1-2 E1, E3,E11, F1/ EN 50173-1/ EN 187 000/ IEC 60974-2, 2-20, 2-21/ ITU G.652D, construction of LSZH outer sheath cable, cable should be used for LAN and WAN back bones, . With its LSZH sheathing these cables should be ideal for indoor/outdoor installations in existing MS/PVC /HDPE Conduits/ slotted channels with ferruling at both ends for identification complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
6 fiber
Supply & Installation of IP-20 & IK-08 , UL Listed Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
15 U Rack with Width 600 mm & Depth 400 mm + 100 mm
Supply & Installation of IP-20 & IK-08 , UL Listed Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet,Vertical Mounting Rail 1.6 MM with 'U'Marking, front sturdy sheet steel frame folded from one piece and welded with 5mm toughened glass door, with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, Set of 75 mm height 4 castors, 2 of which have brakes, Accessories like: 5 Nos of 19" 1U Horizontal Cable manager, 2 Nos of vertical cable managers, 1 no. Keyboard Tray, 4 Nos of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 2 No of 19" 1U, mountable socket strips with 6 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
27 U Rack with Width 600 mm & Depth 800 mm
EPBAX BSR
P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder painted,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
10 Pairs
20 Pairs
50 Pairs
Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Rate of Rise Heat Detectors (Thermal Detectors):GRADE-I Analouge Addressable type Heat Detectors with solid state design with sensing element combination of fixed type and rate of rise of temperature mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangement etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of Response Indicator for indicating the activation of the Remotely located Detector for Addressable type Detectors Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable control (input/output) modules/ Relay Module for shutting down lifts, Hooters, AHU's, Acknoledgement of Sprinkler system with potential free contact monitoring Etc. as Required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
2 - Loop Panel
Add Extra for per Loop expansion beyond Two Loop
SITC of UL 10th edition / EN54 / VDS certified Active Repeater Panel for Fire Alarm System with inbuilt networking port (both RS485 & Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming. The Repeater Panel shall allow users to acknowledge, reset,silence, program, view hisory events.etc (All functions similar to main panel)The user interface of the repeater panel shall be same as the Main Controller with menu driven user interface with smart search.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified 6 ZONE Digital Voice Command Center with FACP, it shall contain all equipment required for all audio control, signaling and supervisory functions. This shall include speaker zone indication and control, digital voice units, microphone etc. The Digital Voice Command Center shall have digital voice call station suitable for 6 zone, digital voice controller & router suitable for 6 zone, 4 nos 240 watt & 1no 480 watt amplifier & digital amplifier capable for 1440 watt load etc.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of 2 way communication Fire Fighter's Telephone Jack.Complete as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of 2 way communication Fire Fighter's Telephone Handset to make a call to the Main FACP from Telephone Jack Location Complete as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
2 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color
2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color
S&F following sizes (dia.) of ISI marked ( IS:9537 P - II ) rigid steel conduit with wall thickness according to IS Specified along with ISI marked (IS:14768 P-II 2003) accessories in recessed using saddles, clamps, fasteners, pvc bushes, check nuts, as required including cutting jhiris in the wall and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
SITC 6 watt Speaker mounted in M S sheet box with perforated front mesh for PA and Emergency System. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Market rate Work
Civil Works
Providing and fixing Automatic Glass Door in all respect as per EI.
Providing and fixing Iron Automatic Boom Barriers With Rf Id, For Parking in all respect as per EI.
WIRING
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.Above 10 mtr.
Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Above 10 mtr.
FAN & LIGHT FIXTURES
MIRROR LIGHT
CHANDELIER LIGHT
COVE LIGHT
COB LASER LIGHT
Supply, Installation, testing and commissioning of Day light Photo Control Sensor Automatic Light Photoswitch 10A, 220V, along withy necessary fixing arrangement complete as per requirement
PANEL EQUIPMENT
P & F of Automatic Transfer Switch (ATS) confirming to IEC60947-6-1, Utilization cateogory AC-33B in Existing panel for automatic on load transfer between two source power supply of 415V through Solenoid/Motorised mechanism and integrated with three positions realize fast transfer within 100 ms. ATS shall have three postions (S1-OFF-S2) , Manual / Auto Override feature, The two sources can be isolated in the off position with a padlock. capability to expand with RS 485 communication module, which can ensure real-time transmission of communication data. ATS shall have automatic generator start & stop control function; Auxillary contacts to indicate mechanical positions. Minimum Electrical operations 6000, of following Current ratings, including making connections etc.. 2000 Amps
LANDSCAPE
EXTERNAL, LANDSCAPE, FAÇADE & WATER FEATURE LIGHTING(NON-BSR ). INSTALLATION OF LIGHTING FIXTURES. Rate for installation of fixtures shall also include the following: All component that may be required to make the installation complete in all respects. a. Suitable length of connecting wires. b. Connecting wires to the point through connection block. c. Bonding to earth wires. D. Drilling holes in supports wherever required. E. Fixing clamps, GI bolts and nuts / brass screws, saddles, rawl bolts and other fixing accessories as required. F. Painting with enamel paint of clamps and other fixing accessories. G. Suitable size junction boxes with connector block for loop in loop out where ever applicable. H.Testing of all fixture and after installation. I. Receiving, installation, testing and commissioning of the following lighting fixtures :
UNDER WATER LIGHT
DOWNLIGHTER
SPIKE BASE LIGHT(7W)
WALL WASHER
BOLLARDS LIGHT
UPRIGHT LIGHT
TREE UPLIGHTER(3.5W)
DG SET(NON BSR)
Supply and transportation at site of 3 phase 415 volts 50 cycle per second 1500 RPM Heat Exchanger cooled Diesel Generator Sets of rating as below. With acoustic enclosure sound level below 75db as per CPCB norms. The engine shall include flywheel to suit flexible coupling with guard, air cleaner, blower fan, fuel pump, variable speed electronic governor, fuel filter, lub oil filter & pump, primary water circulating pump, static battery charger, 24 volt batteries of compatible capacity with battery stand and instrument panel comprising of switch with key etc. as required. The alternator shall be self excited (PMG), self regulated and continuously rated as below suitable for 3 phase 415 volts 50 cycles, 4 wire system and shall be provided with static excitation unit, Alternator insulation shall be class 'H' suitable to withstand tropical conditions and shall generally comply with BS 5000 and IS 4722. The overload capacity shall be not be less than 110% of rated capacity for 1 hour in every 12 hours The DG set shall be mounted on a fabricated rigid common base frame with GERB make resilient anti-vibration mountings to provide 99% vibration isolation. The DG set shall include all accessories, fittings, instruments & standard tool kit complete as per specifications and as required including control cabling. The cost shall include providing adopter box for Bus-duct/Cable termination as required. (CPCB4+ compliance)..500 KVA at 0.8 pf 415V 50Hz 3-ǿ
750 KVA at 0.8 pf 415V 50Hz 3-ǿ
LIGHTNING PROTECTION (NON-BSR)
Rates shall also include the following : All fixing accessories such as brass saddles, brass screws rawl plugs etc. Jointing by rivetting and brazing after rivetting in case of copper and by welding / bolting in case of GI. Cutting chases, holes and making good the same wherever required.. Effecting adequate and proper interconnections. Use of copper thimbles. Lightning protection system shall comply to IEC/ IS: 2309 - 1989. All earthing pits shall be interconnected.
LIGHTNING PROTECTION: SUPPLY, INSTALLATION, TESTING AND COMISSIONING OF ESE LIGHTENING PROTECTION SYSTEM. Lightning Protection Airterminal
Mounting Mast (Pole) .3 m high GI pipe fabrication support structure providing with suitable base plate, should have provision for Guy wire clamping system, termination arrangement for the Down-Conductor
Lightning Strike Counter .Lightning Flash counter working electro mechanically without any power supply. Equipment should count lightning strokes of 0.4KA to 220 KA.
Down Conductor & Accessories. Supply and fixing of down conductor with complete fixing accessories and termination (1 x 70 Sq. mm copper with high voltage isolator supports).
UPS & INVERTER SYSTEM(NON-BSR)
Rate for supply shall also include the following : Approved rating single core copper conductor cable connecting to batteries. All equipment shall be housed in individual cabinets. Battery backup must be given for full resistive load. Battery should be sealed maintenance free type. Real time Web based UPS monitoring system with software on remote computer and by SMS/email shall be provided BMS Interface required with each UPS. All accessories required for paralleling of UPS to be included as per SLD. UPS & INVERTER SYSTEM
20 KVA 3 phase input, 3 phase output on line UPS with minimum 30 minutes backup and as per technical specifation with all acessories each complete with battery rack .
Supply, Installation, testing and commissioning of 5 KVA inverter with minimum 90 minutes battery back-up, Complete with all accessories & as per specifications.
Plumbing
SITC of Dia 50mm Smart Energy Meter, Class-1 accuracy, single/three phase, GSM/RF enabled, suitable for 230/415V, 50Hz AC supply, complete with meter box, accessories, wiring, testing & commissioning, approved make, complete as per specifications.
Providing & Fixing of back flow preventer
Providing & Fixing Garden Yard Hydrent
Providing and Fixing GI Sleeves with Flange for Under Ground and OH Water Tank 50 MM dia GI Sleeve with Flange Length up to .7 M
65 MM dia GI Sleeve with Flange Length up to .7 M
80 MM dia GI Sleeve with Flange Length up to .7 M
200 MM dia GI Sleeve with Flange Length up to .7 M
Domestic and Flushing Water Transfer Pumps for OH Tank Filling
Supplying, testing and commissioning of Water transfer pumps Vertical Inline Multistage Centrifugal pump (direct Coupled), Each Pump shall have TEFC 2900 RPM three phase electric motor (Min. Efficiency class of pump must be IE3). The Pump shall have cast iron (CED Coated) base and head, SS 304 Impeller, SS 304 Casing, SS 316 Saft. The Pump shall be provided with cartridge type Mechanical seal. The Pump shall be suitable for auto/manual operation. For Treated Water Supply From UG Treated Water Tank To OH Treated Water Tank
For Treated Water Supply From UG Treated Water Tank To OH Treated Water Tank
Discharge- 5 M3/H (83 LPM) @ 45 Mtr Head (1W+1S) with Cascading operation panel For Flushing Water Supply From STP to OH Flushing Water Tank Discharge- 5 M3/H (83 LPM) @ 45 Mtr Head (1W+1S) with Cascading operation panel APPROVED MAKE: XYLEM/GRUNDFOS
Dewatering Pumps for Basement, Pump Room
Supply, testing and commissioning of electrically driven submersible de watering pumps (one working and one standby ) for Pumping from water drain sump pump is cast iron with vertical discharge port and integrated submersible 3 Phase totally enclosed motor. The pumps shall have Ductile case iron impeller and all CI Part Should be (CED Coated). For Ensuring safety pumps equipped with double mechanical seal. The pumps will be provided with panel (cascading operation) for auto operation in low level and high level flow conditions. For Basement sump (Dewatering Pump) with Soft Solid handling 10 mm or more Discharge- 10 M3/H (166 LPM) @ 15 Mtr Head (1W+1S) with Cascading operation panel
For Fire Pump room (Dewatering Pump) with Soft Solid handling 10 mm or more Discharge- 10 M3/H (166 LPM) @ 15 Mtr Head (1W+1S) with Cascading operation panel . APPROVED MAKE: XYLEM/GRUNDFOS
WATER TREATMENT EQUIPMENTS :
SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be of carbon + S.S.The stator body of single phase pump shall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. Approved Make - Kirloskar , Xylem Formally Known ITT & Grundfos Filter Feed Pump (1 Working + 1 Standby) Capacity 5 LPH and Head 15 m
Providing, fixing, testing and commissioning of vertical self supporting dual media filter fabricated from MS sheet as per IS : 2825, pressure gauges at inlet & outlet, sample cock, air vent valve with piping, GI class 'C' face piping distribution pipe with diffuser on top, CI butterfly valves Multiport valve and all accessories, with initial charge of filter media for dual media filter, painting inside with food grade epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint complete. Dual Media Filter for Domestic Water Supply : Filtration rate - 5000 LPH (5 m3/hr) Filter dia (approx.) - 600 mm Working pressure - 3.5 Kg/Sq.cm Deasign pressure - 5.0 Kg/Sq.cm
Providing, fixing, testing & commissioning of metering pump type chemical doser with 100 lits.HDPE/ FRP solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects for treated water tank. Chlorination of Domestic Water :
Providing , fixing, testing and commissioning of water softener fabricated from MS plate as per IS : 2825 (shell & thick dished ends) complete with initial charge of resins, GI class 'C' face piping, CI butterfly valves, pressure gauge, hydraulic brine injector, accessories, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, including suitable PVC/HDPE brine tank of 2 regeneration capacity complete with resins of approved quality and make. Hardness Inlet - As per actual Water test report (as of now considered up to 400PPM) Outlet - Commercial zero (<30 PPM) Capacity - 5000 LPH (5 m3/hour) Operating pressure - 3.5 kg/Sq.cm Test pressure - 5.0 Kg/Sq.cm Suggested Resin Quantity - 150Kg Suggested dia - 600 mm
SITC of Hot Water Circulation pump including all standard fittings fully automatic ON / OFF system, 2900 RPM with stainless steel casing, & impellor suitable for following capacity complete in all respect. Appropriate type test certificate / OEM shall have submit NABL / CPRI / ERDA accredited lab type test certificate before execution. All as per pre approved by Engineer in charge. 1.0 HP,3-ph, 12-16 Mtr Head, 48 LPM (3m3/h) (1W+ 1S) HWR
SITC of Pressure boosting pump with 50 Ltr. MS Tank, pressure switch, pressure gauge, and all standard fittings fully automatic ON / OFF system, 2900 RPM with stainless steel casing, & impellor suitable for following capacity complete in all respect. Appropriate type test certificate / OEM shall have submit NABL / CPRI / ERDA accredited lab type test certificate before execution. All as per pre approved by Engineer in charge. 1-ph, 25-30 Mtr Head, 48 LPM (3m3/h) (1W+ 1S) CWS+HWS
Supply, installation, testing and commissioning of Air to Water heating Heat pump 10 HP including the necessary accessories and safeties and capable of delivering hot water at 60 Deg.C. Operating Ambient Temp.: 0 deg. C to 43 deg. CCompressor should be scroll type and ZW series compressor is using for heating Refrigerant Gas: R407C - Heat Exchanger type should be Shell and Tube type All type of System protection/End User/ Component Protection should be available in heat pump Heat pump Heating capacity : 36 KW Heat pump Power Input : 380V/50Hz/3Ph. COP: 3.8.Hot water output capacity : 1000 LPH
FABRICATED ITEMS: Supply, installation, testing and commissioning, of HDGI fabricated floor supported Horizontal type 2000 litres storage capacity Hot water Storage tank. The tank shall be suitable for a minimum working/ Test pressure of 5 kg/sq.cm /7 kg/sq.cm .The tank shall be fabricated out of 6 mm thick MS plate and hemispherical end shall be 8 mm thick . The tank shall be insulated with 100 mm thick Rock wool or rock wool (density not less than 48 kg/cum.) covered with chicken wire mesh including 246 gauge aluminium cladding.
Supplying, storing, and fixing water cooler SS body, capacity 80 L/hr with tap point on wall/counter, complete with all necessary plumbing, drainage, electrical connections, and accessories as per manufacturer’s specs. Make: Bluestar.
SITC Charges (Supply Installation Testing Commissioning)
CCTV SYSTEM, NETWORKING & EPABX
Supply, Installation, Testing & Commissioning of 4 MP IR Fixed Dome Network Camera -1/2.7″ Progressive Scan CMOS, 2592 × 1944 at 25fps, 2.8 mm Fixed lens, 0.003 Lux at F1.4, 0 Lux with IR on, ICR, ONVIF (PROFILE S, PROFILE G, PROFILE T), support H.265, H.264, MJPEG, 120db WDR, BLC, HLC, 3D Digital Noise Reduction, Three individually configurable stream, 12 VDC & PoE, IR range: 40m, Support on-board storage up to 256 GB (SD card not included), Alarm : 1 inputs & 1 outputs, Audio: 1 input & 1 output, Built-in Microphone, , IP67, IK 10, Edge Analytics- Line crossing detection, Intrusion detection, Motion detection, Scene change detection, Face capture, Region entrance detection, Region exiting detection, Video tampering, Audio exception detection, Focus on human and vehicle targets classification, UL, FCC, CE certified.
Supply, Installation, Testing & Commissioning of 4 MP Varifocal Bullet Network Camera -1/2.7'' Progressive Scan CMOS, 2592 × 1944 at 25fps, 2.7 to 13.5 mm Varifocal Auto iris lens, 0.003 Lux at F1.4, 0 Lux with IR on, ICR, ONVIF (PROFILE S, PROFILE G, PROFILE T), support H.265, H.264, MJPEG, 120db WDR, BLC, HLC, 3D Digital Noise Reduction, Three individually configurable stream, 12 VDC & PoE, IR range: 60m, Support on-board storage up to 256 GB (SD card not included), Alarm : 2 inputs & 2 outputs, Audio: 1 input & 1 output, IP67, IK10, Edge Analytics- Line crossing detection, intrusion detection, Scene change detection, Motion detection, Face capture, audio exception detection, Video tampering, Region entrance detection, Region exiting detection, False alarm reduction through human and vehicle target classification, UL, FCC, CE certified.
64ch Network Video Recorder- Connect Up to 64 IP Cameras, Up to 12 Megapixels Resolution, HDMI1/VGA1 and HDMI2/VGA2 outputs provided, Atleast one HDMI output of 4K resolution, atleast one VGA output with output upto 1920 × 1080, Support H.265, H.264, MJPEG, Supports N+1 hot spare system, Supports RAID0, RAID1, RAID5, RAID6 and RAID10, Supports HDD hot swap, Supports Dual Power-Redundant, Incoming Bandwidth 320 Mbps, 8 SATA Hard Disks, ANR Technology, 8 SATA interfaces for 8 HDDs and capacity of each HDD upto 10TB, RS-232; RS-485, Front panel: 2 × USB 2.0; Rear panel: 1 × USB 3.0, Alarm I/O 16/4, 2 RJ-45 10 /100/1000 Mbps self-adaptive Ethernet interface, Multiple network monitoring: Web viewer, CE, FCC, UL certified.
32ch Network Video Recorder- Connect Up to 32 IP Cameras, Up to 12 Megapixels Resolution, HDMI1/VGA1 and HDMI2/VGA2 outputs provided, Atleast one HDMI output of 4K resolution, atleast one VGA output with output upto 1920 × 1080, Support H.265, H.264, MJPEG, Supports N+1 hot spare system, Supports RAID0, RAID1, RAID5, RAID6 and RAID10, Supports HDD hot swap, Supports Dual Power-Redundant, Incoming Bandwidth 320 Mbps, 8 SATA Hard Disks, ANR Technology, 4 SATA interfaces for 4 HDDs and capacity of each HDD upto 10TB, RS-232; RS-485, Front panel: 2 × USB 2.0; Rear panel: 1 × USB 3.0, Alarm I/O 16/4, 2 RJ-45 10 /100/1000 Mbps self-adaptive Ethernet interface, Multiple network monitoring: Web viewer, CE, FCC, UL certified.
8 TB Surveillance Hard Disk
55" 1080P Display, HDMI/VGA input, view angle:178°/178°, 300cd/㎡, plastic casing, VESA, base bracket included, 7*24h
CORE Switch : 12X10G, 12XSFP+ Managed Switch with 5 years support pack from OEM
SFP Modules 1Gig single mode
24-Port Gigabit Ethernet PoE+ Smart Switch with 2 SFP Ports (190W)/ Cloud Managed with 5 years support pack from OEM
16-Port Gigabit Ethernet PoE+ Smart Switch with 2 SFP Ports (190W), Cloud Managed, including 5 years OEM support pack, complete as per specifications and approved make.
24-Port Gigabit Ethernet Smart Switch with 2 Dedicated SFP Ports with 5 years support pack from OEM
16-Port Gigabit Ethernet Smart Switch with 2 Dedicated SFP Ports with 5 years support pack from OEM
AX5400 Dual-Band PoE Multi-Gig Cloud Managed WiFi 6 Access Point with 5 year Cloud Lic and Cloud Controller
Firewall - Fortigate/ SOFOS - 250 users
EPABX
96 analogue extensions, 08 PSTN Trunk Port, 30 Channel SIP PRI, 08 Digital Port, 15 IP User License, 5 IP Softphone/mobile user license, 08 VoIP Channel License along with 8 port Voice Mail expandable upto minimum 224 TDM ports and minimum 500 SIP/IP users without any add-on CPU or chassis/hardware platform.
Analog Phone
IP Phone
Speaker Cable
Supplying, laying, testing, rectification and commissioning of 2 Core x 1.5 sq. mm. Speaker Cu cable in 25 MM Dia. of Medium duty(FRLS) PVC Conduit concealed/surface mounted including cutting/filling, chases, PVC conduits including making connections to Information outlets and patch panels with ferruling at both ends for identification with necessary tools for punching ,stripping crimping and testing as required
SEWAGE TREATMENT PLANT (MBBR TECHNOLOGY ):
PREAMBLE TO BOQ
Sewage Treatment Plant Based on attached Growth Process:
Designing, Supervising, Supplying , Installation, Testing & Commissioning of STP (FAB/FMR/MBBR Technology) for 30 KLD shall be based on attached growth concept (with air diffuser membrane system) (FAB / FMR/ MBBR with 2 reactors in series with sewage handling capacity of 30 KLD/ day for STP .The raw sewage comprises of sewage from the entire housing for which a common STP has to be designed. The collection sump with bar screen shall be a part of the STP. The STP shall be designed as water retaining structures in RCC structure design.All the equipments, pipings, pumps, air blowers and electricals are to be housed in a plant room underground/overground including MS puddle flange/insert need to be hot dipped galvanized, inlet, outlet, overflow, vents,MS covers, drain channel with MS gratings etc.
The raw sewage comprises of domestic sewage from toilet, kitchen, etc. for which a common STP has to be designed.The STP shall be designed based on the following parameters :
Raw Sewage Inlet Parameter :
Daily Flow Rate --- 30 KLD
BOD5 --- 200 -350 ppm
COD --- 300 - 600 ppm
TSS --- 200 - 350 ppm
Oil & Grease --- upto 60 mg/lt
Treated Sewage Outlet Parameter :
BOD5 --- less than 10 ppm
COD --- less than 50 ppm
SS --- less than 10 ppm.
Oil & Grease --- less than 5 mg/lt.
The STP shall consist of following units but not limited to these units as may be required by the manufacturer’s design :
Bar Screen cum Grit chamber for the incoming sewerage from housing complex 1 no RCC Chamber, manually cleaned SS bar screen, bar screen having provision for lifting,etc.
Oil & Grease Trap to remove O&G with baffles
Equalisation Tank for collection of total sewage housing the pumps. Provision for aeration shall be kept to avoid any smell problems.
Flow from Equialization/Anoxic tank / Moving bed bioreactors with PVC media including air diffusers at the bottom, sewage distribution header & baffle wall towards the outlet of the reactor.
Flow from Biological reactor to Tube Settler tank suitable for 30M3 /Day fitted with PVC plates or tube deck media in series at 60 deg. angle increasing the settling area and removal of the particles effectively in a smaller plan area (cost of MBBR & tube -deck media shall be qoute under item in the BOQ.
Chlorine contact cum filter feed tank for chlorine mixing and desired minimum volume for STP.
PVC hypochlorite solution tank ( cap. 100 ltrs.) with dosing pump of suitable capacity adjustable metering type.
Suitable size of treated water tank (make-up water, flushing & irrigation) with online chlorine dosing system to be provided to disinfection the treated sewage water.
Ultrafiltration system for Re-cycle water to be used for flushing system in the housing.
Electrical works including electrical panel, cabling ,cable tray etc,
Note 1: All the Civil Works including equipment foundation shall be in the scope of the Owners.The STP contractor shall co-ordinate, supervise and get all the inserts installed. All supply of MS Puddle Flange/ Inserts plates need to be hot dipped galvanized shall be in the scope of the sewerage treatment plant contractor. The items which are not covered below has to be taken under this head only to complete the entire system.
Supply, installation, testing & commissioning of 2 Nos Stainless Steel Perforated, Corrugated Type Coarse Bar Screen with 10 mm pore size respectively and suitable lifting arrangement ( Each size 700 mm x 900 mm approx.)
Providing and fixing non-clog 40mm solid handling of fully submersible pumps in equalization tanks. The pump shall be complete in SS/CI construction including lifting arrangement for the pumps including piping, valves on the discharge of pumps.
Raw Sewage Pump:
Submersible pumps -5 CUM/hr @ 10-12 mtrs head
Plant Room Sump Pump:
Submersible pumps -10 CUM/hr @ 8-10 mtrs head
Supply, istallation, testing and commissioning of slow speed agitator complete with gear box for Anoxic tank complete with supporting system of agitator in the Anoxic tank. Minimum 1 nos agitator should be consider in anoxic tank of suitable capacity.
Agitatour for Anoxic Tank
Supply, Installing, testing and commissining of MBBR floating PVC Media with specific gravity = 0.93-0.95, surface area = 400sq.m. / cumtr. The vendor hsould supply the media for both Bio Reactors and also consider the media quantity so that system should function proper in STP.
Supply, installing, testing and commmissoning of PVC plate or tube deck media in series at 60 deg angle to be installed tube settler tank alongwith retainer plates, the capacities, length, width and depth of the media shall be consider for proper funtioning of STP. the vendor should include the sludge removal arrangement by means of sludge removal pump the capacity of pump shall be consider by vendor for proper system working complete in all respect under item 5.0 of BOQ
Tube Settler media arrangement
Supply, Installation, Testing and Commissioning of Electo Magnetic Flow Meter for Total Plant Capacity of 30 KLD compact instrument version with measuring sensor (Primary) and Amplifier integrated in one mechanical unit (Suitable for required flow range, inlet/outlet connections, LCD Alphanumeric Display for flow rate, totalizer, with all accessories for inlet flow measurement after sewage transfer pumps from main equalization tanks.
Max. Flow Rate -5 m3/hr
Filter Feed Pumps:
Providing and fixing Horizontal centrifugal pumping set for filter feed pumps and discharging into the treated water tank. The pumps shall have CI casing, Bronze impeller - EN 8 shaft shaft with mechanical rotary shaft. TEFC induction motor mounted on a common channel base-plate, 100 mm dia pressure gauge, GM isolation cock, Motor to be suitable for 400/440 V, 3 Phase, 50 cycles AC power supply. Including all necessary piping, valves and other accessories .
Capacity : 5m3/h @ 30 mtr head(1W+1S)
Sludge Transfer Pumps( For Suitable FAB /FMR /MBBR System)
Providing and fixing horizontal, sludge from instantaneous sludge (for FAB/FMR/MBBR) to sludge holding tank or part of sludge re-circulate into reator for maintaining desired MLSS. The pumps shall have CI casing, impeller - shaft with mechanical rotary shaft to a TEFC induction motor mounted on a common channel base-plate with coupling guard, GM isolation cock, approved design. Motor to be suitable for 400/440 V, 3 Phase, 50 cycles AC power supply. Including all necessary piping, valves and other accessorie.
Capacity 5 m3/hr @ 12-15m for MBBR System.(1W+1S)
Multi Grade Sand filter:
Providing, fixing, testing & commissioning of vertical Pressure Sand Filter fabricated from MS sheet as per manufacturer’s specifications with MS frontal piping complets with two or more coats of approved epoxy paint including valves to provide service , backwash and rinsing operations. Complete with initial charge of filter media. Including Anthracite. Filter shall be painted with two coats of approved epoxy paint inside as well as outside of filter complete in all respect.
Dia & Height -- 600 mm X 1600 mm
Shell Thickness -- 6 mm
Dish Thickness -- 8 mm
Filtration Rate -- 10 m3/hr./m2
Test pressure -- 5.5 Kg/Cm2
Working Pressure - 3.5 Kg/Cm2
Capacity 5CUM / Hr
Activated Carbon Filter:
Providing and fixing vertical MS Activated carbon Filter of as filter media. The shell shall be fabricated from complete with initial charge of filter media. MS frontal piping, complete with two or more coats approved of epoxy point including valve for service, rinse & backwash alongwith other accessories. Filter shall be painted with two coats of approved epoxy paint inside as well as outside of filter complete in all respect.
Dia & Height -- 600 mm X 1600 mm
Shell Thickness -- 6 mm
Dish Thickness -- 8 mm
Filtration Rate - 10m3/hr/m2
Test Pressure - 5.5 kg/cm2
Working Pressure - 3.5 Kg/Cm2
Capacity 5 CUM / Hr
Water Meter:
Supply, Installation, Testing and Commissioning of Electo Magnetic Flow Meter for Total Plant Capacity of 100 KLD compact instrument version with measuring sensor (Primary) and Amplifier integrated in one mechanical unit (Suitable for required flow range, inlet/outlet connections, LCD Alphanumeric Display for flow rate, totalizer, with all accessories for inlet flow measurement after sewage transfer pumps from main equalization tanks.
50 mm dia (Irrigation system)
40 mm dia (Flushing system)
Air diffusion system shall include the following:
Twin type rotary air blowers capable of delivering required amount of free air at required pressure driven through “V” belt or directly coupled through flexible coupling to a TEFCmotor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles A/C supply .
Air flow rate 35m3/hr @ 0.50 kg/sq.cm. or as recommended by manufacturere / vendor/ contractor
Supply, Installation, Testing & Commissioning of Air piping shall comprise of pipes droppers/ laterals with MS (epoxy coated) Header complete with all ball valves & fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good in Equalization tank, Aeration tank & Sludge Holding Tank.
Supply, Installation, Testing & Commissioning of Non clog type air dispersion system comprises of Coarse bubble membrane diffusers in Equalization Tank, Sludge Holding and EPDM fine bubble membrane diffuers for aeration Tank capable of handling required air with better oxygen transfer efficiency / meter water depth. Air dispersion grid including valves & fittings etc.shall be assembled in modular form so that they can be replaced / repaired easily from platform at the top.
Supply, Installation, Testing & Commissioning all piping (as described below) and isolation control valves & fittings etc. for making the system complete.
HDEP/PVC
Submerged air piping in EQT's, SHT and MBBR TANK
MS (EPOXY COATED) :
Air piping & pumped effluent riser (non-submerged).
PVC piping :
Pumped effluent (submerged) & tank overflow pipe line.
UPVC (Heavy) :
Interconnecting pipe line after delivery header of pump/ filter.
Hypo Dosing Pumps having capacity of 0-6 LPH Metering Type with dosing Tanks of 100 Lits.
Electrical Panel/Distribution Board:
Supply, installation, testing and commissioning of electrical panel free floor standing. The panel sheet structure shall undergo seven tank pre-treatment process before painting. The sheet steel shall be all of 14 SWG/2mm thick CRCA sheet. The panel shall be provided with minimum 75mm base channel frame fabricated from ISMC sections. A Continuos earth bus shall run alround the panel with earthing studs provided at minimum 2 places. The control wiring shall be carried out with minimum 2.5 sq.mm copper wires and adeq for remote operation of the starters suitable for STP Equipements.
Supply, Installation, Testing and commissioning of electrical panle Suitable for 30 KLD STP Plant, Including Incomer, outgoing, cable, wires and cable trays with all accessores including earthing system to complete the plant operational as required.
Vender Should submit the complete electrical SLD with all load details along with the tender.
Supply, installing, testing and commissioning of electronic type level controller for filter/ ultra filtration feed pumps and chlorine contact tank comprising of dry run protection in chlorine contact tank low and high level start and stop complete in all respect (for chlorine contact tank and treated water tank and softwater tank ).
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.76 MB
BDA_BUILDING_TECH_BID.pdf
Tender Documents • 6.40 MB
BOQ_942205.xls
BOQ • 1.33 MB
Download all tender documents and submit your bid