Lt Col Priyesh Srivastava
GE AF SURATGARH
REPAIR/MAINT OF CONVENTIONAL EARTHING /CHEMICAL EARTHING LIGHTENING ARRESTER LT PANEL CAPACITOR PANEL UG CABLE SERVO STABILIZER HANGER LIGHTS BLAST PEN DISPERSAL LIGHTS GO-ON-GO LIGHTS AND CONNECTED E/M WORKS AT AF STN SURATGARH
2023_MES_624835_1
8110/E8
Open Tender
Civil Works
Item Rate
180 days
SURATGARH
As per tender documents
10 documents required · 10 mandatory
₹500
GE AF SURATGARH
₹99,800
Yes
12 Dec 2023
25 Oct 2023
24 Nov 2023
25 Oct 2023
22 Nov 2023
8 Nov 2023
Amount
BOQ (REPAIR/MAINT OF CONVENTIONAL EARTHING /CHEMICAL EARTHING LIGHTENING ARRESTER LT PANEL CAPACITOR PANEL UG CABLE SERVO STABILIZER HANGER LIGHTS BLAST PEN DISPERSAL LIGHTS GO-ON-GO LIGHTS AND CONNECTED E/M WORKS AT AF STN SURATGARH.)
M&L for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of 32 x 6 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected up to main DB/LT Panel /Test point and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009 (Part-I), including dismantling old unserviceable earthing complete all as specified and directed.
M&L for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using GI wire 4mm dia as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected up to main DB/LT Panel /Test point and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009 (Part-I), including dismantling old unserviceable earthing complete all as specified and directed.
M&L for removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrosion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with copper strip of size 32 x 6 mm upto test point, strip should be run on PCC block of suitable size upto wall to avoid touching to ground including connecting of strip between two earthing earth pit cover, including dismantling old unserviceable earthing material complete all as specified and directed by Engr in charge.
(a) The test result of each set of earthing is less than 1.0 ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep,User Rep and test result will be recorded in a register with sign of User & Engr-in-charge. (b) 5 Year gaurantee certificate from company for maintaining earth result less than 1 Ohm will be submitted by contractor. (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm. (d) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
M&L for removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrosion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with Copper strip of size 32X6 mm upto test point strip should be run on PCC block of suitable size to avoid touching to ground including connecting of Strip between two earthing, including dismantling old unserviceable earthing complete all as specified and directed by Engr in charge.
(a) The test result of each set after coupling it with existing 02/01 earthing of earthing is less than 1.0 ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep,User Rep and test result will be recorded in a register with sign of User & Engr-in-charge. (b) 5 Year gaurantee certificate from company for maintaining earth result less than 1.0 ohm will be submitted by contractor (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm (d) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
M&L for removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved chemical earthing with copper earth plate electrode 90cm x 60cm x 5 mm thick buried directly in ground vertically at a depth not less than 4.2 metre below normal ground level with top edge of earth plate at a depth not less than 3 meter below normal ground level, earth plate covered with LHOM Earth enhancing chemical compound (Bentonite powder) all around the plate upto 30 cm and electrode connections by using copper strip of 32 x6 mm as earthing lead (upto the test point) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 80mm dia GI pipe filled with earth enhancing chemical compound connected to main switch board or main control board including RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR part 1 complete all as specified and as directed by Engineer-in-charge.
(a) The test result of each set of earthing is less than 1.0 ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep,User Rep and test result will be recorded in a register with sign of User & Engr-in-charge. (b) 5 Year gaurantee certificate from company for maintaining earth result less than 1.0 ohm will be submitted by contractor (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm (d) Earth enhancing compound (Bentonite powder) (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
S&F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm copper strip as earthing lead with saddles and fixing screws etc, including takingdown old GI strip complete all as specified & directed
S&F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x4mm galvanised iron strip as earthing lead with saddles and fixing screws etc, including takingdown old GI strip complete all as specified & directed
S&F test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed inlcuding 3 Nos 8 mm dia 25 mm long hexagonal head screw, fixed as in repair complete all as specified and directed.
S&F of copper strip of size 20 x 3.15 mm on PVC/porcelain insulator at suitable distance with saddles and fixing screw etc for roof/Wall conductors and down conductors above ground all joints of copper strip should be brazed properly, including takingdown old copper strip complete all as specified and directed.
S&F air termination single pointed copper rod 12mm dia 300mm long, fixed as in repair complete all as specified and directed.
S&F air termination single pointed aluminium rod 12mm dia 300mm long, fixed as in repair complete all as specified and directed.
Material and labour for PCC 1:3:6 type C-1 using 20 mm grade stone aggregrate in surface of roof Kerbs (square/rounded type) , mass concrate as in surface of top roof for fixed the Air termination rod complete all as specified and directed.
Supply only 15mm PVC hose pipe for supply the water from tap to earth pits complete all as specified and directed.
S&F right circular Rotational moulded PVC, white colour, tripple layered, water storage tanks of capacity 250 litre (cylindrical vertical with closed top), ISI Marked, hoisted and fixed in position, with & including all fittings such as GI tank nipple etc. , ball valve , complete all as specified and directed by Engineer –in-Charge.
M&L for copper brazing for copper strips of various sizes laying on wall /roof etc with the help of welding machine and skilled tradesmen by using welding rod etc by taking safety precautions during brazing as directed by the AGE EM / users, including takingdown unserviceable copper strips complete all as specified and as directed by Engr in Charge
M&L for brazing for GI strips of various sizes laying on wall /roof etc with the help welding machine and skilled tradesmen by using welding rod etc by taking safety precautions during brazing as directed by the AGE E/M / users, including takingdown unservicable GI strips complete all as specified and as directed by Engr in Charge.
M&L for fixing the porcelain cleat with the help of nut,bolts clamps etc to fix the strips of various size and types to separate from ground and wall as directed at site by Engr in charge, fixed as in repair complete all as specified & directed.
M&L for PVC conduit heavy duty of 40 mm dia size for the protection of the earthing strip on wall/roof with the help nuts ,bolts clamps, PCC work etc as directed at site by Engr in charge
Supply only salt using for earthing pits as directed at site by Engr in Charge
Supply only charcoal using for earthing pits as directed at site by Engr in Charge
Supply and fix FRP based earth pit cover suitable for chemical earthing all as specified and directed by engr-in-charge.
M&L for PCC(1:3:6) type C2 using 40mm graded aggregate earth pit chamber with PCC cover suitable for conventional earthing all as specifed and directed by Engr-in-charge
M&L for Colour coding and marking of earthing pits for LA earthing, signal earthing,equipment earthing and power supply earthing on the MS sheet of 2mm thick of size 30x30cm mounted on 60cm long steel bar of dia 8mm including excavation work ,grouted in cement concrete ,welding painting are deemed inclusive in the quoated rates and colour for coding of earth complete all as specified and directed by the Engr in Charge . Note :- Where ever any transportaion / labour is required for shifting of any machinery/equipment to workshop for carrying out repairs, same shall be arranged under own cost of the contractor. Rates quoted are deemed to be inclusive of this provision.
Supply, fixing, testing and commissioning in replacement of air break isolating switch triple pole mechanically operated with vertical isolation, 12 insulators mounted on steel frame with operating mechanism worked from ground level and including operating rod of 25 mm dia medium grade GI pipe and locking arrangement of capacity 400 Amps 11 KV with drop out fuse set including making all incoming/outgoing connection of HT cable and overhead conductor using new leads and nuts, bolts etc and painting of steel work with 2 coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
S&F MCCB four pole 63 Amps with breaking capacity 16 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 100 Amps with breaking capacity 16 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 125 Amps with breaking capacity 25 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 160 Amps with breaking capacity 25 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 200 Amps with breaking capacity 35 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 250 Amps with breaking capacity 35 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 320 Amps with breaking capacity 36 KA , 415 Volts, adjustable thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F MCCB four pole 400 Amps with breaking capacity 36 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge.
S&F Ampere meter digital type of ratio 0-100 Amp, size 95 Sqmm square type including making incoming/outgoing connections fixed as in repair,complete all as specified and directed by Engineer in Charge.
S&F Voltmeter digital type of ratio 0-415 volt , size 95 Sqmm square type including making incoming/outgoing connections fixed as in repair ,complete all as specified and directed by Engineer in Charge.
S&F Indicator lamp assembly LED type with red/green/blue including making connections fixed as in repair ,complete all as specified and directed by Engineer in Charge.
S&F Current transformer (CT) ratio 100/5 including making connections fixed as in repair ,complete all as specified and directed by Engineer in Charge.
M&L for refixing shifting of existing LT panel/ APFC panel of any capacity/size by taking proper shutdown from power house and disconnecting cables connection both incoming and outgoing complete fixing in new location including making new incomming and outgoing connection , complete all as specified and directed by Engineer-in-Charge. Note: All earth work, sand filling, bricks and PCC works will be measured and paid separately under respective item.
M&L for cleaning of Installation/ Substation including clearing of vegitation, wild growth and trimming of grass etc around the installation compound and removing rubbish off the premises , complete all as specified and directed by Engineer-in-Charge.
M&L for rubbing rusted surface of LT panel/ feeder piller, cleaning the inner and outer surface of panel/ feeder piller box and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer including marking name of incomming and outging connection on LT panel , complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exc 1.5m wide and and not exc. 1.5m depth wide in soft/loose soil for laying electric cables/pipes etc including getting out excavated earth and trimming the sides and bottoms of trenches , complete all as specificed and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested, complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point , complete all as specified and directed by Engineer-in-Charge.
M&L for sand cushioning to cables with a layer of sand 8 cm deep before laying the cable and 15 cm depth (punned down to 10 cm depth after laying and stretching of cable), complete all as specificed and directed by Engineer-in-Charge. Note: Punned thickness (over all 18 cm) shall be measured & paid.
S&F brick of common burnt clay, sub class 'B' old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other , complete all as specified and directed by Engineer-in-Charge.
Taking out old unserviceable LT/HT cable from trenches /Wall/ floor etc and keeping aside for reuse or removal of any size , complete all as specified and directed by Engineer-in-Charge.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 10 Sqmm 2 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 16 Sqmm 4 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 35 Sqmm 4 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 50 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 95 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F Steel tubing galvanised iron, light grade, 40mm bore for cable protection along the pole, under road/depth or under drains ,complete all as specified and directed by Engineer-in-Charge.
Excavation of road cutting by manually including making good to disturb surface after the completion of work with PCC 1:2:4 type B2 on top not less than 150 mm thick including levelling and cambering according to existing road surface, refilling, watering, ramming etc all as specefied and as directed.
Disconnecting LT cable connection, opening, 3 phase voltage stabilizer upto 200 KVA, of make such as Vintek, Blue line, ITE or any other make , balanced or unbalanced type, draining of transformer oil, replacement of unserviceable parts, servicing of moving parts, adjustment of bush assembly, tightening of electric connection, replacement of worn out nuts, bolt, gaskets, carbon brushes, re-filling of transformer oil, reassembling, making connections well cleaning and preparattion of surfaces of servo stabilizer cleaning the inner surface of stabilizer and applying two coats of synthetic enamel paint over a coat of red oxide zinc chorome primer to the outer surface including marking of SM/MES No with white synthetic enamel paint and testing ,complete all as specified and directed by Engineer-in-charge. Note: a) Voltage stabilizer must be repaired by original manufacturer or by authorised service provider of tthe company . b) Spare parts required for replacement will be measured and paid for separately under respective items of schedule, labour for fixing parts is included in the unit rate of item. c) All T & P and transportaion arrangement are deemed to be included in the rates quoted.
Supply only following parts suitable for three phase servo voltage stabilizer upto 200KVA capacity as per existing make or as recommended by original stabilizer manufacturer , complete all as specified and directed by Engineer-in-Charge.
Volt Meter/(Digital/Analog)
Amperer Meter CT Digital/Analog)
Micoprocessor based control card for each phase.
Servo synchronizing motor single phase AC 230 V, 3 Kg torque.
Servo synchronizing motor single phase AC 230 V, 10 Kg torque.
RC Network for 3 Kg torque servo motor.
RC Network for 10 Kg torque servo motor.
Carbon Brush of any capacity.
Supply only dimmerstate unit suitable following capacity of three phase servo voltage stabilizer as per existing make or as recommanded by original manufacturer:-
Capacity 50 KVA, 32 Amps
Capacity 75 KVA, 45 Amps
Capacity 100 KVA, 80 Amps
Capacity 150 KVA, 150 Amps
Supply only main transformer unit suitable for following capacity of three phase servo voltage stabilizer as per existing make or as recommanded by original manufacturer:-
Capacity 50 KVA
Capacity 75 KVA
Capacity 100 KVA
Capacity 150 KVA
Dehydration including filteration and cleaning of transformer oil by dehydration machine to achieve the die-electric strength BDV 50KV at standard gap of electrodes 2.5 mm for one minute including testing of oil with help of suitable equipments after dehydration including oil insulation test before and after dehydration including BDV Test ,complete all as specified and directed by Engineer-in-charge. Note : Contractor shall arrange the dehydration machine and transformer oil, dielectric strength testing equipment or other testing equipments as mentioned and same shall be deemed to be included in the item rate quoted including testing sample before and after dehydration and filtration oil
Supply and filling trasformer power oil meeting IEC 60296-2003-11 3rd edition standard specification and ASTMD 1275B test requirements for corrosive sulpher of BDV not less than 65 KV for filling in repaired Stabilizer , complete all as specified and directed by Engineer-in-Charge.
Dismantling existing unserviceable panel and removal from site and Supply and installation LT Electric control panel, cubical type, for out door use, dust & vermin proof floor mounted made out of CRCA steel sheet of 3.15 mm thick and 2.00 mm thick CPRI approved other parts and angle iron legs of size 50mmx50mmx6mm having front and rear hinged doors with front openable shutters for each MCCB with spreader & extended rotary handle having hinges on one side and locating arrangements with screws type on other sides completely with fully enclosed bus bar chamber, having electrolytic high conductivity insulated bus bar made one of aluminium strips of rating 400 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter , Ammeter and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete all as ncluding necessary PCC work of height 45 cm from the ground level , complete all as specified and directed by Engineer-in-Charge and equipped with the following items. Note: Drawing and all materials viz MCB/MCCB/ instruments etc for LT panel shall be got approved by GE before fabrication. Rate for MCCBs, MCBs, instruments is included in unit rate of items .(Location-ATC) Contd item No 61.01
Supply, Installation and Commissioning LT Feeder Pillar Box of Size 75x75x45cm Outdoor Type Factory made manufactured by a CPRI approved Manufacturer, made out of 3 mm thick CRCA Sheet and Self Supporting, built upon Rigid Frame Work suitable for 440 Volt 3 Phase 4 Wire System having Front and Rear Hinged Doors with Neoprene Rubber Gasket, Epoxy Powder Coated with Danger Plate, Earthing Strip Point and Bottom Detachable Gland Plate complete with suitable Size Zinc Chromium Plated Nuts, Bolts and Washers, etc. having Colour Code aluminum bus bar inter connections for easy Identification including Incoming/Outgoing Cable Holes at Bottom, provision of six nos connectors and embedded with Mild Steel Angle Iron Frame of Size 50X50X6mm and 600mm above Normal Ground Level complete with PCC Foundation in Cement Concrete (1:2:4) type B1 (20mm Graded Stone Aggregate) and Testing after Instalation including Taking down Unserviceable Feeder Pillar Box with Connected Accessories after disconnecting all Incoming and Outgoing Cables, etc., complete all as specified and comprising with the following :–
(a) Aluminium Bus-bar 400 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos (b) MCCB, 4 pole, 200 Amps , rupturing capacity 36 KA Adjustable thermal & Adjustable magnetic release - 01 Nos. (AS INCOMING),L&T/Legrand/ Havelles
Supply, Installation and Commissioning LT Feeder Pillar Box of Size 75x75x45cm Outdoor Type Factory made manufactured by a CPRI approved Manufacturer, made out of 3 mm thick CRCA Sheet and Self Supporting, built upon Rigid Frame Work suitable for 440 Volt 3 Phase 4 Wire System having Front and Rear Hinged Doors with Neoprene Rubber Gasket, Epoxy Powder Coated with Danger Plate, Earthing Strip Point and Bottom Detachable Gland Plate complete with suitable Size Zinc Chromium Plated Nuts, Bolts and Washers, etc. having Colour Code aluminum bus bar inter connections for easy Identification including Incoming/Outgoing Cable Holes at Bottom, provision of six nos connectors and embedded with Mild Steel Angle Iron Frame of Size 50X50X6mm and 600mm above Normal Ground Level complete with PCC Foundation in Cement Concrete (1:2:4) type B1 (20mm Graded Stone Aggregate) and Testing after Instalation including Taking down Unserviceable Feeder Pillar Box with Connected Accessories after disconnecting all Incoming and Outgoing Cables, etc., complete all as specified and comprising with the following :–
(a) Aluminium Bus-bar 500 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos (b) MCCB, 4 pole, 320 Amps , rupturing capacity 36 KA Adjustable thermal & Adjustable magnetic release - 01 Nos. (AS INCOMING),L&T/Legrand/ Havelles
Taking down carefully Unserviceable high bay light/hanger lights/Dispersal lights/Blast pen light fitting from pole/Structure and repair/replacement of worn out parts and carbon cleaning of fittings,cover,copper wire/aluminium wire,clamps ,nuts and bolts, mounting bracket and re assembling the same after repair,testing and refixing in pole/other location including provision of necessery T & P like ladder/Boom Vehicle, tools ets as required for taking down and refixing of hanger light complete all as specefied.
Note : Replacement of defective spare parts of fitting (to make functional ) will be measured and paid separately as supply only. However, cost of replacement screws, nuts, bolts, and cleaning of fittings shall be deemed to be included in quoted rate.
Taking down existing old unserviceable underground LT cable upto size 50 Sqmm, 4/3.5 /2 core keeping aside for reuse/removal from trenches/ wall/pole , complete all as specified and directed by Engineer-in-Charge. NOTE : Excavation and earth work shall be measured and paid separately.
S&F XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 35 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
S&F Galvanised iron steel tubes, ISI marked light grade of size 50 mm bore for cable protection along the poles under road under drains, laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etc including taking down of old unserviceble pipe , complete all as specified and directed by Engineer-in-Charge.
Taking down carefully aluminum point wiring (light, fans, socket etc) complete including battens and fittings such as switch, ceiling rose, light fittings, regulators, socket, etc. and making good disturbed surface of wall/floor, etc. complete all as specified and directed by Engineer-in-Charge. Note :- Temporary power supply shall be provided by contractor.
S&F Point wiring (surface) complete with FRLS PVC insulated unsheathed 1100 Volts grade, conforming to IS-694, 1.5 sq mm (nominal area) multi stranded copper conductor cable drawn though in including metallic medium grade rigid steel conduit accessories, ISI marked, 19/20 mm dia including all accessories on the surface of walls/floors/ceilings and making good the disturbed surface, with and including sunken type pressed steel/welded MS terminal box 1.2 mm thick bakelite laminated sheet top cover 3 mm thick and 1.5 Sq mm copper earth continuity wire connected to earth dolly complete forone Light point controlled by one switch, complete all as specified and directed by Engineer-in-Charge.
S&F Point wiring (surface) complete with FRLS PVC insulated unsheathed 1100 Volts grade, conforming to IS-694, 2.5 sq mm (nominal area) multi stranded copper conductor cable drawn though in including metallic medium grade rigid steel conduit accessories, ISI marked, 19/20 mm dia including all accessories on the surface of walls/floors/ceilings and making good the disturbed surface, with and including sunken type pressed steel/welded MS terminal box 1.2 mm thick bakelite laminated sheet top cover 3 mm thick and 2.5 Sq mm copper earth continuity wire connected to earth dolly complete One 3 pin socket outlet 15 Amps independent board with cable 2.5 sqmm copper conductor and 2.5 sqmm cable as earth continuty conductor complete all as specified and directed
S&F Switch piano flush button single pole one way 5 amp 240 volts, including connecting and testing , complete all as specified and directed by Engineer-in-Charge.
S&F Ceiling rose, surface bakelite, 65 x 50 mm, three terminals, including connecting and testing, complete all as specified and directed by Engineer-in-Charge.
S&F Switch socket combination 5 in 1, 5 and 15 Amp flush type universal including connecting and testing ,complete all as specified and directed by Engineer-in-Charge.
S&F Gong bell (Buzzer type) electric 230 volt AC, 50 Hz for GO NO-GO lights, fixed as in replacment , complete all as specified and directed by Engineer-in-Charge.
Supply and fixing LED light fitting 1x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitablesize, including taking down old unserviceable light fitting, complete all as specified and directed by Engineer-in-Charge.
Supply and Fixing of Flameproof cum Waterproof LED Bulk Head light fitting of 15W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size including taking down old unserviceable light fitting, complete all as specified and directed by Engineer-in-Charge.
Open construction heavy duty copper ballast for HPSV/MH 400 W light fittings including taking down of old unserviceble ballast , complete all as specified and directed by Engineer-in-Charge.
Open construction heavy duty copper ballast for HPSV/MH 150 W light fittings including taking down of old unserviceble ballast , complete all as specified and directed by Engineer-in-Charge.
MH lamp 150 watts (DE) ,fixed as in replacment of old unservicable material , complete all as specified and directed by Engineer-in-Charge.
Ignitor for 250W/150W/400W HPMV/HPSV/MH light fittings ,fixed as in replacment of old unservicable material , complete all as specified and directed by Engineer-in-Charge.
M&L for LED Highbay 150 Watt suitable for Hangers / industrial application heat sink made of copper & equipped with fluid dynamic pressure technology ,lumen efficacy > 150 lm/w , CRI > 85% ,THD < 15% UL certified , driver equipped with double power embedded system, & automatic Power Shutdown and returning circuit embedded with Power supply, which turns off power against Fire, High Temperature, Over-voltage and Over-current. The luminarie should have 5 KV surge protection, PF > 0.95. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report, including taking down old unserviceable light fitting , complete all as specified and directed by Engineer-in-Charge. Make: Havells Cat No SAUCERGENXADVHBP150WLED857PNBBORL/ Crompton or equivalent
M&L for LED Highbay 120 Watt suitable for Hangers / industrial application heat sink made of copper & equipped with fluid dynamic pressure technology ,lumen efficacy > 120 lm/w , CRI > 85% ,THD < 15% UL certified , driver equipped with double power embedded system, & automatic Power Shutdown and returning circuit embedded with Power supply, which turns off power against Fire, High Temperature, Over-voltage and Over-current. The luminarie should have 5 KV surge protection, PF > 0.95. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report, including taking down old unserviceable light fitting , complete all as specified and directed by Engineer-in-Charge. Make: Havells Cat No SAUCERGENXPROHBP100Wled757P60dBoltG/ crompton or equivalent
Supply and fix 150 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 16500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-charge. Make : Havells Cat No JETAIRISFLS150WLED757P2AV2WBLTG/crompton or equivalent
Dismantling unserviceable motor from electrically operated gate of hangers, rewinding and refixing the motor, replacement of unserviceable SWR and Fan Belt, oiling and greasing of all pullies and wheel of the gate, repair of starter and making gates fully operational , complete all as specified and directed by Engineer-in-Charge.
Earth continuity conductor or main earthing lead of galvanised iron strip of size 32x6mm fixed to wall on insulators or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc , including taking down existing unserviceable galvanised iron strip, complete all as specified and directed by Engineer-in-Charge.
Epoxy base insulators of suitable size 40mm height for fixing GI earth strip on wall/ceiling/floor/poles etc. including taking down existing unserviceable insulators, complete all as specified and directed by Engineer-in-Charge.
Earth continuity conductor or main earthing lead of 25 x 3 mm aluminium strip fixed to wall on insulators or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc , including taking down existing unserviceable aluminium strip, complete all as specified and directed by Engineer-in-Charge.
Air termination, single pointed aluminium rod 12 mm dia and 300 mm long bolted to aluminium strip 25x3 mm , including fixing brackets, clamps made out of steel sections, nuts,bolts and securing of complete system on roof of the building, including taking down existing unserviceable aluminium air termination rod, complete all as specified and directed by Engineer-in-Charge.
Supply, Installation and Commissioning LT Feeder Pillar Box of Size 75x75x45cm Outdoor Type Factory made manufactured by a CPRI approved Manufacturer, made out of 3 mm thick CRCA Sheet and Self Supporting, built upon Rigid Frame Work suitable for 440 Volt 3 Phase 4 Wire System having Front and Rear Hinged Doors with Neoprene Rubber Gasket, Epoxy Powder Coated with Danger Plate, Earthing Strip Point and Bottom Detachable Gland Plate complete with suitable Size Zinc Chromium Plated Nuts, Bolts and Washers, etc. having Colour Code aluminum bus bar inter connections for easy Identification including Incoming/Outgoing Cable Holes at Bottom, provision of six nos connectors and embedded with Mild Steel Angle Iron Frame of Size 50X50X6mm and 450mm above Normal Ground Level complete with PCC Foundation in Cement Concrete (1:2:4) type B1 (20mm Graded Stone Aggregate) and Testing after Instalation including Taking down Unserviceable Feeder Pillar Box with Connected Accessories after disconnecting all Incoming and Outgoing Cables, etc., complete all as specified and comprising with the following :–
(a) Aluminium Bus-bar 200 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos
Supply and fix MCB SPN 240 volts 6 to 32 Amps breaking capacity 10 KA 'C' Series rating 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc fixed in repair complete all as specified and directed.
S&F MCB SP, 6 to 32 Amps, C series, breaking capacity 10 KA, 'C' curve 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc fixed in repair complete all as specified and directed
Supply and fix 2 core 4 sqmm PVC insulated PVC sheathed weather proof multistranded aluminium conductor cable 1100 volts grade drawn through in GI conduit, pole etc with MS clamps from junction box to street light fitting all as specified and directed.
Contract Amount shall be derived after affecting the amount of Schedule of Credit in General Summary on serial page No 17 of tender documents.
m/s krishna builders
SRI SAI CONSTRUCTION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .