Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAccepted-AOC 1630 SECTOR 7C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | ₹4.4 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹4.5 Cr+₹7.0 L (1.58%)Rejected-AOC | ₹4.5 Cr+₹7.0 L (1.58%) | L2 | Rejected-AOC Not Being L1 |
| 3 | L3₹4.7 Cr+₹27.8 L (6.29%)Rejected-AOC 04 L BLOCK MARKET SECTOR 11 NOIDA 201301 UP GAUTAM BUDHA NAGAR | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹4.7 Cr+₹27.8 L (6.29%) | L3 | Rejected-AOC Not Being L1 |
| 4 | L4₹5.0 Cr+₹56.9 L (12.9%)Rejected-AOC STREET NO 11 SECTOR NO 04 TILAK NAGAR SAGAR ROAD BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | ₹5.0 Cr+₹56.9 L (12.9%) | L4 | Rejected-AOC Not Being L1 |
| 5 | L5₹5.2 Cr+₹82.0 L (18.6%)Rejected-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹5.2 Cr+₹82.0 L (18.6%) | L5 | Rejected-AOC Not Being L1 |
| Sl No | Description | Qty | Unit | PURBANCHAL BUILDERS L5 | SHRI GANESH ENTERPRISES L2 | GEPS PROJECTS L3 | FRIZO INDIA PVT LTD L4 | SAGGI ELECTRIC COMPANY L1 |
|---|---|---|---|---|---|---|---|---|
| .00NOTE:- (i) Schedule 'A' Part I to VII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. (ii) Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates. | ||||||||
| 1.00 | Total amount of Sch 'A' Part I (Building)
Note : Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 55,99,999 ₹55,99,999 | 42,32,000 ₹42,32,000 | 60,00,000 ₹60,00,000 | 70,00,000 ₹70,00,000 | 39,88,574 ₹39,88,574 Lowest |
| 2.00 | Total amount of Sch 'A' Part-II (INTERNAL ELECTRIC SUPPLY).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 1,49,279 ₹1,49,279 Lowest | 1,79,367.26 ₹1,79,367.26 | 2,10,000 ₹2,10,000 | 2,00,000 ₹2,00,000 | 1,68,707 ₹1,68,707 |
| 3.00 | Total amount of Sch 'A' Part-III (INTERNAL WATER SUPPLY).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 22,499 ₹22,499 | 11,178.08 ₹11,178.08 | 45,000 ₹45,000 | 15,000 ₹15,000 | 10,279 ₹10,279 Lowest |
| 4.00 | Total amount of Sch 'A' Part-IV (SITE CLEARANCE AND EARTH WORK).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 11,82,999 ₹11,82,999 | 12,10,360.15 ₹12,10,360.15 | 15,00,000 ₹15,00,000 | 13,00,000 ₹13,00,000 | 9,20,620 ₹9,20,620 Lowest |
| 5.00 | Total amount of Sch 'A' Part-V (ROADS, PATH AND CULVERT).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 56,999 ₹56,999 Lowest | 57,537.94 ₹57,537.94 | 1,00,000 ₹1,00,000 | 75,000 ₹75,000 | 59,904 ₹59,904 |
| 6.00 | Total amount of Sch 'A' Part-VI (EXTERNAL WATER SUPPLY).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 2,79,999 ₹2,79,999 | 1,54,870.01 ₹1,54,870.01 | 1,71,000 ₹1,71,000 | 1,70,000 ₹1,70,000 | 1,46,269 ₹1,46,269 Lowest |
| 7.00 | Total amount of Sch 'A' Part-VII (LIGHTINNG PROTECTION ).
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 99,999 ₹99,999 | 91,804.4 ₹91,804.4 | 1,80,000 ₹1,80,000 | 1,00,000 ₹1,00,000 | 86,130 ₹86,130 Lowest |
| 8.00 | Total amount of Sch 'A' Part-VIII (SEWAGE DISPOSAL )
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 16,299 ₹16,299 | 10,054.38 ₹10,054.38 | 30,000 ₹30,000 | 20,000 ₹20,000 | 8,990 ₹8,990 Lowest |
| 9.00 | Total amount of Sch 'A' Part-IX (FENCING AND GATE )
Note: Details of prepriced schedule are given in tender documents. | 1 | Lump sum | 4,72,999 ₹4,72,999 | 3,46,731.32 ₹3,46,731.32 | 4,50,000 ₹4,50,000 | 4,00,000 ₹4,00,000 | 3,43,930 ₹3,43,930 Lowest |
Tender Value
₹5.6 Cr
EMD Value
₹6.1 L
Closing Date
23 Dec 2025, 6:00 pmClosed
CWE AF Borjhar
HQ CWE AF Borjhar Military Engineer Services PO Airport Borjhar Guwahati Assam 781015 Tele 0361 2841626
PROVN OF 33 KV SUBSTATION AND DISTRIBUTION TRANSFORMER VCBs AND ALLIED WORKS UNDER GE AF BORJHAR
2025_MES_728002_2
CWE(AF)/BOR/TOKEN-17/ 2025-26
Open Tender
Electrical and Maintenance Works
Lump-sum
365 days
Borjhar
As per tender documents.
7 documents required · 7 mandatory
₹3,000
GE (AF) Borjhar
₹6.1 L
Yes
6 Feb 2026
9 Dec 2025
25 Dec 2025
9 Dec 2025
23 Dec 2025
16 Dec 2025
NOTE:- (i) Schedule 'A' Part I to VII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. (ii) Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
Total amount of Sch 'A' Part I (Building) Note : Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-II (INTERNAL ELECTRIC SUPPLY). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-III (INTERNAL WATER SUPPLY). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-IV (SITE CLEARANCE AND EARTH WORK). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-V (ROADS, PATH AND CULVERT). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-VI (EXTERNAL WATER SUPPLY). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-VII (LIGHTINNG PROTECTION ). Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-VIII (SEWAGE DISPOSAL ) Note: Details of prepriced schedule are given in tender documents.
Total amount of Sch 'A' Part-IX (FENCING AND GATE ) Note: Details of prepriced schedule are given in tender documents.
Supply and fix lightning arrestor for 33 KV with 10 KA station class poreclian type complete including taking down old unseriveable all as specified and directed by Engineer in charge.
Sch 'A' Part-XI (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col 5 signifies this fact only.
Material and labour for construction of brick masonry valve chamber of size 600mm x 600mm x 750mm (Internal dimension) with PCC 1:3:6 foundation 150mm thick, brick work 23cm thick built in CM 1:6, PCC 1:3:6 coping 50 mm thick, plastering 15mm thick in CM 1:4 to all internal and exposed surfaces including excavation earth work in any type of soil, MS sheet cover 3mm thick fixed with angel iron frame 30x30x4 mm including hinges of size 125mm with locking arrangement embedded in PCC and painting ot MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc, complete all as specified and directed by Engr-in-charge.
1 A. 11 KV VCB (Main Incommer) : Supply, Installation, Testing and Commissioning of 11 KV 800 Amp, 26.3 KA cassette type with spring charging motor rated 230 VAC, tripping coil and closing coil suitable for and upto 110 VDC enclosed in IP 4X, steel enclosure for LV compartment, PT chamber, incoming and outgoing busbar compartment dimension of entire VCB (2080x600x1750) and thickness 16/2mm MS sheet steel with RAL 7032 powder coating with glossy finish with incoming back bottom entry & outgoing side exit with inbuilt anti-pumping system 6NO + 6NC contract complete all as specified and directed by Engr in charge. Current Transformer : 200-100A/5+5A, CL-0.5+15VA, 10P10+15VA double core, double ratio STC 26.3 KA for 1 sec resign cast. Potential Transformer : 11000/ /3/110 /3, Cl-I, 200 VA single core three phase, drawout type potential transformer with 3.15A 11 KV fuse primary fuse protection. 1 B. Protection Equipments : (i) IDMT relay 230 VAC, 5A, 50, 50N, 51.5 IN protection with 3 O/C + 1 EF (REJ601/MicomP127/140) (ii) Master trip relay 86 protection suitable upto 110 VDC (iii) Trip circuit supervision relay, ANSI, 95TC, suitable upto 110 VDC (iv) Aux contactor with 2NO+2NC addon block suitable upto 110 VDC (v) Space heater (vi) Thermostat with "L" fixing bracket (vii) Suitable protection devices for all protection like IDMT relay auxilary supply, PT sec protection ,closing tripping spring charge, AC DC indicator heater thermostat plug socket, DC supply power pack etc., as required 1 C. Monitoring Equipments : (i) 3 PH multifunctioning meter, CL-0.5 (ii) 3 Ph, 3 Wire digital TVM, CL-0.5 (iii) Hooter, suitable for and upto 110 VDC (iv) LED indication lamp for breaker on - Red (v) LED indication lamp for breaker off - Green (vi) LED indication lamp for breaker auto trip - Amber
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE Pipe 160/136 mm dia in any length including jointing materials to carry HT UG cables of size 185/400 Sqmm 3 core and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed. Note : Quoted rates inclusive of HDPE pipe 160/136 mm dia 0.4 MPA work pressure
Supply, laying, jointing, connecting using heavy duty lugs and testing of electric power cable, heavy duty 33KV (E) grade, XLPE insulated, screened, bedded, galvanised steel strip or wire armoured with aluminium conductor of cross sectional area of 300 sqmm, 3 core, laid in trenches/cable duct complete all as specified and directed.
RATE In Figures with all taxes and duties To be entered by the Bidder Rs. Ps.
Horizontal isolator double break triple pole mechanically operated mounted on double post insulator and steel frame out door type suitable for vertical installation single brake provided with locking arrangement, consisting of MS channel ,HT post type insulator 2 nos in each phase ,copper alloy high pressure assembly ,operating rod of 40/32 mm dia GI pipe heavy grade confirming to IS-1818 of 1972 ,suitable for 33000 volt ,400 Amps short time withstand current 72 KA for 3 sec complete all as specified.MAKE: CROMPTON GREAVES / ABB/ BHEL/AREVA/SIEMENS/jaipuria
Supply and install 33 KV Post insulator two in series 10 KN suitable for 33 KV system including necessary fixing arrangement complete all as directed.
Supply and fix drop out fuse unit suitable for 33000 volt ,400 amps mounted on MS channel complete with post insulator (two in series) fuse barrel etc for 3 phase.MAKE: CROMPTON GREAVES / ABB/ BHEL/AREVA/SIEMENS
Supply,Installation,Testing and commissionbing OUTDOOR TYPE Current Transformer, 36 KV, 200/100/5 A,, 2 CORE , CORE -I Burden 15VA Accuracy class 0.5 FOR METERING AND CORE -II Burden 30 VA Accuracy class 5P20 FOR PROTECTION CLASS AND COMPLETED system mounted on steel structure complete all as specified and directed.
Supply,Installation,Testing and commissioning OUTDOOR TYPE dead tank potential Transformer 36KV, ratio of 33/v3/110/v3/110/v3, Accuracy class core I- 0.5, core -II 3P, Class A insulation Burden 100 VA for both the core including terminal connectors and junction box outdoor type complete all as specified and directed
S&F Fire Extinguisher portable Foam type 6 ltr ISI Marked
Set of Three
Total amount of Sch 'A' Part-X (EXTERNAL ELECTRIC SUPPLY). Note: Details of prepriced schedule are given in tender documents.
Supplying and laying synthetic Rubber insulated mats 10 mm thick for voltage upto 33 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 1m x 2m
Supply only Electric rubber hand gloves 33 KV.
Supply, Install,testing and commissioning of battery bank OF 110 volt DC ( 55 nos Lead acid VRLA MAINTANANCE FREE battery of 2 volts 100 AH) INCL necessary internal connection , wooden/steel racks suitable for kept at powerhouse incl Automatic Floatt cum boost ( 20AMPS) Battery charging equipment SCR controlled suitable for 30Volts 100 AH VRLA batteries with the following features/accessiories. (i) input power supply 230 volt, 1 phase, 50 HZ, (ii) out put Voltage( Float/Boost Mode) 34 Volts, (iii) Output Current: 20 Amps (MAX) , at Float mode: 10 Amps DC continious plus Trickle charging Current, At boost mode: 15 Amps at Battery Terminal (iv) Mode of Operation /Terminal Charging : Automatic/Manual (v) Control configuration: 1-Phase full wave half control thyristorised bridge fed through 1-phase transformer and controlled by constant potential controller unit with load limiting feature. (vi) Protection against:(i) battery under/over voltage(ii) Battery over charge/overload, (iii) Short circuit(iv) Surge suppressor(v) AC/DC CURRENT PROTECTION. (VI)fuse fail, (vii) earth fault protection. (vii) LED indications For: i) AC Input, ii) Float Charging, iii) Boost Charging, iv) charge Complete, v) Battery short, vii) reverse Polarity.
Supply, Install,testing and commissioning of D.C.D.B. considering 12 nos 12 Amps 2 Pole MCB in non compartmentalized panel.
Supply, installation, commissioning and testing of 11 KV, STC- 25KA/3s, Indoor type, floor mounted 800 amp, 350 MVA, “VCB Panel Board (consisting of 02 Nos. Incoming VCB, 02 Nos Outgoing VCB & 01 No Bus Coupler)” horizontal draw out horizontal isolation floor mounting manually operated panel with 230 Volt motor mechanism & 110 V dc shunt/ close coil and other fittings & accessories including provision of inbuilt 110V power pack in each VCB with all required wiring & accessories. Internal arc: 25kA/0.1s, BIL - 12kV/28kV/75kV. 25 KA breaking capacity for 3 Sec, totally enclosed with extended copper busbar of 800 Amps for each phase metal clade , indoor extensible type flush front, horizontal isolation, horizontal draw out type with electrical and mechanical interlock and automatic safety shutter gear including pad locking arrangement, isolation plug assemble with Vacuum interrupters(OEM) with each pole individually encapsulated by epoxy insulations to make it dust proof and self-aligning finger type isolation contacts, truck having integral racking with necessary interlocks ( for insertion and removing of VCB) manual and automatic motor charge independent closing / tripping spring, trip free operating mechanism with closing and tripping push battens and mechanical breaker interconnected with HT sleeve, copper bus bur of 800 Amps including all prospection , indication , operation, monitoring and control and accessories as per specification given below .
S&F pin type,porcelain,vitreous,white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nuts ,150 mm hight,300 mm dia for 33000 volts.
Supply, Install,testing and commissioning A.C.D.B. considering 12
Supply and fix UPS with SMF Battery 12V 26 AH- 6 Nos, single phase AC input 160 to 260 V and out put 230 ± 1% of capacity 2 KVA for illumination of Sub-Station building
Each Set
M&L for fixing the polycarbonate body cable junction boxes of size 155 x 210 x 92 mm, with five wayaluminium connector (Heavy duty) terminals for 10 - 16 sq mm, 1100V cable, IP 66, weather proof, outdoor installation type with threaded cable glands & pole mounting brackets with one SP MCB 6 Amps etc complete all as specified & directed. Make- Hensel / OBO
Supply and fixing all in one comprising of high efficiency LEDs (120 lm/W), solar street Light with luminaire wattage 24/25W, High Efficiency Mono Crystalline Solar PV Module 12V 50W, lithium Ferro phosphate battery 12.8V 24Ah with inbuilt BMS technology, high efficiency LED >93%, MPPT solar charge controller and aluminium extruded body, specially designed intelligent microwave sensor to control the dimming nad brightness of light leads to extend working time and 5 mtr long octagonal pole (type CPT-5030) top dia 70 mm bottom dia 130 mm sheet thickness 3 mm including base plate of size (L x B x T) 200 x 200 x 12 mm, bolt size 4 x 16 mm dia and bolt length 450 mm, Note:-Suitable Excavation work and PCC work as recommended by manufacturer shall be included in the quoted rate all as directed and specified by Engr-in Charge. Make: Havells/Wipro/Surya/Orient or equivalent make specified in CA.
Supply, install, testing and commissioning of transformer step down copper wound 33 KV/0.433 KV ONAN incl std fittings and off load changeover +7.5% to -7.5% @ 2.5% per step with vector group Dyn-11, outdoor type 63 KVA as per EEL-2 of IS: 1180-2014 with amd no. 1,2,3 &4 formerly EEL-3 (till 30.03.2022) incl fixing arrangement
Supply, laying & testing XLPE insulated, PVC sheathed cable Un armoured, electric control cables (Heavy duty) with stranded copper conductor of size 2.5 sq mm, 4 core, 1100 Volts grade.
Supply, laying & testing XLPE insulated, PVC sheathed cable un-armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm, 8 core, 1100 Volts grade.
Supply, laying & testing XLPE insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 2.5 sq mm, 4 core, 1100 Volts grade.
Supply, laying & testing XLPE insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm, 8 core, 1100 Volts grade.
M&L for cable route indicator made out of Plain cement concrete of 1:2:4 type B1, of size 15 cm x 15cm x 15 cm, with one end of angle iron of size 25mm x 25 mm x 4 mm duly embedded in cement concrete and the other end of angle iron duly welded with chequered ms plate of 120 mm dia engraved with "MES HT Cable", angle iron of approx lenght 45 cm, complete all as specified and all as directed for HT Cable route indicator.
M&L for LLDPE septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc. complete for 25 ursers including necessary fitting and fixtures.
M&L for Soak well size 1.8m dia x 3.0m deep effective depth of excavation in any type of soil foundation in PCC 1:3:6, wall of honey combed masonary with topping of M-25 concrete, including intercepting chamber, screen chamber made up of brick work in CM, RCC cover slab in M-25/SFRC cover inter connecting pipe of RCC/DWC complete filled with brick bats of suitable size complete.
Supply and fixing for mild steel galvanised chain link fencing 3.15 mm dia of mesh wire and mesh opeing size 100 x 100mm with straining bolts, 10 mm dia round bars binding with 0.9mm dia MS binding wire, flat iron fillets ( for securing wire mesh etc. ), binding and jointing complete including necessary drilling, bolting or revetting etc. complete all as specified and as directed. Note:- Flat iron, round bars, nut bolts, and waashers etc, shall be measured as supply only and paid seperately.
S&F super razor punched barp tap (SRPBT) Aluminium based helix coil with and including necessary GI fixing clips for securing complete all as specified and directed with following specifications:- (i)Dia of coil (when unstreched) - 610mm (ii)Nos of circles - 51 turns per coil (iii)Weight of each coil with hessian pack 8.50 Kg + .50Kg (iv)Coverage per Oil - 8Rm (v) Central core wire as per IS -4454 galvanised as per IS-2629 (vi)Razor punched strip :- Razor punched tape in CONSEC-ZAL steel comprising of ALuminium base with zinc alloy coating @ 150gm/sqm confirming to ASTM A-792/A-792/m with additional primer treatment of Epoxy/Polyurethene & final Paint Top coat of caulified green shade (BSL 139) by hot Dipping process.
VCBs and Allied Works
Supply, Installation, Testing and Commissioning of 11 KV 800 Amp, 26.3 KA VCB (1 Incommer + 1 Bus cuplor and 2 Outgoing unit indoor type VCB Panels retrofitting retrofit enclosed in IP 4X made out from 2 mm thick CRCA steel enclosure with RAL 7032 powder coating complete with the following specifications all as specified and directed by Engr in charge:-
(i) CT Ratio :300/1 A,Core I CL 1.0 with 15 VA burden for metering, Core II CL 5P 10 With 15 VA burden for Protection. (ii) 11 KV Epoxy Resin Cast Potential Transformer Ratio : 11/ √3 KV/110/ √3V, 3 Phase, Winding-1: CL 0.5 with 50 VA burden for metering & Winding-2: 3P, 50VA Burdenfor Protection. (iii) Motorised mechanism with motor operating voltage 230 V AC - 01 No (iv) Mechanical ON OF spring charge/disc trip circuit healthy indication - 01 No (v) Heater 80W with switch - 01 No (vi) Panel illumination lamp with door switch - 01 No (vii) Operation counter - 01 No (viii) OVF: 1.2 continuous, 1.9 for 8 hours. (ix) Mechanical cable inter lock on door - 01 Lock. (x) Pistol Grip TNC Switch -01 No (xi) Socket with switch (230V AC 15 Amps) - 01 No (xii) Earthing terminals - 02 Nos (xiii) Continious rated Closing and tripping coil with rated voltage 110 volt DC- 1 set (xiv) Mechanical endurance test-M2 and Electrical Eudurance capacity E2 (a) Multifunction meter, Digital type (Displaying V,PF,Hz,KVA,KW,KVAR,KWh,KVARh etc) Class 0.5 with RS 485 port for commuinication of Modbus protocol Make : L&T, Conzerve. (b) SCADA compatible Relay IDMT four pole 3 O/C + 1 E/F WITH iNSTANTENEOUS OVER CURRENT AND EARTH FAULT PROTECTION Relay -01 NOS . Make: Make Schneider model MiCOM P-111 / GE P-42 for INcoming and ougoing VCB /equivalent in ABB /Schneider/ Siemens/CG. (c) annuiceator complete with showing type of fault , accept/reset button with minimum 12 windows and suitable for auxiliary supply voltage 110 volt. (d) High Speed Master Trip Relay – 1 No . ABB /Schneider/ Siemens/CG. (e) Trip Circuit Supervision Relay (VAX) – 1 No ABB /Schneider/ Siemens/CG. (f) Digital independent Volt meter and a
Material and labour for dismentling of existing old unserviceable VCBs (04 VCBs and 01 Bus Cuplor) from 33 KV MRS and deposited to MES store yard for further their disposal and reassemble the existing VCBs with new ones complete with necessary wiring work and setting up togethers all as specified and directed by Engr in charge.
Supply and fixing of Power pack 230VAC/(110)VDC, 10AH,2x12VDC battery based sourced from auxiliary supply, backup ability to serve tripping & closing coil (multiple trip close) and supply to spring charging motor complete all as specified and directed by Engrineer in charge. (Note : Rate for necessary wiring to be included the quoted rates.)
Material and labour for providing Chemical Earthing complete with copper earth plate electrode of size 900 mm x 600 mm x 5 mm thick buried in ground vertically to a depth not less than 5 mtr below ground level with top edge of plate at a depth not less than 4.25 mtr below normal ground level with a bottom layer of MGSO4 of 10cm thick, earth plate surrounded with graphite powder, vegetable soil mixture, charcol and common salt in equal proportion around and 15 cm above the plate and 10 cm thick MGSO4 as top layer and the remaining portion filled with excavated earth and connected with copper strip 32mm x 6 mm duly brazed and by means of bolts, nuts & washers up to 7.5 mtr length and connected to earthing test point, GI pipe (light grade) 20 mm bore for watering with funnel and wire mesh, GI protection pipe(light grade) 40 mm bore all as shown in Elect Plate No.3 of MES Sch Part- I and as specified and testing on completion including provn of earth pit with necessary earth work, PCC (1:2:4) type B1chamber, Cast Iron frame with hinged pit cover of size 12 inches x 12 inches having 7 kg weight all as specified and as directed.
Supply and fix disc type insulator vitreous 145 mm high and 255 mm dia ball and socket type white /brown 70 kn "four in one series" assembly for tension with clamps for conductor suitable for 33 000 volt working pressure complete all as specified and as directed.
Supply and fix PG clamp suitable for DOG/otter ACSR)
S&F Fire Extinguisher portable Carbon dioxide 4.5 KG ISI Marked
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.46 MB
Tendernotice_2.pdf
PDF • 0.31 MB
3-10.pdf
Tender Documents • 1.00 MB
5-10.pdf
Additional Documents • 0.91 MB
6-10.pdf
Additional Documents • 0.70 MB
7-10.pdf
Additional Documents • 0.79 MB
8-10.pdf
Additional Documents • 0.63 MB
9-10.pdf
Additional Documents • 0.65 MB
10-10.pdf
Additional Documents • 0.84 MB
LD.pdf
Additional Documents • 0.75 MB
2-10.pdf
Additional Documents • 0.64 MB
4-10.pdf
Additional Documents • 0.59 MB
9083tender.pdf
Tender Documents • 2.47 MB
1-10.pdf
Additional Documents • 0.75 MB
BOQ_832901.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .