Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.3 LAccepted-AOC 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹28.5 L+₹17,899 (0.63%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹28.9 L+₹57,857 (2.04%)Rejected-Finance NEAR MES FILTER PLANT SANGOOR UDHAMPUR J K 182101 | UDHAMPUR | UDHAMPUR | J K | 182101 | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | L4₹29.4 L+₹1.1 L (3.92%)Rejected-Finance 53 HOUSING BOARD COLONY PHASE II UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
20 Aug 2022, 6:00 pmClosed
Sh A K Dubey IDSE SE CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
PROVN OF 250 KVA TRANSFORMER FOR UTILITY SERVICES NEAR MPH UNDER GE (UTILITIES) UDHAMPUR
2022_MES_541094_1
CWE/U(U)-54/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
UDHAMPUR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹58,000
17 Sept 2022
26 Jul 2022
22 Aug 2022
26 Jul 2022
20 Aug 2022
8 Aug 2022
Amount
Supply, installatio. Testing commissioning of oil cooled copper wound step down BIS marked & BEE 2 star labelled" transformer of capacity 250 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433 V 3, phase 4 wire , 50 C/S oil immerse, naturally coooled externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433 V with tapping at +-/2.5% to +- 5% & +- 7.5% on HV side and to be changed by means of hand operated off load tap changing gear including first filling of new transformer oil of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland. Silica gel, breather, oil level indicator gauge drain out valve ( oil tank) exhaust vent air release valve temp gauge, cast iron wheel et comply with EEL-3 IS 1180-2014 with amendment 1,2&3 vaild till 30.03.2022 having total losses @ 50% load 920 W & total losses@100% load 2700 W. Following items/ Accessories included in this rate therefore no any extra cost will be paid for this items complete as in repairs and deposited to MES store complete all as specifie and directed by Engr-inCharge. (i) Name, rating & diagram plate (ii) Off circuit tap changing switch (iii) Earthing terminals (iv) Lifting lugs (v) Oil drain valve with plug (vi) Oil filter valve with plug (vii) Conservator with oil filling hole (viii) Thermometer pocket ix) Air release plug (x) Silicagel breather (xi) Removable inspection opening (xii) Explosion vent
Srl item No 01 Contd … Note : a) Construction of plinth/platform for transformer 2 mtr height x 2.5 mtr width x 2.5 mtr length including morum filling and PCC at top 10cm thick (1:2:4) and PCC foundation with 1:4:8(80cm width x 2.7 mtr length in square foundation 25cm geight all as per drawing provided by the department including plastering to exposed walls and white wash. Providing MS Channel on top of size 75x40x8 mm of 1.5 mtr in lenght for rolling to transformer including chain link fencing of wire mesh 150x 100 size made out of GI Wire of height 1.5 mtr fixed with the help of MS Strip 25x6 mm and including MS angle 75x45x6mm thick nos post by means of drilling holes at the distance of 30com and fixed with the help of suitable nut, bolt and washer. The length of the MS angle iron not less than 2.25mtr , top of the pad to the shape of 60degree including 3 nos for inserting barbed wire including 03 runs of barbed wire and including provision of gate of size 1.5mx 0.9mtr made out of MS angle iron 50x 50x6 mm and MS bar 12 mm dia for meshing the gate and locking arrangements including PCC goundation 1:2:4 type B-1 for posts complete all as specified and directed b) Necessary chain link fencing required around Stabiliser/ Transformer are inclusive of above price.Provision of 4 no rubber mats Synthetic 2mx1mx0.5m at near the surfaces of Plint of transformer Note: Pre -commisioning, inspection of transformer shall be carried out by rep of Accepting offr and T&P for the inspection shall be arrange by contractor, cost of the T&P etc for testing shall deemed to be included in the unit rate.
Supply installed , testing and commissioning and testing factory made and tested CPRI type test certified ) LT feeder pillar box ( KIOSK ) out Each door type , floor mounted , compertmantalised suitable for 415 Volts 3 phase 4 wire , 50 Hz AC supply system , dust and vermin proof made of 3.15mm CRCA MS sheet with digital Volt meter Ammeter with CTS Led lamps RYB for all incomers & outgoings base frame of 50x50x6mm angle iron powder coated , having front and rear openeable hinged double door shutters with aprons for cable entry and Steel handle proper locking arrangement e.g godreg double locking system with three nos of keys complete including taking down old U/S LT panel/ busbar with following:- Incoming:- ( a ) MCCB 400 amps , 4 pole. 50Hz .415 V with rupturing capacity 35/36 KA - 01 No L&T / Scineiders / C&S / ABB or Equivelent ( b ) Bus bar electrolytic grade copper 600 amps 4 pole and supported on Non - hygroscopic , non carbonising , corrosion resistance SMC insulators not less than 1 Mtr long mounted on insulators for incomming supply 01 No. Outgoing:- ( a ) MCCB 125 amps , 4 pole 25 KA with adjustable thermal over load release 50 Hz , 415 volts grade 01 Nos . (b) On load change over switch 125 Amps, 4 pole. 25 KA with adjustable thermal over load release 50 Hz , 415 volts grade - 01 Nos (c) MCCB 100 amps , 4 pole , 25 KA with adjustable thermal over load release 50 Hz , 415 volts grade -05 Nos Note- (i) Rate quoted is deemed to be inclusive of PCC foundation / pedestrian and connected earth work. (ii ) Panels shall be placed above 0.6 mtr of ground level (iii ) Outgoing MCCBS shall be fed with solid busbar connectors. ( iv ) Cables shall be terminated using gun metal / SS glands. (v) cable glands for incoming LT cable 240 sqmm - 1 Nos and out going cables 185 sqmm -01 Nos and 95 sqmm - 02 Nos is deemed to be included in quoted rates.
All as above items No - 03 above but following capacity for Incoming:- (a) MCCB 100 amps, 4 pole, 25KA, 50Hz ,415 V with rupturing capacity 35/36 KA-01 No L&T /Scineiders/C&S/ABB or Equivelent. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole - 01 set Outgoing:- ( a ) MCB DB metal clad four pole enclosure, Each- 04 Nos Note- (i) Rate quoted is deemed to be inclusive of PCC foundation / pedestal and connected earth work (ii) Panels shall be placed above 0.6 mtr from ground level (iii) Outgoing MCCBS shall be fed with solid busbar connectors and ( iv ) Cabics shall be terminated using gun metal / SS glands . (v) including suitable thimbles / lugs , nut bolts washers fitted the cables (vi) cable glands for incoming LT cable 185 sqmm - 01 Nos and out going cables 50 sqmm - 02 Nos and 35 sqmm 02 Nos is deemed to be included in quoted rates.
S&F Factory made sheet metal enclouser (junction box) made out of 14 SWG CRCA sheet powder coated weather proof outdoor type with 60 cm long legs 4 Nos made out of 40X40X6 mm equal angle size of enclosure not less than 75X60X30 cm depth with front and rear openable double door with locking arrangement including 4 strip aluminium bus bar of rating 400 amps suitable of one incoming and 5 outgoing feeders, mounted on insulators including disconnection of cable from the burnt bus bar and reconnection of cable from the burnt bus bar and reconnection in the new chamber with nuts and bolts including lugs of suitable sizes, necessary earth work and PCC foundation for grouting of four legs all as per existing Including taking down old bus bar complete all as specified and directed by Engr-in-Charge. Note: Glands shall be provided for LT cable (incomming & outgoing) all as specified and directed by Engr-in-Charge.
MCB TPN, 63 Amps, 415 Volts, rupturing capacity 10 KA "B" Series including providing aluminuium thimbles for outgoing cable, complete all as specified and as directed by Engr-in-Charge.
S&F MCB DB Metal clad four pole Enclouser, complete all as specified and as directed by Engr-in-Charge.
Supply & fix for XLPE insulated, armoured, aluminium conductor cable, 11000 volts grade, heavy duty, cross sectional area 95 sq mm ,3 core, laid in trenches/ducts/through pipe complete all as specified and as directed by Engr-in-Charge.
Supply and Laying and fixing in replacement of along the poles or passing through pipes or laid under floor of through walls etc jointing and testing LT Cross Linked Polythene Insulated (XLPE insulated) galvanized steel strip armoured electric cable 1100 volt grade heavy duty ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area as under including taking out old UNSV LT cables:- (Note : Excavation, earthwork, Pipe for cable protection to be measured and paid for separately)
16 Sqmm 4 core.
25 Sqmm 3.5 core.
50 Sqmm 3.5 core.
95 Sqmm 3.5 core.
120 Sqmm 3.5 core.
185 Sqmm 3.5 core.
M & L for providing earthing with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 25 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity. Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge
Supply and fixing Route indicator 750X200X200mm with slant embosed facing including earth work and grouting 600mm below ground level, complete all as specified and as directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete, all as specified and directed by Engr-in-Charge.
Supply and fix cable jointing kit for 11KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and acessories suitable for 3 core XLPE armoured aluminium conductor cable 95 sq.mm, complete, all as specified and directed by Engr-in-Charge.
Supply and fixing of danger notice plate board of size 250 mm x 200mm for HT 11000 volts system made of 1.6 mm thick mild steel sheet , vitreous enamelled white , with letters, in english hindi or urdu and conventional skull and bones in signal red colour and fixed with MS clamps ,bolts,nuts of approved size, complete all as specified and as directed by Engr-in-Charge.
Supply and fixing Steel tubular swaged pole erected to truly vertical or planted as strut complete with 6 mm thick MS Base plate,welded to pole,finial taper cap, bolts, nuts, screws, 11 Mtr long, type 410 SP - 55,including drilling of holes of required size for fixing of cross arms,painting the exposed surfaces of pole with two coats of aluminium paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the portion embedded in concrete, and marking pole no. with black paint at suitable height all as specified and directed by Engineer-in-Charge.Note:- The earthwork, PCC foundation, steel clamps, MS Cross arms & bracing of angle iron etc will be measured and paid separately under relevant items of Sch ‘A’
Supply and Fix lightning arresters expulsion type complete with all fittings suitable for 11000 volts grade conforming to IS-3070 part-I, transmission class, discharge capacity 65 kilo amp, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing Air break gang operated switches 12 instulators type with drop out fuses assembly mounted on MS Channel with operating mechanism works from ground level suitable for 11000 volts, 200 Amps, including Gl pipe handle, clamps bolls, nuts, jumper wire connecting with stranded conductors with locking arrangement, complete all as specified and as directed by Engr-in-Charge.
Plain cement concrete 1:3:6 type C-2 using 40mm graded crushed stone aggregates as in foundation, filling and mass concrete, complete all as specified and as directed by Engr-in-Charge.
Plain cement concrete 1:2:4 type B-1 (using 20 mm graded stone aggregate) for coping of poles, complete all as specified and directed by Engr-in-Charge.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections ( flat, angle, channel) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and as directed by Engr-in-Charge.
S&F double walled corrugated (DWC) pipe of size 120mm including snap fit coupler conforming to IS:14930 (Pt-II)/IS-16205 Pt-II for protection of HT cable in under ground complete all as specified & directed by Engineer-in-charge.
Description all as per srl item No 21 here-in-before but of size 77mm.
Excavating in trenches, not exceeding 1.5 m wide and exceeding 1.5 m in depth; for foundation, trenches for laying of cable etc. and getting out in any type of soil, complete all as specified and as directed by Engr-in-Charge.
Description all as per Srl itemNo 23 above but depth exceeding 1.5 m and not exceeding 3.0 metre.
Returning filling in (soil) including spreading leveling watering and well ramming in layers not exceeding 25cm thick, complete all as specified and as directed by Engr-in-Charge.
Removal of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed by Engr-in-Charge.
proach associates
FANGALIA TRADERS
vijay kumar gupta and co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .