Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAdmitted-Finance 379 B FIRST FLOOR CHIRAG DELHI NEW DELHI 110017 | NEW DELHI | SOUTH DELHI | DELHI | 110017 | ₹1.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.2 Cr+₹5.4 L (4.75%)Admitted-Finance | ₹1.2 Cr+₹5.4 L (4.75%) | L2 | Admitted-Finance |
| 3 | L3₹1.2 Cr+₹9.9 L (8.80%)Admitted-Finance 306 BAKSHI HOUSE 40 41 NEHRU PLACE NEW DELHI 110019 DELHI | SOUTH EAST | DELHI | 110019 | ₹1.2 Cr+₹9.9 L (8.80%) | L3 | Admitted-Finance |
| 4 | L4₹1.3 Cr+₹13.0 L (11.6%)Admitted-Finance | ₹1.3 Cr+₹13.0 L (11.6%) | L4 | Admitted-Finance |
| 5 | L5₹1.3 Cr+₹13.6 L (12.1%)Admitted-Finance | ₹1.3 Cr+₹13.6 L (12.1%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | VOLKS ENERGIE PVT LTD L3 | DY Infra & Projects Private Limited L5 | Mvac Engineers L2 | AIR DESIGN SOLUTIONS L1 | UTILITY SERVICES L4 |
|---|---|---|---|---|---|---|---|---|
| 1.00SH-A - Fire Alarm System | ||||||||
| 2.00 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the Two loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 + 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. | 1 | Each | 1,50,000 ₹1,50,000 Lowest | 1,90,000 ₹1,90,000 | 1,58,400 ₹1,58,400 | 5,37,000 ₹5,37,000 | 3,66,354 ₹3,66,354 |
| 3.00 | Supplying, installation, testing & commissioning of intelligent addressable photothermal detector complete with mounting base etc. complete as required. | 87 | Each | 1,500 ₹1,30,500 Lowest | 2,100 ₹1,82,700 | 3,370 ₹2,93,190 | 3,598 ₹3,13,026 | 3,428 ₹2,98,236 |
| 4.00 | Supplying, installation, testing & commissioning of fault isolator etc. complete with base as required. | 10 | Each | 900 ₹9,000 Lowest | 2,200 ₹22,000 | 3,370 ₹33,700 | 4,030 ₹40,300 | 2,638 ₹26,380 |
| 5.00 | Supplying, installation, testing & commissioning of addressable manual call point etc. complete as required. | 10 | Each | 2,000 ₹20,000 Lowest | 3,000 ₹30,000 | 4,030 ₹40,300 | 4,030 ₹40,300 | 2,427 ₹24,270 |
| 6.00 | Supplying, installation, testing & commissioning of addressable fire control module etc. complete as required | 6 | Each | 1,500 ₹9,000 Lowest | 2,800 ₹16,800 | 4,030 ₹24,180 | 4,579 ₹27,474 | 2,872 ₹17,232 |
| 7.00 | Supplying, installation, testing & commissioning of addressable horn cum strobe etc. complete as required. | 6 | Each | 1,500 ₹9,000 Lowest | 3,200 ₹19,200 | 3,370 ₹20,220 | 6,400 ₹38,400 | 3,378 ₹20,268 |
| 8.00 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc. as required. | 14 | Each | 100 ₹1,400 Lowest | 200 ₹2,800 | 470 ₹6,580 | 138 ₹1,932 | 543 ₹7,602 |
| 9.00 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. | 200 | Mtr | 220 ₹44,000 | 160 ₹32,000 Lowest | 220 ₹44,000 | 317 ₹63,400 | 207 ₹41,400 |
| 10.00 | Dismantling of existing 4 zone fire alarm system consist of 1 No. FACP, 85 Detector, 10 Nos. RI, 10 MCP, Hooter etc. complete including wiring and shifting of same in AAI Store. | 1 | Job | 5,000 ₹5,000 Lowest | 15,000 ₹15,000 | 19,800 ₹19,800 | 13,500 ₹13,500 | 16,805 ₹16,805 |
Tender Value
Refer Docs
EMD Value
₹4.3 L
Closing Date
19 Aug 2026, 3:00 pmClosed
SM (ENGG.-E), AAI, RHQ-NR
AIRPORTS AUTHORITY OF INDIA, RHQ-NR, 2ND FLOOR, NATS COMPLEX, NEW DELHI-110037
Renovation of terminal building SH (i) Provision of VRV/VRF system and associated Civil/Electrical works (ii) Replacement of Fire Alarm and Detection System (FADS) lighting designing for illumination and aesthetics internal EI and associated worK
2026_AAI_285406_1
AAI/RHQ-NR/E-E/RENV/BKN/2026
Open Tender
Electrical Works
Item Rate
150 days
AAI, BIKANER AIRPORT
Please refer Tender documents.
14 documents required · 14 mandatory
₹1,180
₹4.3 L
16 Sept 2026
27 Jul 2026
20 Aug 2026
28 Jul 2026
19 Aug 2026
28 Jul 2026
28 Jul 2026 - 7 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SH-A - Fire Alarm System | |||||
| 2 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the Two loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 + 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. | - | Each | 5,00,000 | - |
| 3 | Supplying, installation, testing & commissioning of intelligent addressable photothermal detector complete with mounting base etc. complete as required. | - | Each | 4,000 | - |
| 4 | Supplying, installation, testing & commissioning of fault isolator etc. complete with base as required. | - | Each | 4,000 | - |
| 5 | Supplying, installation, testing & commissioning of addressable manual call point etc. complete as required. | - | Each | 4,500 | - |
| 6 | Supplying, installation, testing & commissioning of addressable fire control module etc. complete as required | - | Each | 4,500 | - |
| 7 | Supplying, installation, testing & commissioning of addressable horn cum strobe etc. complete as required. | - | Each | 4,000 | - |
| 8 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc. as required. | - | Each | 210 | - |
| 9 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. | - | Mtr | 80 | - |
| 10 | Dismantling of existing 4 zone fire alarm system consist of 1 No. FACP, 85 Detector, 10 Nos. RI, 10 MCP, Hooter etc. complete including wiring and shifting of same in AAI Store. | - | Job | 15,000 | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.43 MB
TenderDocuments.pdf
Tender Documents • 19.34 MB
BOQ_333343.xls
BOQ • 0.37 MB
Corrigendum_1.pdf
PDF • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .