Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹29.9 L
EMD Value
₹59,770
Closing Date
24 Nov 2025, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Extension of causality Block for District Hospital Pulwama B.W.O Electric work
2025_PWDJK_294950_1
NIT No.187/2025-26 Dt/11/11/2025
Open Tender
Electrical Works
Percentage
PULWAMA
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,100
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹59,770
24 Nov 2025
12 Nov 2025
25 Nov 2025
12 Nov 2025
24 Nov 2025
12 Nov 2025
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havell/Polycab/ SSK/ Anchor/equivalent as directed by engineer incharge.) single core cable in surface / recessed (cutting the wall and making good the same in case of recessed conduit ) medium class PVC conduit/ duct( Anchor/ Polycab /Ravindra/equivalent make as directed by engineer incharge.), with modular switch ( Legrand Mylinc- Allzy /SSK NV/schneider Zencelo /Crabtree athena/ eq. make as directed by EIC.), modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. The job also includes providing and laying of circuit wiring with 3 x 2.5 sq. mm FRLS PVC insulated copper conductor ( Havells/ polycab/ Finolex/ Anchor/ eq. make) Single core cable in surface recessed medium class PVC conduit.
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor ( Havell/Polycab/SSK/ Anchor/equivalent as directed by engineer incharge.) single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm + 1X 4 sq. mm earth wire , FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/Anchor /eq. make to be approved by EIC ) single core cable in surface/recessed (cutting the wall and making good the same in case of recessed conduit ) medium class PVC conduit ( Anchor/ Polycab /Ravindra/equivalent make as directed by engineer incharge.)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. Modular Switch & Socket:- ( Legrand Mylinc-Allzy /SSK NV/schneider Zencelo /Crabtree athena / eq. make to be approved byEIC.)
Wiring for 6- 10 amp power plug with 2X2.5 sq. mm FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/Anchor / eq. make to be approved by EIC ) single core cable in surface/recessed (cutting the wall and making good the same in case of recessed conduit ) medium class PVC conduit ( Anchor/ Polycab /Ravindra/equivalent make as directed by engineer incharge.) alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- ( Legrand Mylinc-Allzy /SSK NV/schneider Zencelo /Crabtree athena / eq. make to be approved by EIC.)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. For AC's
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/Anchor make/ equivalent make as directed by engineer incharge.), single core cable in surface/ recessed (cutting the wall and making good the same in case of recessed conduit ) medium class PVC conduit as required.
(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
(d)2 X 6 sq. mm + 1 X 6 sq. mm earth wire
( b )4 X 10 sq. mm + 2 X 6 sq. mm earth wire
(f) 4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make as directed by EIC )along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, complete
Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes
S/F testing and comm. Of 36 W + 4 ft. wall mounted LED batten with powdered coated aluminum housing & integrated electronic driver with minimum system lumen efficacy of 100 lm/W with THD<10%.( commercial series) CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/ Trulux /Wipro/ eq. make. sample to be approved before installation..
AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of three years ,which includes replacement of fixtures of Philips/ Trulux /Wipro/ eq. make. sample to be approved before installation..
Supply installation testing and comm. of flood light 100 W ( warm, white ), Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ Havell /Wipro/Crompton / eq. make to be approved by EIC. the job also includes the angle iron stand of suitable size to be grouted in cement concrete with hold fasteners complete job.
Supply installation testing and comm. Of 250mm sweep exhaust fan Shutter type of havell /USHA/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 No. Aluminium blades, 30 cm long down rod, 2nos. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, and including iron hook complete . USHA Striker/Havells Oyster matalic/Crompton aura/equivalent make as directed by engineer incharge.
Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate Anchor roma plus/Legrand Mylinc /SSK NV/schneider Zencelo /Havell Coral / eq. make to be approved by EIC.
SITC of wall fan 400 mm sweep as approved by EIC ,240v,50 Hz complete , etc. as required. Make(Usha /Orient/Crompton/ Havells/ eq. make to be approved by EIC
Sub Head-3 - Distribution system
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board,( legrand/ Scheinider/Hager / eq. make to be approved by EIC) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)
4 way, Double door ( 12+4)
8 way, Double door ( 24+4)
Supplying and fixing of following rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. legrand / Schinider/ L&T ./equivalent make as directed by engineer incharge.
a) 6-32 Amp SP MCB
b) 40-63amp DP MCB
c) 40-63amp TPN MCB
Providing of Chemical earthing as per IS standards by way of digging 10' deep pit then embedding 3 meter G.I Earthing electrode , 80mm dia. connecting the plate with main control board by8- 10 SWG G.I wire with 1/2" dia. Full thread brass nut and bolt and washers. Refilling of pit with chemical compound.
S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
c)120 sq.mm 3.5 core
c)70 sq.mm 3.5 core
Earth work excavation for cable trench, 2 ft deep with an average breadth of 1.5ft and refilling of trench with excavated earth after laying of cable and ramming it properly excluding cost of cable.the job also includes laying of warning tape .
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
160 mm dia (OD-160 mm & ID-135 mm nominal)
Design, Fabrication, Supplying, Installation, Testing and Commissioning of Cubical type LT panel Board ( outdoor type) suitable for 415 V 3 Phase 4 wire 50 HZ AC supply system, duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required and as per the following discription ( IP-42).( As per approved design,size may vary as per site requirement)
Normal INCOMING:
a)200A 4P MCCB 25 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC. 1 No.
b) 4 No. of Aluminium Bus Bar of 400 Amp. 1 Set
c)Digital meters and phase indicators -1 set.
d) onload Change over switch 160 Amp for generator.Front operated. 1 No.
e) 4 No. of Aluminium Bus Bar of 200 Amp. 1 set
c)Digital meters and phase indicators -1 set.
Inverter Incommer
(a) 100 amp DP MCCB 16 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC.
(b) 200 Amp 2 strip bus bar
c)Digital meters and phase indicators -1 set.
OUTGOING:
c) 40-63amp DP MCB 10 K Legrand/ Shinider/Semiens/ABB / eq. make to be approved by EIC. 8 No.
c) space for 24 way MCB's
Supplying,Installation,Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical
S/I testing and comm. Of three phase ( Outdoor type) 60 KVA 50HZ oil cooled(Transformer oil is to be provided with stabilizer conforming to IS 335,IEC296)) unbalanced type servo voltage stabilizer(A.E / Cosco/Chinar/ Electricfield / eq. make to be approved by EIC) having an input voltage ranging from 156V to 415 V ( phase to phase) and balanced output voltage of 415V, +/- 1%. ( Test certificate to be provided by the manufacturer) The unit incorporate
b) A three phase change over switch to read voltage on incoming and output side
c) indicating lights 6 No two numbers for each of the motorised units, one for lower limit and other for higher limit.
e) Single phase Preventer ( contactor Switch of required rating) Legrand make.
f) six potential meter resistance with lock meter two for each phase control, one for sensitivity and other for level control.
g) two sets of indication lamps three numbers each to indicate output and input indication
h) 20 % over load bearing capacity for one hour.
Supply installation testing and comm.of invertor battery 150 AH/12 V Exide invatubular/ equivalent make.
Supply installation testing and commissioning of Sine Wave Inverter Capacity 3.5 KVA, Rated Power 2940 W,Supports Four battery,24 Month Warranty Safe for sensitive appliances with Sine wave out-put, Inverter should run heavy loads like AC, Geyser, Photocopiers, Auto over-load handling capacity Installation and maintenance friendly Offers high quality and reliable power back-up solution for office and homes ,MCB for protection from Input mains,Bypass switch for supplying output directly from grid in case of Home UPS fault.Noiseless Operations with the help of low harmonic distortion, Intuitive Display to easily understand status of mains availability, battery status, etc.Comprehensive protection against short-circuit, reverse polarity, battery over-charge, deep-discharge etc.Adaptive Battery charging control system technology (ABCC) ensures faster battery charging and enhances battery life by around 70%.Supports a wide battery range, i.e. Flat Plate, Tubular & VRLA (SMF).praffered make Luminous/ Microtek/Exide/ eq. make to be approved by EIC
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.06 MB
BOQ_954406.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .