Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹32.9 L+₹1.5 L (4.67%)Rejected-AOC HYDERPORA NEAR ELLAQUAI DEHATI BANK SRINAGAR KASHMIR J K 190014 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190014 | L2 | Rejected-AOC Other than L1 | |
| 3 | L3₹33.5 L+₹2.0 L (6.50%)Rejected-AOC NEAR MES FILTER PLANT SANGOOR UDHAMPUR J K 182101 | UDHAMPUR | UDHAMPUR | J K | 182101 | L3 | Rejected-AOC Other than L1 | |
| 4 | L4₹42.9 L+₹11.5 L (36.5%)Rejected-AOC 278 BALMIKI MOHALLA BURAIL SECTOR 45 CHANDIGARH CHANDIGARH CHANDIGARH 160047 INDIA | CHANDIGARH | CHANDIGARH | 160047 | L4 | Rejected-AOC Other than L1 |
Tender Value
₹31.5 L
EMD Value
₹63,020
Closing Date
3 Sept 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Maj Devdutt deshpande
GARRISON ENGINEER (AF) THOISE 19 FBSU, c/o 56 APO, PIN 937219
PROVN OF 82.5KVA DG SETS AND CONNECTED ACCESSORIES FOR PRE-FAB SHELTER AT BASE CAMP UNDER GE (AF) THOISE
2024_MES_648423_3
GEAF/T-08/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF THOISE
As per tender documents
7 documents required · 7 mandatory
₹500
GE AF THOISE
₹63,020
Yes
12 Dec 2024
8 Jul 2024
5 Sept 2024
8 Jul 2024
3 Sept 2024
15 Jul 2024
Amount
Supply,install ,testing, commissioning of 'Silent type' Prime duty with continuous operation diesel generating set alongwith having prime power rating of 82.5 KVA (66KW)at NTP, 415 Volt, 75 db noise level at 1 mtr distance from DG Set with suitable Engine to develope 82.5 KVA, AC 415 Volt at 1500RPM , 0.8 lagging power factor at 415 volts suitable for 50 hz 3 phase system and ,confirming to CPCB-IV norms / latest CPCB , acoustic enclosure, anti vibration mountings, control panel and foundation.The DG set should be robust in construction factory tested and assembled to ensure perfect alignment of Engine and Alternator on a common base frame with same manufacturer. The DG set shall be comprising of following items as under:
Diesel Engine : The diesel engine shall be of four stroke cycle multi-cylinder,direct injection, water cooled, turbo charged with after cooler, Air to air aftercooling and optimised turbocharger for increased altitude capabilities, developing suitable BHP @ 1500 RPM under tropical condition of Thoise of BS 5514/ISO 3046 with an over load capacity of 110% for one hour in any specified 12 hrs of continuous operation,sThe engine shall confirm to IS:10000/BS:649/BS 5514.The engine shall have the following accessories: -(i) Cooling fan and radiator. (ii) DM water cooling systems with pre-mix anti-corrosive additive. (iii) Turbocharger. (iv) Fly wheel with fly wheel housing. (v) Electrical engine starter motor (disengagement after start-up) with Batteries. (vi) Battery charging systems. . (vii) Thermal sealing of exhaust pipe and aluminium cladding for complete exhaust pipe and silencer. (viii) Required filters for fuel, lube oil, air etc. (ix) Sets of flexible hoses as required. (x) Suitable coupling to Alternator with guard. (xi) Suitable Engine controller for protection of the engine. (xii) Heavy duty air cleaner etc.
Engine protections: (i) High coolant temperature warning & trip (ii) Low lubricating oil pressure warning & trip (iii) Low coolant level warning & trip (iv) Fail to crank trip (v) High and Low speed trip (vi) Low or High battery voltage alarms. (vii) Lack of fuel (viii) Set fail to start protection after failure of the set
Governor: The governor shall be of electronic type
Exhaust : The exhaust piping system shall be optimized to meet stringent noise emission standards laid down by MoEF / CPCB-IV compliant.The exhaust line shall be extended beyond the height of the utility building roof as required by pollution control norms. Suitable supporting structure for installation shalll be provided.
Hot air exhaust (Radiator cooling): As per OEM recommendation if suffecient exhaust for radiator is not available , the contractor has to provide GI duct for hot air exhaust from DG set up to designated place of duct outlet. The duct shall be made of 14 Gauge thick including necessary civil work.
Fuel Tank : Inbuilt/internal bottom mounted (with-in DG set or with-in base frame) diesel tank of suitable capacity with mounting brackets, complete with fuel inlet, out let, air vent, drain plug, level indicator, inter connection pipes from tank to diesel generator as required. Suitable barrier shall be provided between Diesel tank and the Engine. Fuel tank shall be fabricated as per tropical condition of Thoise with approx. capacity or designed capacity shall be suitable for 8 hrs continous operation.
Starting system :The engine starting shall be by means of totally enclosed axial type electric starter suitable for12 volts DC starting system comprising of starter motor, voltage regulator and arrangement for initail exciation complete with suitable number of batteries as Per OEM Specifiaction ,Sealed Maintenance Free (SMF) Lead-Acid type .The battery shall be supplied with a suitable floor mounted MS stand treated with seven tank treatment, two coats of red oxide /primer & acid resistant paint with wooden base, adaptor box etc . with copper conductor battery leads of required length and socket/clamps
Alternator: (i) 82.5 KVA 3 phase 0.8 PF 415V, 4 wire 1500 rpm self-excited and self regulated through AVR confirming to IS :4722/BS 2613 suitbale for tropical condition with brush less exciter, housed in screen protected drip proof enclosure. The alternator shall be confirming to IS 13364 Part-2 & IS 15999 Part-1/ IEC 60034 Part-1 capable of delivering rated output at rated power factor of 0.8, with,a. Terminal voltage differing from the rated value by not more than +/- 5%. (ii). Frequency differing from the rated value by not more than +/-0.5%. (iii). Short circuit capacity of 300% for 10 seconds. (iv). Over load capacity of 110% for one hour. The insulation class of the Alternator shall be class F/ H. The temperature rise shall be limited to class B and Ingresses enclosure protection shall IP23 or better.The out put terminals of each Alternator shall be connected to an MCCB of suitable capacity through a cable system. The control Panel shall be housed inside the acoustic enclosure.
Alternator Protection: Alternator should have following protections: - (i) Over and Under voltage (ii) Under and Over frequency warning and trip (iii) Loss of excitation (iv) Over current and Earth Fault and Short Circuit Protection (v) Unbalanced loads
Acoustic enclousure : The acoustic enclosure should be supplied along with DG set from the manufacturer outlet itself as per latest CPCB norm.Acoustic enclosure shall be of powder coated and fabricated out CRCA MS sheet. The canopy shall have hinged doors, one door with glass window to view proper parameters on the control panel. The canopy and doors shall have inside lining of fire retardant foam/glasswool as acoustic materials. The base frame shall be fabricated in ISMC channel or in sheet metal, with lifting hooks for convenient lifting of complete set i.e. along with canopy, engine and alternator. The sound level shall have less than 75 db (A) at a distance of 1 meter.High quality noise absorbant and fire-retardant grade acoustic Insulation material (P.U. Foam) complying to IS 8183. The allowable temperature raise inside the canopy is 5 to 7 deg. Centigrade. The Measurement of noise should be as per ISO 3744/ ISO 8528 (Part 10) standard.The canopy has the provision of emergency push button, external to the canopy. Note : The acoustic enclosure shall be made by the OEM of original engine Manufacturer.
Note : (i) The Gen set must be affixed with label meeting the following requirement (The lable shall be durable and legible) (ii) Name and address of the engine manufacturer. (iii)Certificate that this engine conforms to the CPCB IV emission norms shall be provided (iv) Type and approval certificate number. (v) Date of manufacturing of Gen set. (vi) The complete DG Set including Engine / Alternator shall be factory assembled by manufactured or its authorizes dealer as approved for assembling of the DG set. A certificate in this connection shall be submitted to the GE. (vii) Anything missed out above but technically required for efficient working of DG set is deemed to be including in quoted rates. (viii) The quoted rate shall be deemed to be inclusive of first fill of engine oil (ix) The quoted rate shall be deemed to be inclusive of minimum 12 hours test run at site as specified in PS in presence of IEM/ rep of accepting officer, all testing arrangements / equipments for water load test/ suitable strip heater load shall be made available by the contractor for tests. POL shall be arranged by contractor for testing and cost deemed to be included in quoted rate.
(x) The contractor shall arrange load / resistive load / water load for testing for final testing of DG set at site and the cost is deemed to be included in quoted rate. (xi) DG set should be sound proof as per latest policy/ latest CPCB Norms. (xii) Drawing for Plinth of DG Set shall be provided by OEM and approved by GE. (Xiii) The DG set shall be suitable for operation in high altitude and in climatic conditions prevalent in Thoise, Ladakh. (xiv) The cost of Civil/Foundation as per OEM specification is deemed to be included in Item Rate
Excavation in trenches n.exc. 1.5 mtr wide and n.exc 1.5 mtr deep for foundations of poles/stays/cable etc not exc 10 Sqm area on plan and getting out in Hard/Dense soil complete all as specifed and as directed by Engineer-in-Charge.
Returning filling in including spreading levelling, watering and well ramming in layer each not exc. 25 cm thick in a soft/loose soil complete all as specified and directed by Enginer-in-Charge.
Removing surplus soil to a distance not exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other complete all as specified and directed. Note:-Excavation and earth work to be measured and paid for separately
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge. Note: Punned thickness shall be measured.
M&L for in repair / replacment XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 50 Sqmm,3.5-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed.
Supply, installation, testing and commissioning of electric LT Feeder Pillar Box, Outdoor, cubical type, Pedestal mounted, factory made, CPRI approved,Copper Bus Bar 400 Amps fabricated out of 3.15mm thick mild steel sheet mounted on frame of mild steel angle iron 50x50x6mm . The panel shall be be damp,dust and vernim proof and shall be suitable for climatic condition of the station. All incoming and outgiong cable entries shall be from the bottom .Removable undrilled gland plates shall be itted or cable entry. The dimensions of panel shall be as onrequired bai for incorporating the electrical accessories/switchgear a specified.The front and back side of the feeder pillar box shall be provided with hinged double door with locking arrangement.The busbar shall be supported at regular intervals using RP,SMC or DMC insulatiors. The feeder pillar box shall be provided with Danger Plate in front and back.The feeder pillar to be fabricated comprising the following:- Make as per CPRI Approved Inccoming:- (a) Change Over Switch 200 Amps -03 Nos (b) MCCB, four pole, 125 Amps, 415 Volts, adjustable type, with breaking capacity 35 KA- 04 No (c) MFn Meter V, A, F, PF etc Make L&T , Equivelent in Seimns and Schinider -01 No Outgoing (i) MCCB 4 pole 415 Volts of capacity 63 amps thermal magnetic release adjustable type of breaking capacity 25 KA-03 No (Outgoing) (ii) MCB TPN 4 pole 415 Volts of capacity 32 amps thermal magnetic release adjustable type of breaking capacity 25 KA-01 No (Outgoing) (iii) MCB SPN 32 Amps 240 Volts -02 No
Earthing complete with copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
M/S ZAHOOR AHMAD KHAN (BID ID -3079543)
FANGALIA TRADERS (BID ID -3063713)
Dharm Singh Contractor (BID ID -3068697)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .