| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-AOC | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹9.9 L+₹2.6 L (36.0%)Rejected-Finance | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹10.2 L+₹2.9 L (39.5%)Rejected-Finance | L3 | Rejected-Finance Not being lowest | |
| 4 | L4₹10.4 L+₹3.1 L (42.9%)Rejected-Finance | L4 | Rejected-Finance Not being lowest | |
| 5 | L5₹11.0 L+₹3.7 L (51.2%)Rejected-Finance BOOTH NO 56 MAIN MARKET SECTOR 40 C CHANDIGARH U T 160036 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160036 | L5 | Rejected-Finance Not being lowest |
Tender Value
₹11.3 L
EMD Value
₹23,000
Closing Date
3 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) B/R Chakeri Kanpur
GE (AF) B/R Chakeri Kanpur
PROVISION OF DUMMY LOAD FOR AF NET/EXCHANGE AND PROVISION OF 5 KVA UPS/INVERTER FOR BLOOD STORAGE CABINET AT BLOOD BANK AND PHASE SEQUENCE CORRECTOR AT VARIOUS LOCATIONS AT 7 AFH KANPUR CANTT
2020_MES_368436_3
GE(AF)/CHK/T-18 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
AFH 07 Kanpur Cantt
Class E and cat b(i)
8 documents required · 8 mandatory
₹500
GE (AF) B/R Chakeri Kanpur
₹23,000
26 Nov 2020
19 Sept 2020
8 Oct 2020
19 Sept 2020
3 Oct 2020
21 Sept 2020
60 days
Amount
Supply, installation, testing and commissioning resistance/heater type 415 V, 50 Hz, 3 Phase 4 wire operational load 20 KW, 20KW, 10 KW, 10 KW, 10 KW and 5 KW air cooled as required with suitable fan as per manufacturing norms, Panel made of CRCA sheet with hanging arrangements and trolley wheel for easy conveyance for capacity 75 KVA DG Set complete all as specified and as per site requirement alongwith following accessories:- Note:- Suitable size of cable required for incoming and outgoing connections shall deemed to be included in the unit rate quoted by the Contractor in this item.
Item No 1.00 continued.. (a) MCCB 160 A, 4 Pole 36 KA-01 No (b) Digital Voltmeter- 01 No (c) Digital Ammeter- 01 No (d) Frequency meter- 01 No (e) Overlaod relay- 01 No (f) Short Circuit Protection- 01 No Note:- Suitable size of cable required for incoming and outgoing connections shall deemed to be included in the unit rate quoted by the Contractor for this item. Make- Adof Simak or equivalent make approved by GE in writting.
Supply, installation, testing and commissioning of online UPS of capacity 5 KVA three phase in and three phase out, copper wounded suitable for 415 volts, 50 Hz AC supply with battery back up system consisting of sealed maintenance free dry batteries, 15 Nos of Capacity 12 Volts, 65 AH, complete with batteries stand for mounting of batteries and connecting lead including incoming and outgoing connections with panel etc. complete all as specified and directed. ( Make: UTL/Microtek/Powerline/Legrand ) Note:- Suitable size of cable required for incoming and outgoing connections shall deemed to be included in the unit rate quoted by the Contractor in this item.
S & F three phase sequence corrector cum protection system 415/440 Volt, 50 Hz, internal working voltage 12/14 Volt, Contactor ML-12 suitable for 200 KVA/215 HP load complete with incoming and outgoing cable connections with lugs, cable glands along with MCCB TP 400 Amps in a indoor feeder pillar box of 2 mm thickness CRCA sheet factory made powder coated, mounting on bracket made out of 40 mm x 3 mm angle iron frame complete all as specified and directed.
S & F three phase sequence corrector cum protection system 415/440 Volt, 50 Hz, internal working voltage 12/14 Volt, Contactor ML-04 suitable for 75 KVA/80 HP load complete with incoming and outgoing cable connections with lugs, cable glands along with MCCB TP 150 Amps in a indoor feeder pillar box of 2 mm thickness CRCA sheet factory made powder coated, mounting on bracket made out of 40 mm x 3 mm angle iron frame complete all as specified and directed.
S & F of Phase sequence cum motor protection system 415/440 volt, 50 Hz, internal working voltage 12/14 Volt, Contactor ML-03 suitable for 50 HP capacity load for auto change of phase sequence and adjustable low and high voltage protection system to protect the machinery, mounting on bracktet made out 40x3 mm angle iron frame all control wiring, cable connections complete along with incoming MCCB 100 Amps capacity complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode 60cm x60 cm x6.0 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m below normal ground level connected to galvanized earth lead aluminium strip of size 32 mm x 6 mm and 7.5 m long fixed by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 connected to earthing test point as specified or indicated including testing on completion including PCC pit in PCC (1:3:6) type C-2 using 20 mm graded stone aggregates. RCC (1:2:4) Mix, reinforced with 6mm dia MS bars @ 150mm c/c RCC cover slab 40mm thick with two nos fitting handle, GI pipe 20mm dia light grade with funnel & wire mesh for watering and 40mm dia light grade GI pipe for aluminium earth strip protection etc. complete all as specified and directed.
Supply, laying and testing of XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 35 sq mm 3½ core, laid in trenches/ducts /encased in GI pipe /fixed to pole complete all as specified and directed.
Ditto all as per Item No. 7.00 above but cable size 70 sqmm 3½ core.
Ditto all as per Item No. 7.00 above but cable size 95 sqmm 3½ core.
Preetpowercontrol
G S SANDHU & CO.
SAXENA BANDHU
L-7 Primewave Communications
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .