MAJOR AJIT CHOUDHARY
GE (AF) Kalaikunda PO Kalaikunda Air Field Dist Paschim Medinipore State West Bengal Pin 721303
DAY TO DAY MAIN OF E/M SERVICES AND REPL OF ELECTRICAL FITTINGS, REWIRING AND ALLIED WORKS AT DOMESTIC AREA AND REP/MAINT OF STREET, SOLAR, FLOOD, HIGH MAST EXTR LIGHTING AND ALLIED WORKS AT TECH AREA AND DDK RANGE AT AFK KKD UNDER GE (AF) KKD
2023_MES_596153_1
C/8869/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KALAIKUNDA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF KALAIKUNDA
₹80,000
Yes
4 Jul 2023
17 May 2023
20 Jun 2023
17 May 2023
19 Jun 2023
31 May 2023
Amount
Taking down carefully copper/ aluminium point wiring (light, fan, socket or power) complete including fittings such as switches, ceiling roses, pendent, regulators, sockets, light fittings etc, removing materials from site and making good disturbed surfaces of walls, floors etc., complete all as specified and directed.
S&F point wiring with 1.5 Sqmm FRLSH multi stranded copper conductor 1100 V grade,as per IS 694: 2010 , ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLSH cable drawn in & including PVC casing caping of 25 mm wide, with double locking type, including all accessories casing caping as approved by EIC, with PVC 1.5 mm multi stranded insulated unsheathed copper wire, ISI marked of green colour for continous earth, including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable duly painted with aluminium paint inside and anticorrosive paint out side with 2.8 mm thick bakelite hylam sheet cover, ISI marked with CM/L no. for mounting switch & sockets for the following:- Note : (i) Contractor has to make the surface good after flushing the sunken box as per existing specification without any extra cost
One light/Fan point controlled by one 5 Amps switch one way complete
One bell point controlled by one 5 Amp bell push complete
One 3 pin 5 amp switch socket combination point on independent board with other switches.
One 3 pin 5A switch socket combination point on same board with other switch.
All as per item 2.00 here in before but power point wiring with 4.0 Sqmm FRLSH multi stranded copper conductor 1100 V grade,as per IS 694: 2010, ISI marked , PVC insulated unsheathed cable & including PVC casing caping of 25 mm wide , including all accessories casing caping complete with PVC 4.0 sqmm multi stranded insulated unsheathed copper wire, ISI marked of green colour for continous earth, for industrial metal clad socket power point.complete all as specified and directed by EIC.
S&F switch piano flush type single pole,5 Amp. AC, 230 V one way complete all as specified and directed by EIC. (Note : Item to be measured if execuated under new point wiring)
S&F in repair switch piano flush type single pole,5 Amp. AC, 230 V one way complete all as specified and directed by EIC.
S&F Polycarbonate Switch socket combination 5 Amps ,2 in 1, flush type complete all as specified and directed by EIC.(Note : Item to be measured if execuated under new point wiring) .
S&F in repair Polycarbonate Switch socket combination 5 Amps ,2 in 1, flush type complete all as specified and directed by EIC.
S&F bell push flush type single pole one way, 5 Amp, AC,230V complete all as specified and directed by EIC.(Note : Item to be measured if execuated under new point wiring)
S&F in repair bell push flush type single pole one way, 5 Amp, AC,230 V complete all as specified and directed by EIC.
S&F switch socket combined outlet 2 in 1, 3 pin, flush type 5 and 15 Amp universal multi purpose complete all as specified and directed by EIC. (Note : Item to be measured if execuated under new point wiring)
S&F in repair switch socket combined outlet 2 in 1, 3 pin, flush type 5 and 15 Amp universal multi purpose including taking out old u/s complete all as specified and directed by EIC.
S&F Bell ,Ding dong type electric AC, 230V, Single phase,complete all as directed by EIC.(Note : Item to be measured if execuated under new point wiring)
S&F in repair Bell ,Ding dong type electric AC, 230V, Single phase, complete all as specified and directed by EIC.
S&F ceiling Rose, surface,bakelite 65mm polycarbonate three terminals, AC, 230 Volts complete all as specified and directed by EIC.(Note : Item to be measured if execuated under new point wiring)
S&F in repair ceiling Rose, surface,bakelite 65mm polycarbonate three terminals, AC, 230 Volts complete all as specified and directed by EIC.
Supply and Fix in repair of 3 pin plug top AC-230 v 15 Amp complete all as specified and directed.
S&F in repair plug top metal body suitable for single phase 240V,IP44 ,20A 2P with Earth Make :Hager cat no:VZ1311or equivalent of make:Legrand/ABB
S&F in repair metal socket suitable for single phase 240V,IP44 ,20A 2P with Earth, metal body Make :Hager Cat no: VZ1411or equivalent of make:Legrand/L&T
S&F LED tube lamp 20 Watt (reterofit type, T8 pattern, single/double side connection) LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 1800, lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, ATHD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours complete fitting to be fixed in existing or new batten/ patti including changing the wiring suitable for T8 LED retrofit lamp in existing tube light fitting including taking down old unserviceable complete..Make : Bajaj Cat No. BLRB 20W CW LED (retrofit LED tube lamp 18 Watt, Single end connection) or equivalent in WIPRO /PHILIPS as approved by GE.
S&F LED 20 Watt tube light fitting intregated type, including LED retrofit tube lamp 20 W , LED tube light nominal power 20 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 2100, lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 extruded aluminium LED battens life span of minimum 50000 working hours as per catalogue No Make :- Bajaj (Batten Cat No. BCLAB 20W LED P batten and tube suitable for 18/20 watt retofit LED tube single side connection type). LED or equivalent in Wipro/Philips as approved by GE complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting including taking down old unserviceable complete all as specified & directed. . Note : Make of batten and LED tube lamp should be of same make.
S&F LED 20 Watt tube light fitting intregated type, including LED retrofit tube lamp 20 W , LED tube light nominal power 20 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 2100, lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 extruded aluminium LED battens life span of minimum 50000 working hours as per catalogue No Make :- Bajaj (Batten Cat No. BCLAB 20W LED P batten and tube suitable for 18/20 watt retofit LED tube single side connection type). LED or equivalent in Wipro/Philips as approved by GE complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting complete all as specified & directed. . Note : Make of batten and LED tube lamp should be of same make.
S&F in repair LED lamp 18 Watt 4 Pin type, colour Temp 6500K, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts. frequency of 50 Hz, lumen output of minimum 1800 Lumen efficacy of minimum 110 lumens per watt, with output short circuit protection and surge protection upto 3 KV, protection grade IP 20, CRI greater than 80%, available CCT of 6500K, life span of minimum 50000 working hoursretrofit type in existing fitting with necessary change in wiring complete all as specified and directed Make: Bajaj/Philips/Wipro.
S & F LED bulkhead light with pressure die-cast housing light fittings nominal power 10/12 watt LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts. frequency of 50 Hz, lumen output of minimum 1100, lumen , , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 3 KV, protection grade IP 65, CRI greater than 80%, THD below or less than 15%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours complete all as specified and as directed.. (Note : Item to be measured if execuated under new point wiring)
S & F in repair LED bulkhead light with pressure die-cast housing light fittings nominal power 10/12 watt LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts. frequency of 50 Hz, lumen output of minimum 1100, lumen , , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 3 KV, protection grade IP 65, CRI greater than 80%, THD below or less than 15%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours complete all as specified and as directed.
S&F LED 9/10 Watt tube light fitting intergated type, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, , lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours complete suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.5 sqmm three core, and PVC round block white colour x 2 Nos for mounting of fitting complete all as specified & directed. Make :- Bajaj/ /Wipro/Philips as approved by GE
S&F in repair LED 9/10 Watt tube light fitting intergated type, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, , lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, ATHD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours complete suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.5 sqmm three core, and PVC round block white colour x 2 Nos for mounting of fitting complete all as specified & directed. Make :- Bajaj/ /Wipro/Philips as approved by GE
S & F in repair LED street lights nominal power 25 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 2500, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with epoxy powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours as per catalogue No.Bajaj Cat Part No. BCLST25 W LED IV2 or equivalent of Make mentioned under Appendix "B" including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed.
S&F LED 2X18 Watt tube light fitting (T8 type) ,single/double side connection type including two nos LED retrofit tube lamp 2X18 W , LED tube light nominal power 18 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 2100, lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hours as per catalogue No Make :- Bajaj (Batten Cat No. BLRB DB 218 box type batten suitable for 18/20 watt retofit LED tube single side connection type). LED lamp : Make : Bajaj Cat No. BLRB 20W CW LED (retrofit LED tube lamp 20 Watt, Single end connection) or equivalent in Wipro/Philips/ GE as approved by GE complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting including taking down old unserviceable complete all as specified & directed. . Note : Make of batten and LED tube lamp should be of same make.
S & F LED street lights nominal power 60 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 6000, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with polyester powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 with and including taking down defective light fitting from any location mounted on any type of poles/bldgs/ tower/ high mast / Blast pan of up to 18 Mtr height including all necessary scaffolding and safety measures complete after disconnecting of supply cable for replacement of fittings all as specified and directed by Engineer in charge. Note : (i) Any T& P required for the work shall be arranged by the contractor.(ii) It is mandatory that contractor shall submit the insurance certificate minimum 5 Lakh sum assured of all staff/employee employed by him for the work services. . Make Bajaj/Wipro/GE
S & F LED flood lights nominal power 120 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with polyester powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours Make mentioned under particular specification including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 with and including taking down defective light fitting from any location mounted on any type of poles/bldgs/ tower/ high mast / Blast pan of up to 10 Mtr height including all necessary scaffolding and safety measures complete after disconnecting of supply cable for replacement of fittings all as specified and directed by Engineer in charge. Note : (i) Any T& P required for the work shall be arranged by the contractor.(ii) It is mandatory that contractor shall submit the insurance certificate minimum 5 Lakh sum assured of all staff/employee employed by him for the work services. . Make Bajaj/Wipro/GE
S & F LED flood lights nominal power 150 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with polyester powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours Make mentioned under particular specification including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 and including taking down defective light fitting from any location mounted on any type of poles/bldgs/ tower/ high mast / Blast pan of up to 10 Mtr height including all necessary scaffolding and safety measures complete after disconnecting of supply cable for replacement of fittings all as specified and directed by Engineer in charge. Note : (i) Any T& P required for the work shall be arranged by the contractor.(ii) It is mandatory that contractor shall submit the insurance certificate minimum 5 Lakh sum assured of all staff/employee employed by him for the work services. . Make Bajaj/Wipro/GE
Taking down carefully copper/ aluminium submain wirings of any size (2 runs single core including earth continuity) complete including PVC casing capping/ PVC conduit/Steel Conduit with fittings etc, removing materials from site and making good disturbed surfaces of walls, floors etc., complete all as specified and directed.
M&L for Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts grade, 4.0 Sqmm size with multistranded copper conductor FRLSH cable as per IS 694: 2010 (with colour code), drawn in but including PVC casing capping not less than 25 mm ISI marked including all accessories of casing caping as approved by EIC, including PVC insulated unsheathed 4.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete all as specified and directed.
M&L for Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, FRLSH cable as per IS 694: 2010 drawn in but including PVC casing capping not less than 25 mm ISI marked including all accessories of casing caping as approved by EIC including PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as continous earth conductor cable connected to earth dolly complete all as specified and directed. .
S&F for Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLSH cable of 10.0 Sqmm (with colour code), drawn in including PVC casing caping not less than 38 mm width ISI marked double locking type including one including one run of PVC insulated unsheathed, multistranded copper conductor FRLS cable of 10.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in surface/ recess complete all as specified and directed by EIC.
S&F for Sub main wiring with Four run of single core (3 phase) PVC insulated unsheathed cable 1100 volts grade, 6.0 Sqmm size with multistranded copper conductor, FRLSH cable drawn in with and including PVC casing capping not less than 32 mm ISI marked including all accessories of casing caping including one run of PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete all as specified and directed by EIC. ( 4 x 6.0 sqmm + 1 x 6.0 Sqmm earth wire).
S&F for Sub main wiring with Four run of single core (3 phase) PVC insulated unsheathed cable 1100 volts grade, 10.0 Sqmm size with multistranded copper conductor, FRLSH cable drawn in but including PVC casing capping not less than 38 mm ISI marked including all accessories of casing caping including one run of PVC insulated unsheathed 10.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete all as specified and directed by EIC. ( 4 x 10.0 sqmm + 1 x 10.0 Sqmm earth wire).
Taking down old unserviceable TPN / SPN MCB DB's incl MCB of any size and any discription complete all as specified and directed .
S & F sheet metal enclosure for MCB, DB, VTPN 415 Volts,IP-43, 100 amps rated copper busbar 4 way Double door ( Vertical DB with prov of MCB as incomer) Confirming to IS as per IEC 61439-3 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing complete all as specified and directed by Engr-in-charge. Make Legrand/ Seimens/ Schinder/Hager/ABB
S&F sheet metal enclosure for VT DB TPN, MCB DB TPN 4 way (with provision for MCCB as INCOMER and MCB as out going), Confirming to IS as per IEC 61439-3, IP 43,double door including 63 Amp, 25 kA,TP MCCB as incomer (Vertical type double door, 63 Amps MCCB rate inclusive) including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing complete all as specified and directed by Engr-in-charge. Make - Hager Cat Part No. VYV04DM-P and 63 A MCCB, TP, 25 kA , Cat No.HHS063DR Model: or equivalent of make: ABB/Legrand.
S & F sheet metal enclosure MCB, DB, SPN, 240 Volts, 100 Amps rated copper busbar, Confirming to IS as per IEC 61439-3, 12 way Double door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43, IK09 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge.Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, Confirming to IS as per IEC 61439-3, 8 way Double door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43 , IK 09 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge.Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 Amps rated busbar, Confirming to IS as per IEC 61439-3, 4 way Double door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43, Ik09 including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed .Make- Legrand/ Seimens/ Schinder/Hager.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 2 way, single door without bus bar, enclosure made up of CRCA sheet steel RAL 9003 powder coated, IP 30 complete all as specified and directed by Engr-in-charge. ( Note: DB and MCCB/MCB shall be of same make)
S & F circuit breakers (MCB), single pole (SP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 32 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F circuit breakers (MCB), two pole with one protected pole (SPN), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated Rated current 6A to 32 A,, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed. Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F circuit breakers (MCB), three pole with one protected pole (TPN), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated Rated current 40 to 100 A,, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F in repair single pole and neutral enclosure with two pin and earth, plug and socket , suitable for single phase 240 V,complete with one single pole MCB of capacity 20 amps having `C` charactristic, breaking capacity 10 KA, including industial plug top, complete all as specified and as directed. Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S & F circuit breakers (MCB), three pole (TP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 25A to 63 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.Make- Legrand/ Seimens/ Schinder/Hager. Note: DB and MCCB/MCB shall be of same make.
S&F in repairs laminated hylam sheet cover, ISI marked, cut with grooves for mounting of fittings like switches, sockets, fan regulators etc. including fixing in loc with new galvanised screw and cup washer including taking down u/s complete all as specified and directed by EIC of following sizes.
11 x 13 inches
9 x 11 inches
5 x 8 inches
5 x 5 inches
S&F stepped type electronic fan regulator 100 watt flush type (delux) on the existing hylem laminated sheet etc as required complete all as specified and directed by Engr-in- charge. (Note : Item to be measured if executed under new point wiring)
S&F in repair of stepped type electronic fan regulator 100 watt flush type (delux) on the existing hylem laminated sheet etc as required complete all as specified and directed by EIC.
S&F in repair PVC casing caping of min 25 mm dia exclusive of boxes (junction/ terminals) but inclusive of all tees, bends, elobows, reducers, bell mouth tube ends and fixing accessories such as coupler, lock nuts, saddles, pipe hook etc to be fixed on surface for dressing of wiring in neat presentable condition by proper relaying of existing PVC cables including removing of cables/ wires and relaying after fixing of new casing capping including taking out old u/s all as specified and directed by Engineer in charge.
S& F in repair Rigid non-metallic PVC conduit dia 25 mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock,nuts, saddles, pipe hooks etc complete all as specified and directed by EIC.
S & F Non metallic PVC medium grade conduit 20 mm dia, ISI marked for drawing aluminium/ copper conductor cable between pole junction box and light fitting including fixing clamp made of GI strips and nut and bolts (Minimum 3 clamp in each pole to be provided.) including taking out old unserviceable complete all as specified and directed. Make : Presto Plast "MMS"or equivalent make
Supply and Fix in repairs, Modular Switch, one way, 6 Amps, 1 Module, complete all as specified and directed.
Supply and Fix in repairs, Modular Switch, one way, 16 Amps, 1 Module, complete all as specified and directed.
Supply and Fix in repairs, Modular Bell switch , 6 Amps, 1 Module, complete all as specified and directed.
S&F in repair modular socket 6A/16A 2/3 Pin combined -2 module including repairing/replacement of whole modular fittings and frame with new one as per existing fittings all as specified and directed by Engr- in - Charge.
S&F in repair modular switch socket combination 16A , 6 Pin combined -3 module including repairing/replacement of whole modular fittings and frame with new one as per existing fittings complete all as specified and directed by Engr- in - Charge.
S&F in repair of stepped type Modular electronic fan regulator 2 module , 120 watt on the existing hylam laminated sheet etc as required complete all as specified and directed by Engr- in - Charge..
Supply and Fix in repairs, Modular Fan step regulator, 120W - 1 module,complete all as specified and directed.
Supply and fixing in repairs wall mounted bed side study lamp aluminium body, 3W LED type warm white including LED driver with on /off button switch ,flexible pipe with lamp head 360 degree rotating type, 220 Volts complete all as specified and directed by Engr- in- charge. Make :BAJAJ or equivalent of make JAQUAR/CG/Wipro.
Taking down existing panel light fitting any type (600 mm x 600 mm) recess mounting/surface and S&F LED light fitting 36 watt recess mounting of size 600 mm x 600 mm , LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 4000, lumen efficacy of minimum 115 lumens per watt, isolated electronic LED driver (SMPS based constant current supply) with output short circuit protection, over voltage protection, surge voltage protection upto 2 KVs, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, ITHD below or less than 15%, CW available CCT of 5700K, power factor of minimum 0.95, CRCA powder coated white after phosphochromate treatment housing, life span of minimum 50000 working hours including making electric connection from source with PVC sheathed copper conductor wire of 1.5 Sqmm x 3 core complete all as specified and directed by EIC. Make Bajaj/Philips/Wipro
S&F for repairing distribution box(DB's) of any rating, any size by proper dressing of wirings,providing lugs, screw, nuts , cleaning of the burned surfaces etc, tightening of all the connections of incoming and outgoings from the MCB's/ DB, connecting Earthing connection to each earth dolly including fixing of DB cover by providing screws etc complete all as specified and directed by EIC.
S&F in repair single phase direct connection type KWH meter , temper proof, plastic body with LCD display, 230/240V, 10-60 Amp, accuracy class I, 50 Hz, Conf to IS 13779, IP 54, with ( parameters to show Date, time, current reading, KW, PF) including taking out old u/s complete all as specified and directed by EIC Make : Secure (Model Saral) or eqivelent of make: L&T Note : Old u/s meter to be deposite in AGE E/M store.
S&F in repair three phase, 4 wire direct connection type KWH meter , temper proof, plastic body with LCD display, 230/240V( P-N) and 400/415V (P-P), 10-60Amp, sprint 350, accuracy class I, 50 Hz, Conf to IS 13779, IP 54, with polycarbonate cover( parameters to show Date, time, current reading, KW, PF) in existing position by providing Polycarbonate box cover, including making complete electrical connections, connecting PVC cable by providing suitable size copper lugs etc, complete all as directed specifed and directed by EIC. Make : Secure(Sprint 350) /L&T/HPL/Siemens. Note : Old unservieable meter to be deposite in MES store.
S&F Polycarbonate angular lamp holder with back plate, suitable for LED Lamp fittings all as specified and directed by EIC including taking out old u/s.(Note : Item to be measured if executed under new point wiring)
S&F in repair Polycarbonate angular lamp holder with back plate, suitable for LED Lamp fittings including taking out old u/s complete all as specified and directed by EIC
S & F LED downlight recess round shape nominal power 8/9 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 500, lumen efficacy of minimum 90 lumens per watt, isolated electronic LED driver (SMPS based constant current supply) with output short circuit protection, surge voltage protection upto 2 KVs, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 15%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die cast aluminium housing and ring, life span of minimum 50000 working hours complete all as specified and as directed.Make : :Wipro/Philips/Bajaj/GE
Supply and fix Round highway LED light 120 watt with PDC housing, 240 v, PF > 0.90, colour Temp 6500 K,IP66, System Luminious efficacy >110Lm/W, , make: Crompton cat part No.LBH11-120-CDL/60M or equivalent of make : Bajaj/CG
S&F LED bulb 9/10 watt with B22 base, 1100 lumen, 6500 K complete all as specified and directed by EIC. Make : :Wipro/Philips/Bajaj/Havells .(Note : Item to be measured if executed under new point wiring)
S&F in repair LED bulb 9/10 watt with B22 base, 1100 lumen, 6500 K including taking out old unserviceable complete all as specified and directed by EIC. Make : Make : :Wipro/Philips/Bajaj/GE
Supply and Fix in repairs, decorative wall light fixture Decorative, wall mounting, brushed nickel finish fixture with Opal Glass diffuser suitable with 9 W LED lamp B22 base. (Spiral B-22 base) complete all as specified and directed. [Model .LHFOAJE1TN1I060 for light fitting and lamp Make 'Havells' or equivalent Model of Make 'Philips'/ 'Bajaj/GE']
M & L for bracket made out of GI pipe 40 mm dia medium grade, 1.6 metre long bent to shape with MS flat iron clamps made out of 40 mm X 6 mm thick 2-nos mild steel nuts, bolts incuding painting two coats of aluminium paint over a coat of primer all as specified and directed by Engineer In Charge. including taking down old u/s.
S&F PVC flexible roll white colour ,size 20 mm with and including all accessories ISI MARKED including taking out old unserviceable complete all as specified and directed MAKE: Presto Plast or equivalent of make :Supreme/Prince/Finolex
Note :- (i) For item to be replaced under repair (day to day complaint) contactors trade man should report to E/M complaint cell daily and take complaint from concren JE E/M and after attending complaint he should give feedback and return the complaint slip to concern JE E/M in the evening at 17.30 Hrs on same day. (ii) Tradesman deployed for work should wear proper uniform with full shirt and full Pant. Colour code will be decided by EIC. (iii) For any minor repair required in wiring or their is any fault in circuit where the item under repair is to be replaced, contractor has to identify and recitified the fault without any extra cost. (iv) Contractor must ensure a stock of 25% of total qty as catered in CA or 25% of balance qty of the item as catered in CA (during currency of contract) at the MES provided store. If the contractor not provided said above recovery shall be made as per Terms and Condition of the contract as specified in particular specification. However no ‘Advance on Account’ against this provision as material laying at site shall be admissible.
(v) All LED lights/ flood lights shall be properly connected with earth dolly provided with fittings and earth connection. (vi) All LED lights have replacement warranty of 3 years from the date of completion of the contract accordingly condition 46 of GCC (IAFW-2249) shall be amended to extent mention above. Contractor has to submitt warranty certificate from manufacturer . Payment of light fitting will be released after receiving of 3 year replacement warranty certificate (vii) The LED lights will replaced by the contractor free of cost in the case of manufacturing defects and defects covered in standard warranty policy. (viii) The contractor shall submit the surge protection certificate and type test certificate LM 79, LM 80 for luminaries. (ix) All LED fitting shall be identified by printing or fixing sticker duly mentioned the CA number and date of completion. (x) For any change in product or change in catalogue No. etc due to technological up gradation, letter has to be obtained from the lighting company on their letter head signed by an official of National level. (xi) All T&P required at site for installation of light on Bldg/ hanger or at any location shall be arranged by contractor.
Rate quoated above all items here in before inclusive provision as under :Making arrangement for establishment of centralized complaint centre in the existing building as under :- (a) Infrastructure required in Complaint cell i.e. Computer, printer, telephone, furniture, stationary, transport and other necessary items/materials to establish a complaint centre able to receive and manage complaints from the users by all means ie Manual complaint mechanism, Telephonic complaints mechanism, SMS complaint Mechanism and e-mail complaint mechanism, online complaint mechanism and to maintain a consolidated list of complaints and its redressal mode indicating all its relevant data as directed by Engineer-in-Charge.
(b) Provision and maintenance of all tools, plants, equipment and safety gear required for tradesmen under this contract (c) Provision of communication facilities to supervisor and tradesmen. (d) Monitoring and management of complaints report from generation to execution of complaint including pending complaints. (e) Updating status of lodged complaints before change of eight hour shift. (f) Provision of motorized conveyance for deployment to all tradesmen under this contract. (g) Basic inputs to be noted from the complainants will be locality, Building No, Qtr No, Name and Rank of complaint and exact nature of complaint and mobile No/ telephone or based on inputs provided in the complaint redressal sofware. (h) MES may provide software for generation of complaints. However operation entry, printout and releated activities wrt complaint registry and redressal will be the resposibiity of the contractor. On lodging the complaint, the Complaint No will be assigned for reference . Accordingly a corresponding complaint slip shall be generated by the system with all relevant info. Complaint slip should be printed in triplicate and to be handed over immediately to Supervisor who shall detail appropriate tradesmen for repair with required materials/store. One copy of complaint shall be retained in complaint centre and two copies with tradesmen.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any kind of soil ,complete all as specified and directed Note : Manual excavation to be done. During excavation if any damage occured to existing cable any type/ water pipe line, it will be contractor responsibilty to get it repair and make functional by providing jointing kit etc without any extra cost. Contractor has to repair it within 24 hrs so that essential service can not be effected due to such damage.If contractor fails to repair it within 24 hrs penalty @ Rs 500/-per hour will be charged to contractor. In this GE decision will be final.
Returning filling in soft/loose soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point all as specified and directed.
M&L providing sand cushioning with a layer of clean, dry, fine sand for protection of electric cable laid in trenches/ducts, punned down to desired thickness complete all as specified and directed. (Note: For payment purposes only punned down thickness of sand shall be measured )
M & L for laying old size sub class ‘B’ brick for PVC/ XLPE under ground cable protection in trench, layed in the manner that width of brick to be peperndicular to the axis of cable , over LT under ground cable
Laying only bricks for PVC/ XLPE under ground cable protection in trench, layed in the manner that width of brick to be peperndicular to the axis of cable , over LT under ground cable (retreived from taking out of old unsv cable) all as specified and directed.
Checking of street light feeder over head conductors /underground cables including digging out incoming and outgoing cables of any sizes from loop near junction box/ feeder pillar box in tranches, cutting burntout uninsulated portion of cable and rectify the defect and relaying the XLPE cable under ground aluminium conductor in trenches and returning and filling the excavated soil including using elect tools, equipments and safety devices after arranging elect shut down of street light feeders from substation to remove elect faults like tightening of loose jumpers, trimming of tree branches on a particular span, re-tightening of binding wires on insulators, re-tightening of cable lugs etc all as required at site and as directed. Note:- (i) The elect employed for the purpose will be highly skilled along with one mate and should have all necessary tools and safety devices. (ii) Suitable size of cable lugs to be provided by contractor for fixing /jointing the cable in bus bar etc. (iii) Cable gland if required shall be provided and included in cost of repair. (iv) Existing cable to be removed from MCCB/MCB and to be refixed after providing suitable size lugs. Cost of lugs included in cost of repair.
Supply and fixing loop in- loop out fuse thermoplastic junction box of internal dimention 254 x 180 x 90mm made of FRP/ Polycarbonate sheet with weather proof canopy and locking screw fitted with and including 50 Amp rated 4 way connectors for 3 phase and neutral incoming/outgoing , mounted in the box, fixing on street pole/rail poles including necessary aluminium clamps, suitable glands, lugs and GI nut and bolt including taking down old unserviceable junction box all as specified and as directed by Engr-in-Charge. Make - Cape Electric, Model -CJB013PS or equivalent make of Hansel/ Sintex.
S & F in repairs 3 core flexible conductor FR-LSH cables for outdoor use, PVC insulation of type C and having PVC sheath of type ST2, 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for fittings complete all as specified and as directed.
S & F in repairs 3 core flexible conductor FR-LSH cables for outdoor use, PVC insulation of type C and having PVC sheath of type ST2, 2.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for fittings complete all as specified and as directed.
Supply and Fix in repairs, 3 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, type MNX 40 rating, 40 Amps, complete all as specified and directed. [Cat No.CS94190 of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB/Hager.]
Supply and fixed in repair of multifunction digital timer switch (5-40) Amps , 240 Volts , AC , Singlephase complete all as specified and as directed. [Cat No.67DDTO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB/Hager.]
Supply and fixed in repairs MCB TPN 63 Amps, 'C' series 10kA, 415 Volts and to be housed in DBs complete including necessry connection complete all as specified and directed. (Note :- Suitable size cable lugs to be fixed with MCB are deemed to be included in unit rate ).
Supply installation, testing and commissioning of outdoor street light panels, degree of protection IP 54, AC 230 V, 50 Hz, single phase, maximum load12 kW, prewired with astronomical time switch,contactor TP rating 65 Amp and MCB single pole & neutral rating 63 Amp,all as per Cat No. TL065ASO of Make “Indoasian” or equivalent Model of Make Havells/C&S Electric/Hager, complete all as specified and directed.
Supply and fixing swaged & welded MS steel tubular poles, overall length 9.00 metre long, complete specification as per 410-SP-31 of IS: 2713-1980 single swan neck complete with cast iron base plate, final taper plug, pole cap, bolts/nuts, screws/washes, painting with two coats of black bituminous paint through out internally and externally upto planting depth and two coasts of black and yellow alternate strips 30 cm each upto 1.2 mtr from the ground level. The remaining external position shall be painted with two coat of aluminium paint and one coat of cement based paint on PCC copping of pole including numbering of pole with black syenthic paint/ Stricker including dismantling/removing of old damaged Poles of any description and taking asides including all electrical connection, demolition of existing PCC foundation and making good to disturbed surface complete all as specified and as directed by Engr-in-Charge. (Note:- Earth work, PCC work, shall be measured and paid separately.)
M & L Painting of steel pole (swan neck type or straight type) up to 12 mtr height with cross arms, clamp of any length and shape for LT overhead line/ for street light with two coat of aluminium paint after scraching out old paint, cleaning and exiting surface rust free, preparation of the existing surface, including marking pole numbers in a 15 cm dia yellow circle with number writting with black syenthic paint/ Stricker, including painting strips in alternate from bottom to top with three strips of black syenthatic paint & two strips of Yellow/ Sky blue paint (as per existing pattern through out the circumference of pole, including removing extra wall papdi ,peel off wall papdi by sand paper and making good with putty as per existing thickness and applying one coat of white washing on PCC copping of pole and re-numbering of pole with approved size of letter ( Example - P- 001) with synthetic enamel paint of white colour background and black colour lettering complete all as specified and as directed.
M & L Painting to the LT PCC poles with strips in alternate from bottom to top with three strips of black synthatic paint & two strips of Yellow/ Sky blue paint (as per existing pattern) through out the circumference of pole including one coat of lime wash on PCC copping of pole , two coat of white colour cement base paint on pole and two coat of aluminium paint to channels, cross arm, clamps and pipes fixed/ mounted on pole after scraching out old paint, cleaning and making exiting surface rust free, preparation of the existing surface, including marking pole numbers in a 15 cm dia yellow circle with number writting with black syenthic paint/ stricker complete all as specified and directed.
M & L for Tree trimming around 5 mtr around existing overhead line, removing of vegitation and bushes between one span (2.5 Mtr both side , distance between span pole to pole max 25-50 mtrs to be consider as one span) complete all as specified and directed by Enginner-In-Charge. Note:- (i) Contractor has to trim and pruning of tree to be done falls in span between pole to pole. (ii) Necessary survey of site to be done before quoting the rate. If required JCB to be used for clearing the vegitation on the rout of overhead line. (iii) Due to speedy growth of trees/ branches pruning / trimming to be done in perodicity as required irrespective of location. Location can be repeated as per the requirement and measured as per work done. (iii) After tree pruning disposal of branches and kept in stack at the site (within 100 mtrs) directed by Eng in charge shall be done by the contractor.
Materials and Labour for plain cement concrete (1:3:6) Type C-2 using 40 mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed.
Materials and Labour for plain cement concrete (1:2:4) type B0 using 12.5 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles throating, as directed including necessary from work complete all as specified and directed.
Comprehensive maintenance of up to 16 meter high mast shaft conforming IS 5986 (Steel Gr BSEN 10025-S355JO ),High mast as per OEM recommendation installed at various location by after lowering down or through OEM Certified Agencies as approved by GE, including repairing of Control Panel of Hight mast assy , repair / replacement of unserviceable parts like MCB, Contractor, auto manual switch, NO + NC switch , starter motor , replcement of u/s indicators, start stop switch , reapiring and complete wiring of panel with min 1.5 Sqm mwire all as specified and directedand making the system functional by replacing/ repairing the defected parts to the entire satifcation of the Engineer-in-charge. Note : (i) Spares required for the replacement shall be deemed to be included in quoated rates (ii). Each maintenance job shall be covered period of 09 Months
M & L for rewinding of burnt induction motor 1-2 HP, Single phase, 240 V, 50 Hz of high mast with super enamelled copper conductor of the same specification as per old one after dismantling / cutting out burnt windings from stator assembly, cleaning slots properly complete with insulating slots packing, sleeves, papers & reassembling stator and rotor after replacement of worn out spares/matching works, fixing new terminal connector block, replacement of old bearing at both end with bearing grease,installed at various locations through OEMs Certified Agencies as approved by GE,including renewal/replacement of defected parts to the entire satifcation of the Engineer-in-charge
Supply install, testing and commissioning Integral LED aviation light comprising of aluminium housing with polycarbonate enclosure,including taking ou unservieable all as specified and directed. Make Bajaj Cat Part No 110731 BGAV 302 LED or Philips.
Taking down and disconnecting Old unservieable solar street light and Supply and fixing all in one Solar street light made with High Efficiency Mono Crystalline Solar PV Module, Lithium Ferro Phosphate battery with in-built BMS technology, High Efficacy LED, MPPT Solar Charge Controller and Aluminium Extruded body & is specially progrmmed to automatically control the dimming and brightness of light, which increases the backup time with system wattage 20 watt, 12 Volt, DC system lumen output greater than 2400 lumen, system panel module capacity 12 V, MPPT charge controller and PR Sensor with CCT 6000-6500K incl polycrysttaline cell, IP-65 with efficiency greater than 90% with adjustable tilt angle 0-15 degree complete all as specified and directed as per Engr-in-charge. CAT No - BSZSL 20 W LED of Make Bajaj or equivalent to Philips/Wipro/Crompton.
Neha Enterprise
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .