BOQ FOR HVAC (FCU), CIVIL AND ELECTRICAL WORKS AT CBI HQ BUILDING, NEW DELHI
1 16.1 CHILLED WATER PIPING
Supplying, laying/ fixing, testing and commissioning of following nominal
sizes of chilled water piping inside the building (with necessary clamps,
vibration isolators and fittings but excluding valves, strainers, gauges etc.)
duly insulated with 80 kg/cum density resin bonded fiber glass or 144 Kg/ cu
m density mineral wool (non Combustible) pipe section insulation covered with
a layer of 120 gm/sqm polythene sheet (vapour barrier) and finally applying
0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing
feltstrip(as per IS:1322 as amended up to date ) at joints and repairing of
damage to building etc. as per specifications and as required. Note: The Pipes
of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size
above 150mm shall be welded black steel pipe heavy class as per IS: 3589,
from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from
minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS :
1239 and pipes size above 150mm shall be welded black steel pipe heavy class
as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350
mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and
Supplying, fixing, testing and commissioning of following valves, strainers,
2 16.7 gauges in the chilled water plumbing duly insulated to the same specifications
as the connected piping and adequately supported as per specifications.
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O-
Ring PN 16 pressure rating for chilled water/hot eater circulation as specified
1 1.1 CHILLED WATER BASED CASSETTE UNITS
Supply of chilled water cassette units each mprising of following as per
the specifications :
Digitally signed by AMIT
Fan section complete with forward curved centrifugal blowers housed in pre
painted GI casing , FHP motor, 3 rows deep chilled water coil, insulated
condensate drain pan, coil piping connections using necessary copper
piping, condensate drain connections, copper wiring, washable aluminium
mesh multilayer filters etc., high efficiency drain pump, in built thermostat,
motorized valve for flow control including control wiring, y stainer, balancing
valve, connection fitting, decorative panel, drain pump failure alarm, 3 fan
speed control,pressure gauge, digital thermometer etc. Unit should be suitable
for working on heating & cooling mode. Units shall be suitable to operate on
220+10%V,50Hz, 1 phase AC power supply and shall be of following nominal
NDSR-1 supply of Actuator for controlling Nos 34 12237.00
NDSR-2 Connection of FCU with Cnavas & Mouthpiece. Nos 4 10797.00
Civil & Electrical Works:
1 1.14 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes
of FRLS PVC insulated copper conductor, single core cable in surface/ recessed
medium class PVC conduit as required.
Providing & fixing false ceiling at all heights with GRG (Glass Fibre Reinforced
Gypsum) false ceiling tiles of Size 595x595 mm o fapproved texture, design
and patterns having moisture content less than 2%, humidity resistance of
99%, NRC0.50 to 0.75 as per IS 8225:1987, Non combustible as per BS 476
(part 4)-1970 and light reflectance of 85% (minimum) to be laid in true
horizontal level suspended on inter-locking metal T-Grid of hot dipped
galvanised iron section of 0.33mm thick (galvanized @ 120 grams per
sqmincluding both sides) comprising of main-T runners of size 15x32 mm of
length 3000 mm, cross - T of size 15x32 mm of length 1200 mm and
secondary intermediate cross-T of size 15x32 mm of length 600mm to form
grid module of size 600 x 600 mm, suspended from ceiling using galvanised
mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm
outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto
1000 mm length and L-shape level adjuster of size 85x25x2 mm. Galvanised
iron perimeter wall angle of size 24x24x0.40 mm of length 3000 mm to be
fixed on periphery wall / partition with the help of plastic rawl plugs at 450
mm center to center and 40 mm long dry wall wood screws. The work shall be
carried out as per specifications, drawing and as per directions of the Engineer-
With fully perforated 12 mm thick micro tegular edged or 10 mm thick square
edged GRG false ceiling tiles.
Digitally signed by AMIT
Providing and fixing false ceiling at all height including providing and fixing of
frame work made of special sections, power pressed from M.S. sheets and
galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS :
277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with
flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to
the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts,
other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required
length with nuts & bolts of required size and other end of angle hanger fixed
with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200
mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge
of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450
mm centre to centre, shall be fixed in a direction perpendicular to G.I.
3 12.45 intermediate channel with connecting clips made out of 2.64 mm dia x 230
mm long G.I. wire at every junction, including fixing perimeter channels 0.5
mm thick 27 mm high having flanges of 20 mm and 30 mm long, the
perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450
mm centre, with 25mm long dry wall screws @ 230 mm interval, including
fixing of gypsum board to ceiling section and perimeter channel with the help
of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and
finishing to a flush finish of tapered and square edges of the board with
recommended jointing compound , jointing tapes , finishing with jointing
compound in 3 layers covering upto 150 mm on both sides of joint and two
coats of primer suitable for board, all as per manufacturer's specification and
also including the cost of making openings for light fittings, grills, diffusers,
cutouts made with frame of perimeter channels suitably fixed, all complete as
12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board Sqm. 200.00 1529.10
Buy back of 10 nos x 16 HP and 3 nos x 8 HP of Outdoor VRV Units and 1.5 TR
cassette AC ) and 4 nos X 8.5 TR TFA Units
Total Cost of work including GST 42,78,287.71
Digitally signed by AMIT
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT CBI HVAC.pdf
Tender Document
BoQ CBI HVAC.pdf
Tender Document
SCC CBI HVAC.pdf
Tender Document
GCC PMC 2022 Upto Amendment 11.pdf
Tender Document
Forms.pdf
Tender Document
Instruction to Bidder for online Bid Submission.pdf
Tender Document
corrigendum-3483-Corrigendum.pdf
pdf • 0.56 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .