Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32 LAccepted-Finance 5TH FLOOR DP 9 P T I BLDG SALT LAKE SALT LAKE KOLKATA WEST BENGAL 700091 | KOLKATA | KOLKATA | WEST BENGAL | 700091 | L1 | Accepted-Finance Quoting Lowest rate | |
| 2 | L2₹42.2 L+₹10.2 L (31.9%)Rejected-Finance 184 187 TEMPLESTEPS BLOCK ANNASALAI LITTLEMOUNT CHENNAI CHENNAI TAMIL NADU 600015 | CHENNAI | TAMIL NADU | 600015 | L2 | Rejected-Finance Quoting Higher rate |
| Sl No | Description | Qty | Unit | Otis Elevator Company(India)Limited L2 | KONE ELEVATOR INDIA PRIVATE LIMITED L1 |
|---|---|---|---|---|---|
| 1.00 | SITC of Automatic Lift ( as per manufacturer design & as per detailed specification below conforming to IS ) and putting into operation after final testing in the existing lift shaft complete with all accessories and repairing the damage wall / floor if any etc to complete as reqd. | 2 | Sets | 20,68,540 ₹41,37,080 | 15,85,000 ₹31,70,000 Lowest |
| 1.01Make : OTIS / KONE/SCHINDLER | |||||
| 1.02Type: Passenger Lift . | |||||
| 1.03Load : 16 Passenger / 1088 Kg . | |||||
| 1.04Control: Microprocessor based with AC variable voltage & variable frequency ( VVVF). | |||||
| 1.05Machine:- Energy efficient machine, Gearless, With Machine Room. | |||||
| 1.06Position of Machine Room: Directly above the Hoistway. | |||||
| 1.07Speed:1.0 Mtrs./ Sec | |||||
| 1.08Floor served: G+2 | |||||
| 1.09Landing: 3 all on same side | |||||
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
11 Feb 2026, 11:00 amClosed
Sr.Superintending Engineer
Office of the Sr. Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Upgradation of 02(Two) Nos. Fully Automatic Bed Cum Passenger Lift at Emergency Building of Burdwan Medical College and Hospital, Purba Bardhaman.
2025_WBPWD_946200_1
WBPWD/SSEWEC/BED /NIQ-24/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
Purba Bardhaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.1 L
Office of the Sr. Superintending Engineer, Western
26 Feb 2026
12 Nov 2025
13 Feb 2026
12 Nov 2025
11 Feb 2026
18 Nov 2025
12 Nov 2025 - 17 Nov 2025
17 Nov 2025
Make : OTIS / KONE/SCHINDLER
Type: Passenger Lift .
Load : 16 Passenger / 1088 Kg .
Control: Microprocessor based with AC variable voltage & variable frequency ( VVVF).
Machine:- Energy efficient machine, Gearless, With Machine Room.
Position of Machine Room: Directly above the Hoistway.
Speed:1.0 Mtrs./ Sec
Floor served: G+2
Landing: 3 all on same side
Total Rise : 11 Mtr (Approx) (Bidder should visit the site)
Operation: Microprocessor based implex full collective with or without attendant.
Signals: Digital car position indicator,car travels direction indicator in car & at all landing with call registration indicator.
Leveling accuracy: ±5 mm(Micro levelling arrangement)
Car inside : 1600 mm ( W ) x 1000 mm ( D ) x 2400 mm (H) or As per manufacturer's standard conforming to IS.
Car Entrance : Clear Opening 900 mm (W) x 2400 mm (H) protected with car door.
Car Enclosure: Stainless Steel sheet (20 SWG) with Hairline finish with hand rail.
Car Ceiling & Lighting: Stainless Steel with hairline finish with LED lighting and Fan.
Car Ventilation: Pressure fan with anodised aluminium grill.
Car Flooring : Decorative granite flooring (As per direcion of EIC and according to this Department's Order).
Car Door: Stainless Steel centre opening automatic door provided with V3F controlled door drive system.
Landing Door: Stainless steel centre opening automatic door provided with V3F controlled door drive system
Door Opening: Automatic power oprated door with full length Photocell assembly light curtain sensor.
Car operating panel : A best quality Screen touch car operating panel with floor indication and digital hall position & direction indicatiors.
Landing operating panel : A best quality Screen touch car operating panel with floor indication and digital hall position & direction indicatiors.
Fire Rated Door : 2 Hours
PROTECTIVE DEVICES & OTHER ACESSORIES
ARD: Automatic rescue device complete with dry maintenance free batteries as required for automatic evacuation to the nearest floor in case of power failure / single phasing/others.
Overload Protection:Fully loaded with overload protection.On overloading the lift car will not start with door remaining open and give audio display indication
Emergency lighting in car: Battery operated emergency lighting in the lift car.
Intercom system: Battery operated intercom system in Lift Car, Machine Room & Control Room
Emergency Alarm: Battery operated alarm bell system in lift car and control room
Fireman switch:Fireman switch at main landing terminal.
Voice Synthesizer: Voice announcement system (Voice Synthesizer) in the car to announce the position of the elevator in the hoist way as the car passes or stops at a floor served by the elevator.
Main rope - Belt Type (Flat Coated steel belt with V groove / Sreel rope)
Communication & Monitoring the Lift : Lift controller/ Panel shall be Ethernet/Modbus ready with necessary converter, DC Power supply module etc. if required, and there shuld be single Ethernet/Modbus output from the Controller/panel and the same should be connected to BMS (Building Management System) and the controller/ panel should have also required for monitoring of real time data with date & time, maintenance-call back record, Mantrap notice, call records, location of car, Lift room temperature etc. should be noticed & display to in any desktop & mobile though wireless system.
Other works: Necessary cutting of wall/floor for fixing the Fire Alarm switch, all Button switch and also making provision to entry of rope, electric wire etc. as required to complete the job.
DIMENSION OF SHAFT & POWER SUPPLY
Available Shaft Dimension: 2300(W) mm X 2000(D)mm (Bidder should visit the site)
Pit Depth : 1600 mm (Bidder should visit the site)
Overhead : 4200 mm (Bidder should visit the site)
Electric power supply: AC 415 Volt 3phase, 50 Hz, terminated in machine room as per IS.
Terms & Condition
i) The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
ii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
iii) The rate quoted by the manufacturer should be inclusive of cost for providing 2 years DLP after completion of 1 year of initial commisioning.
iv) Rates should be quoted with minor civil works, wall cutting and mending good the damages to the original finish.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 17.49 MB
BOQ_2250517.xls
BOQ • 0.33 MB
new2911.pdf
Additional Documents • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .