Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.4 LAccepted-AOC 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | ₹5.4 L | L1 | Accepted-AOC AOC_Issued |
| 2 | L2₹5.8 LRejected-Finance BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | ₹5.8 L | L2 | Rejected-Finance that the bid is not L1 |
| 3 | L3₹6.7 LRejected-Finance 7 1B GRANT LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | ₹6.7 L | L3 | Rejected-Finance that the bid is not L1 |
| Sl No | Description | Qty | Unit | Computer Gallery L2 | P R INFOSYS L3 | Creative Projects L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation, Testing and Commissioning of ( VDS / UL /FM approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with inbuilt fault isolator with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base. IP Rating : IP - 42. as required. (Note: Detector without inbuilt fault isolator is also acceptable provided the vendor provides one independent fault isolator module for every group of addressable devices, no. of addressable devices in a group will be as per latest recommended India/international standards) (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 22 | Nos. | 2,200 ₹48,400 | 2,650 ₹58,300 | 2,100 ₹46,200 |
| 2.00 | Supply, Installation, Testing and Commissioning of ( VDS / UL /FM approved Addressable Heat detector with Fixed temperature of 59°C and ROR feature to raise an alarm when the temperatures raises 11.1°per Minute with inbuilt fault isolator with Binary coded address setting. Dual LED’s for 360° visibility. Non-Polarized, Sleek low-profile housing design. Regular 100mm base. IP Rating: IP - 42 as required. (Note: Detector without inbuilt fault isolator is also acceptable provided the vendor provides one independent fault isolator module for every group of addressable devices, no. of addressable devices in a group will be as per latest recommended India/international standards) (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 4 | Nos. | 600 ₹2,400 | 2,000 ₹8,000 | 1,600 ₹6,400 |
| 3.00 | Supply ,Installation, Testing and Commissioning of ( VDS / UL /FM approved addressable Manual Pull Station -Single Action with back box, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 2 | Nos. | 3,650 ₹7,300 | 4,000 ₹8,000 | 4,200 ₹8,400 |
| 4.00 | Supply, Installation, Testing and Commissioning of (VDS / UL /FM/ LPCB approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic (Note: Cnventional type sounder is also acceptable provided the vender providas addressable Control Module) with extra acceesories as required. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 2 | Nos. | 8,000 ₹16,000 | 8,000 ₹16,000 | 4,200 ₹8,400 |
| 5.00 | Supply, Installation,Testing & Commisioning of Addressable LPG Gas detector ( VDS / UL /CC/FM approved ) with Base and all necessary accessories. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 2 | Nos. | 3,000 ₹6,000 | 4,200 ₹8,400 | 8,500 ₹17,000 |
| 6.00 | SITC of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 2 | Nos. | 5,200 ₹10,400 | 5,200 ₹10,400 | 3,500 ₹7,000 |
| 7.00Supply ,Installation, Testing and Commissioning of Addressable fully networkable fire alarm control Panel VDS/UL approved suitable for the devices as stated in the previous item of this BOQ along with 20% spear capacity with each loop loading exceeding 80% of the capacity of detectors and devicestaken together, loop card wich will have 125 / 254 devices of both detectors and modules in a single line circuit on any combination, SLC should supports both Class A and Class B wiring. Shall have an LED indication for FIRE, Normal and Redundancy conditions which consists of display board which will have 160 Character Display with Touch key pad, Mother board which will have ARM CORTEX M3 32 Bit Processor, Inbuilt RS-485 Networking Circuit for peer to peer networking, Inbuilt USB 2.0 Port for upload and download the Configuration tools, | ||||||
| 7.10 | Two inbuilt programmable inputs, Two inbuilt NAC's, and Three Programmable Relays. power Supply Board, having minimum 1000 event memory, which will have SMPS fully protected board, which its operates on 120 to 220V AC ± 10% with 50/60 Hz, battery backup 24V DC with built-in charger. the panel have IP-50 rating complete as required and as per specification. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel) | 1 | Set. | 1,40,000 ₹1.4 L | 1,54,000 ₹1.5 L | 1,65,000 ₹1.6 L |
| 8.00 | Supply & Laying of 2 Core 1.5 sq.mm Shielded FRLS copper Cable (For Loop). (Make. Finolex /Polycab /RR Kebel /KEI/ Havells/ Gloster) | 750 | Mtrs. | 90 ₹67,500 | 98 ₹73,500 | 35 ₹26,250 |
| 9.00 | Supply & Laying of 20 mm NB PVC rigid conduit pipe on the surface of the wall. (Make: Precisson-Medium/ Ploycab-Medium) . | 700 | Mtrs. | 10 ₹7,000 | 10 ₹7,000 | 10 ₹7,000 |
Tender Value
₹5.5 L
EMD Value
₹11,000
Closing Date
31 Dec 2024, 1:00 pmClosed
EEI,KNHED, PW Dte
THE EXECUTIVE ENGINEER, P.W.D /KOLKATA NORTH HEALTH ELECTRICAL DIVISION
SITC of Fire Detection and Alarm system at New Emergency Building including installation of LPG Gas detector at the campus of Dr. B.C.Roy Post Graduate Institute of Paediatric Sciences Phoolbagan Campus
2024_WBPWD_771419_1
WBPWD/EE/KNHED/e-NIQ-104/24-25
Open Tender
ELECTRICAL WORKS ORG
45 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹11,000
Office of The EE, KNHED, PW Dte
17 Apr 2026
20 Nov 2024
2 Jan 2025
20 Nov 2024
31 Dec 2024
27 Nov 2024
26 Nov 2024
Amount
Supply, Installation, Testing and Commissioning of ( VDS / UL /FM approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with inbuilt fault isolator with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base. IP Rating : IP - 42. as required. (Note: Detector without inbuilt fault isolator is also acceptable provided the vendor provides one independent fault isolator module for every group of addressable devices, no. of addressable devices in a group will be as per latest recommended India/international standards) (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply, Installation, Testing and Commissioning of ( VDS / UL /FM approved Addressable Heat detector with Fixed temperature of 59°C and ROR feature to raise an alarm when the temperatures raises 11.1°per Minute with inbuilt fault isolator with Binary coded address setting. Dual LED’s for 360° visibility. Non-Polarized, Sleek low-profile housing design. Regular 100mm base. IP Rating: IP - 42 as required. (Note: Detector without inbuilt fault isolator is also acceptable provided the vendor provides one independent fault isolator module for every group of addressable devices, no. of addressable devices in a group will be as per latest recommended India/international standards) (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply ,Installation, Testing and Commissioning of ( VDS / UL /FM approved addressable Manual Pull Station -Single Action with back box, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply, Installation, Testing and Commissioning of (VDS / UL /FM/ LPCB approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic (Note: Cnventional type sounder is also acceptable provided the vender providas addressable Control Module) with extra acceesories as required. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply, Installation,Testing & Commisioning of Addressable LPG Gas detector ( VDS / UL /CC/FM approved ) with Base and all necessary accessories. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
SITC of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply ,Installation, Testing and Commissioning of Addressable fully networkable fire alarm control Panel VDS/UL approved suitable for the devices as stated in the previous item of this BOQ along with 20% spear capacity with each loop loading exceeding 80% of the capacity of detectors and devicestaken together, loop card wich will have 125 / 254 devices of both detectors and modules in a single line circuit on any combination, SLC should supports both Class A and Class B wiring. Shall have an LED indication for FIRE, Normal and Redundancy conditions which consists of display board which will have 160 Character Display with Touch key pad, Mother board which will have ARM CORTEX M3 32 Bit Processor, Inbuilt RS-485 Networking Circuit for peer to peer networking, Inbuilt USB 2.0 Port for upload and download the Configuration tools,
Two inbuilt programmable inputs, Two inbuilt NAC's, and Three Programmable Relays. power Supply Board, having minimum 1000 event memory, which will have SMPS fully protected board, which its operates on 120 to 220V AC ± 10% with 50/60 Hz, battery backup 24V DC with built-in charger. the panel have IP-50 rating complete as required and as per specification. (Approved Make: Honeywell/ Siemens/ Securiton/ Bosch/ Jhonson Control/GST/Ravel)
Supply & Laying of 2 Core 1.5 sq.mm Shielded FRLS copper Cable (For Loop). (Make. Finolex /Polycab /RR Kebel /KEI/ Havells/ Gloster)
Supply & Laying of 20 mm NB PVC rigid conduit pipe on the surface of the wall. (Make: Precisson-Medium/ Ploycab-Medium) .
Supply & Laying of 20 mm HD UPVC pipe on the surface of the wall. (Make: Supreme/ Ori-Plast) .
Supplying & fixing 25mm medium gauge GI Pipe ( Utkarsh ISI-Medium/ Jindal ISI-Medium / Bhusan ISI-Medium / Bansal ISI-Medium / AM-NS ISI-Medium) Protection with necessary fittings and jointing metarials as required
Checking, Testing Fault Rectification and Re-commissioning of necessary field devices (Multisensor Detectors, MCP, Hooter) EN Standard, VDS & FM approved Siemens make.
Supply, Installation, Testing and Commissioning of EN Standard VDS & FM Approved Siemens make Multi-sensor Detectors with base and all necessary accessories.
Checking, Testing, Fault Rectification and Re-commissioning of EN Standard VDS & FM Approved Siemens make 2 Loop Fire alarm Panel (Model No - FC722).
(Rate should be quotated all taxes and duties, GST)
Computer Gallery (BID ID -5938552)
P R INFOSYS (BID ID -5939239)
stage.html
html • 0.05 MB
technical_1708063.pdf
techsummary_1708063.pdf
finance_1708063.pdf
BOQ Comparative Chart
xlsx
finsummary_1708063.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.58 MB
2911.pdf
Tender Documents • 1.46 MB
suspension.pdf
Additional Documents • 2.91 MB
BOQ_1708063.xls
BOQ • 1.79 MB
Download all tender documents and submit your bid