| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.8 LAccepted-AOC 225 NAROT COLONY MODEL TOWN PATHANKOT PB 145001 | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹31.5 L+₹6.8 L (27.3%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L2 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹64,500
Closing Date
17 Jan 2023, 6:00 pmClosed
GE (SOUTH) PATHANKOT
GE (SOUTH) PATHANKOT
SPECIAL REPAIR TO LIGHTENING CONDUCTORS INSTALLED ON AMN STORE HOUSE ESH AT MIL STN UNCHIBASSI UNDER GE SOUTH PATHANKOT
2022_MES_569956_1
GES/PKT/T-51/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) PATHANKOT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (SOUTH) PATHANKOT
₹64,500
Yes
23 Feb 2023
19 Dec 2022
19 Jan 2023
19 Dec 2022
17 Jan 2023
3 Jan 2023
Amount
Disconnectiong, dismentling and taking down carefully single pointed air termination aluminium rod incl GI Pipe any size incl nuts & bolts and seggregating U/s or serviceable parts incl removing from site or setting aside for reuse
Disconnectiong, dismentling and taking down carefully single pointed air termination copper rod incl GI Pipe any size incl nuts & bolts and seggregating U/s or serviceable parts incl removing from site or setting aside for reuse
Disconnecting, dismentiling and taking down carefully aluminium strip of any size up to 32 x 6 mm complete with saddles, GI tubing insulators and seggregating U/s or serviceable parts incl removing from site or setting aside for reuse
Disconnecting, dismentiling and taking down carefully copper strip of any size up to 20 x 3.15 mm complete with saddles, GI tubing insulators and seggregating U/s or serviceable parts incl removing from site or setting aside for reuse
Fixing only aluminium strip retrived from item No 03 above
Fixing only serviceable aluminium termination rod retrived from item No 01 above
Fixing only serviceable copper termination rod retrived from item No 02 above
S&F in repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete with saddles and insulators made out of porcelain and fixing screws for roof conductor/down conductor including nut bolts& washers drilling and riveting for joints of suitable size as required at site all as specified and directed by Engr -in- Charge. Note :- Porcelain insulators are to be fixed at an interval of not more than 75 cm
S&F in repair Copper strip 20 x 3.15mm with saddles and fixing screws etc.for roof conductors and down conductors above ground complete with saddles and insulatiors made out of procelain and fixing screw for roof conductor/down conductor including nuts bolts washers drilling and reveting for joints of suitable size as required at site all as specified and directed by Engr-in-Charge. Note procelain insulators are to be fixed at an interval of not more than 75 Cm
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated location for loop earthing etc. with GI strip 32x6mm including dismantling old ones.
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated location for loop earthing etc. with 20 x 3 mm copper strip.
S&F air termination single pointed aluminium rod 12mm dia and 300 mm long for fixing on GI pipe medium grade 40mm dia pipe duly making suitable fixing arrangement of one end of air termination rod all as specified and directed by engr-in-charge. Note: GI pipe required will measured and paid separately.
S&F air termination single pointed copper rod 12mm dia and 300 mm long for fixing on GI pipe medium grade 40 mm dia pipe duly making suitable fixing arrangement of one end of air termination rod all as specified and directed by engr-in-charge. Note: GI pipe required will measured and paid separately.
M&L for plain Cement concrete 1:2:4 type B-1, (Using 20 mm graded aggregate) as in foundation block for fixing GI pipe for installation of air termination rod etc. complete all as specified Note:- Unit rates includes for provn of form work for rough finished surfaces and finishing the exposed surfaces with 5 mm thick rendering in CM 1:3 all specified.
S&F GI pipe medium grade 40 mm dia for fixing Aluminium strip 25x3.15 mm on roof for lightening protection duly drilling 2 Nos holes on Aluminum strip and GI pipe on one end and fixing with screws/suitable size of bolts & nuts complete all as specified. Note: GI Strip required will measured and paid separately.
M&L for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of GI and GI strip protected by provision of GI medium grade pipe 40mm bore, 20mm dia GI medium grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing).
M&L in replacement of existing old u/s earthing with copper earth plate electrode 600x600x 3.15 mm burried directly in ground not less than 3.25 mtr deep below normal ground level with top edge of earth plate not less than 2.5 Mtr below normal ground level connected to the copper strip 20x3 mm size by means of bolts ,nuts,check nuts and washers of brass after welding of copper strip to earth electrode to full length of earth plate and 20x3 mm copper strip protected by provision of GI light grade pipe 40 mm bore upto test point etc incl provision of concrete pit in PCC1:2:4 type B-i , using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle ,excavation and earth work in any type of soil ,charcoal dust and salt light grade GI watering pipe 20 mm bore with funnel and wire mesh upto main test point complete all as shown in electrical plate No 5 of MES Sch 191 Part-I all as specified and directed . NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing).
Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.
UNITED ENGINEERING CORPORATION
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .