Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance A21 3RD PHASE THIRU VI KA INDUSTRIAL ESTATE LABOUR COLONY GUINDY CHENNAI TAMIL NADU 600032 | CHENNAI | TAMIL NADU | 600032 | Admitted-Finance |
| 2 | Admitted-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | Admitted-Finance |
| 3 | Admitted-Finance 201 PLOT NO 32 SHALAKA BLDG TPS II JUHU ROAD SANTACRUZ WEST MUMBAI SUBURBAN MAHARASHTRA 400054 | MUMBAI SUBURBAN | MAHARASHTRA | 400054 | Admitted-Finance |
| 4 | Admitted-Finance 90 MYLAPORE CHENNAI TAMIL NADU 600004 | CHENNAI | TAMIL NADU | 600004 | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹48,930
Closing Date
9 Nov 2020, 11:30 amClosed
Regional Manager
AAI Cargo Logistics and Allied Services company Limited,Chennai Airport,Chennai-600016
Replacement of Chilled Water Pump of centralized AC plants at Admin Block and Integrated Cargo Complex at Ph III
2020_AAICL_60082_1
AAICLAS/ELEC-17/WATERPUMP/2020
Open Tender
Electrical Works
Works
90 days
Integrated Air Cargo Complex Meenambakkam Chennai
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
AAICLAS
₹48,930
20 Nov 2020
20 Oct 2020
12 Nov 2020
20 Oct 2020
9 Nov 2020
31 Oct 2020
20 Oct 2020 - 31 Oct 2020
Amount
Supply, fixing, testing & commissioning of Primary Chilled Water Pumps (Horizontal Split Case) for centralized AC plant on suitable size platform of Cement concrete with common metal base frame including flanging and connection with the main pipe reducer section and delivery pipe connections with flangs gaskets, hardware for plumbing connections, electrical connections etc as required Note: connecting cable is included in separate item) all as required and as directed with following capacity >Flow - 175 M3/HR >Head - 30 M >Motor Rating KW (IE2/IE3) - 22KW >Motor Speed (1450 to 1480)rpm >Impeller - Bronze >Electrical Control panel with Automatic star delta starter overload relay, MCCB timer, Single phasing preventer etc.., in separate panel box of IP 55
Insulation of Chilled Water piping (Cement Insulation) All different type of valve pumps etc., Supplying, laying/ fixing of following pipes with insulation with fire retardant quality expanded polystyrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) and covering with chicken mesh and overall cement plastering etc as required for existing types of difference sizes in chilled water pipe line.
250mm dia.(32 mm thick insulation)
200mm dia (75 mm thick insulation)
CHILLED WATER PIPING Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated Note:The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS:3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 250mm dia and above.
250mm dia
200 mm dia
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.
200mm dia.
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified
200mm dia.
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. 200mm dia
Rubber Bellows 200 mm dia
Double flanged Butterfly Valves 250 mm dia
Pressure Guage with syphon & cock-6'' Dia
Dial type Thermometer 6'' dia
Supply of 1.1 KV grade of following size of armoured Aluminium conductor PVC/XLPE insulated and PVC sheathed cable as per IS 1551(Part I) 1988/IS-7098 (Part I) 1985 respectively with up to date amendments .
3 core X 35 sq.mm
3.5 core X 35 Sq.mm
Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.(i/c common base channel for the motor pump set)
Insulation of pump fixing of valves & fitting including necessary insulation materials as that for pipe line (pumps and all flanges and strainer)
Towards labour charges water refilling at pipe line and air lock releasing work, re-commissioning of pipeline after water filling
BI MARKETING AND SERVICES PRIVATE LIMITED
Bluestar Limited
TRAC FUJICO AIR SYSTEMS LLP
DElite System Engineering (India) Pvt. Ltd.
PREMIER ENGINEERING TECHNICS PVT. LTD.
Lotus Air Tech Engineering Private Limited
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .