HQ CWE SRI GANGANAGAR
HQ CWE POST BOX 48 SRI GANGANAGAR-335001 (Rajasthan)
SPL REPAIR REPLACEMENT OF WTI OTI RTCC OLTC OF POWER TRANSFORMER OF MRS ALONGWITH CONNECTED ITEMS OF WORKS AT MIL STN ABOHAR
2024_MES_682700_2
CA NO CWE SGNR T-58 OF 2024-25
Open Tender
Miscellaneous Works
Item Rate
180 days
GE ABOHAR
As per NIT
9 documents required · 9 mandatory
₹500
GE ABOHAR
₹56,600
Yes
3 Feb 2025
17 Dec 2024
8 Jan 2025
17 Dec 2024
7 Jan 2025
24 Dec 2024
Amount
M&L for removing old unserviceable isolator and replacement with new one including installation, testing and commissioning of 72.5 KV Isolator for nominal voltage 66 KV system 50 Hz 3 phase system of capacity 1250 Amp continuous current, short time current 31.5 KA for 3 Seconds complete with the following specifications all as specified and directed:- Insulation levels (a) Impulse with stand voltage (i) Phase to earth : 325 kVp (ii) Isolating distance : 325 kVp (b) Power frequency with stand voltage (i) Phase to earth : 140 kV(rms) (ii) Isolating distance : 160 kV (rms) (c) Minimum creep age distance of support and rotating insulator : 1820mm (d) Minimum clearance in air (e) Phase to phase centre distance : 2000mm (f) Between live part and earth : 630mm
(g) Between live part when switch is open : 950mm (i) On the same pole : 950mm (ii) Between adjacent pole : 1300mm (h) Current density (i) Moving blades : 2 Amps/Sqmm (ii) Terminal pads : 17 Amp/Sqmm (iii) Contacts : 1.60 Amps/Sqmm (iv) Terminal connector : 1.25 Amp/Sqmm Design & Construction (a) Nos insulator per pole : 03 (b) Nos of breaks per pole : 02
M&L for removing old unserviceable LA and replacement with new one including installation,testing and commissioning of Heavy duty metal oxide lightning arresters 60 KV 10 KA station medium duty (SM) (old line discharge class -III) as per IEC 60099-4 of 2014 & IS: 15086 (part -4) of 2017 with Qrs=1.6C & wth =7kJ/kV gapless type surge Arrester comprising of Metal Oxide Elements housed in FRP CAGE 'DESIGN B' duly moulded with silicone Polymer to be used on a Nominal system voltage of 66 kV and Maximum System Voltage of 72 kV with an MCOV of 51 kVrms with insulating Base & surge Monitor along with connecting lead of 35 sqmm Copper Cable of 2 meter length with Terminal connector suitable to Single ACSR conductor complete all as specified and directed.
M&L for removing old unserviceable CT and replacement with new one including installation, testing and commissioning of Single Phase, Dead tank type outdoor CT (current transformer), ratio , primary 75-150 A in Core 1-3, Secondary 0.577A in Core -1, core 2 & 3 -1 A for metering & protection, heighest sys voltage -72.5 KV, oil cooled, insulation level -140 KV/325 KVp ,rated STC 31.5 KA for 3.0 seconds ,rated burden -25VA, continious thermal current 120 % of the rated current accuracy with oil as per IEC-60044-1 & IS-2705 suitable for 66 KV including junction box complete all as specified and as directed.
M & L for Earthing complete with copper earth plate electrode 600x600x 3.15 mm burried directly in ground not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.25 Mtr below normal ground level connected to the copper strip 20x3 mm size by means of bolts ,nuts,check nuts and washers of brass and 20x3 mm copper strip protected by provision of GI medium grade pipe 40 mm bore incl provision of concrete pit in PCC 1:2:4, type B-1, using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle, earth work in any type of soil ,charcoal dust and salt, light grade GI watering pipe 20 mm bore with funnel and wire and copper strip upto main earthing of pole/equipment complete all as shown in electrical plate No 3 of MES Sch 2009 Part-I all as specified and directed . Note:- (i) Up to 7.5 Mtr length of pipe of 40 mm dia and copper strip shall be deemed to be included in unit rate quoted by the tenderer. (ii) Resistance of earthing should be less than 1 Ohms failing which the contractor will do the earthing again to achieve the desired result i.e. less than 1 ohms. (iii) In case soil is not suitable same is to be replaced with good quality clay soil to achieve the desired result of less than 1 ohms. (iv) Quoted rate shall be deemed to be inclusive for the above aspects.
Supply and fix in replacement with new one, including installation, testing and commissioning of Circuit breaker SF-6 out door type 66 KV nominal voltage 3 Phase, 50 HZ as per IEC-62271-100 complete with all accessories and of the following technical specifications :- (a) Highest system voltage between phase: 72.5 KV. (b) Rated normal current : 2500 Amps. (c) Rated power frequency withstand voltage Urw : 140 KV. (d) Rated lightning impulse withstand voltage Uw : 325 KV. (e) Short circuit breaking current : 31.5 KA (f) Rated duration of short circuit:3 seconds (g) Minimum creep age distnace to ground ; 1820mm. (h) Type of mechanism enclosed in housing Motor operated spring-spring. (j) Rated operating sequence : 0-0.3 Sec-CO-3 MIN-CO. (k) Rated closing/tripping voltage : 110 VDC (l) Current of closing/tripping coil: 6 A max at 110 VDC.
M&L for removing old unserviceable OLTC,and replacement with new one 66/11 KV, number of position -17,3 phase, operating Step Voltage -1000V,Max operting voltage over Taps -20000V ,Max continious current -300 A on load Tap Changer (OLTC), Rated Voltage-66 KV, Rated Current-300A, , Motor Supply-415 Volts AC, Oil Quantity- 800 Ltr, Appx Weight of oil -680kg , Appx total weight 1265 kg, pressure withstand (external) -0.3ATU ,Vaccum withstand of terminal board-1ATU suitable for 5 MVA transformers.
M & L removing old unserviceable RTCC Panel and replacement with new one shall be IP 42 gland plate to be 3mm thick suitable for 66/11 KV, 5 MVA transformers, sheet thickness (CRCA) :- not less than 1.6 mm Gland plate sheet thickness:- 2 mm , total weight;- 40+ 5 Kg , The cubical has one OFF type hinged door at rear, the door handle operated latches and the handle isprovided with centre key pad lock, interior lighting is providd with door switch ,RTCC shall be vermin and weather proof(Indoor application only) , All appratus mounted in RTCC shall be effectively earthed by means of copper wire having cross section less than 2.5 sqmm , multi stranded copper wire to be used for wiring inside the RTCC, size 1.5/2.5 sqmm PVC ,1100 V grade as per IS 694 for control circuit, 4 Sqmm PVC 1100 v grade as per IS 694 for CT wiring.
M&L for removing old unserviceable WTI and replacement with new one including installation, testing and commissioning of WTI, model 1002, winding temp indicator with 02 contacts 10 mtr capillary length. Range 0 to 150 deg C , 115 mm segmental; accuracy Range with in ± 1.5 % of full scale. (a) O.A. deg no. AM-9004-P1 (option-1 switch contact rating 15 A@250 AC, 0.5 A@250V DC) : (b) Sensing bulb drg no. AM-9001-P1. Note:- Gradient 1.5 [email protected] Deg C ; Union- 1.5 inches male union suitable for 66/11, 5 MVA ECE tranformer complete all as specified and directed.
M&L for removing old unserviceable OTI and replacement with new one including installation, testing and commissioning of OTI model 1002, Oil temp indicator with 02 contacts 10 mtr capillary length. Range 0 to 150 deg C, 115 mm segmental; accuracy Range with in ± 1.5 % of full scale; (a) O.A. deg No. AM-9004-P1 (option-1 switch contact rating 15 A@250 AC, 0.5 A@250V DC) : (b) Sensing bulb drg No. AM-9001-P1. Note:- Gradient 1.5 [email protected] Deg C ; Union- 1.5 inches male union suitable for 66/11 , 5 MVA ECE tranformer complete all as specified and directed.
M&L for removing old unserviceable Buchhloz relay and replacement with new one (Double float type) (having contacts for alarm & Trip) of 05 MVA tranformers complete all as specified and directed.
M&L for removing old underviceable 11 kV LBS panel and replacement with new one rated current- 630 A, Supply voltage- 11KV, No. of phase-03, frequency-50Hz, Rated short time with stand current-31.5 KA/3 Sec, Rated withstand voltage at power frequency of 50 Hz 25 kV rms, rated impluse withstand voltage 75 kV peak, Panel arrangment panel mounted, compartmentalized, Mounting floor-Indoor/ Outdoor, Cooling method- Air cooled, Enclosure thickness CRCA- min 2mm, Degree of protection IP 4X, Paint shade RAL 7035, Main Busbars Aliminium, Busbars size 40X10 Sq mm, Earth bus bar GI, Bus bar size- 40x5 sqmm, main bus bar size- 40X 10 Sqmm, type of bas bar support insulators cable, termination epoxy resin cast, incoming and outgoing top cable entry/bottom entry as per BOQ Arc Quenching medium Air, Temp. rise at rated normal current above 50 deg C, Number of panel as per BOQ, Cable size for incoming and outgoing 3CX 500 Sqmm, Type of operating mechanism Quick Make- Break, manual spring assisted installation on termination Bar, safety features and interlocks will be provided between mainswitch and earth switch door, general finish for indoor/outdoor LBS totally enclosed, metal clad, vermin and dust proof suitable tropical climate use as detailed in the specification.
DIAMOND SALES COROPORATION (BID ID -3207997)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .