Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.0 CrAccepted-AOC | ₹23.0 Cr | L1 | Accepted-AOC LOWER BIDDER |
| 2 | L2₹23.5 CrRejected-Finance | ₹23.5 Cr | L2 | Rejected-Finance HIGH BIDDER |
| 3 | L3₹24.6 CrRejected-Finance | ₹24.6 Cr | L3 | Rejected-Finance HIGH BIDDER |
| 4 | L4₹25.9 CrRejected-Finance | ₹25.9 Cr | L4 | Rejected-Finance HIGH BIDDER |
| 5 | L5₹26.6 CrRejected-Finance | ₹26.6 Cr | L5 | Rejected-Finance HIGH BIDDER |
Tender Value
Refer Docs
EMD Value
₹33.6 L
Closing Date
12 May 2022, 3:00 pmClosed
Shri G I WADHWA Chief Executive
CCE R AND D WEST PASHAN PUNE
PROVISION OF CIVIL WORKS FOR DEVLOPMENT AND MANUFACTURING OF PRIMARY EXPLOSIVE AND INITIATING DEVICES AT HEMRL PUNE
2022_DRDO_681337_2
CCEW/C-2/20220/HEMRL/PLG
Limited
Civil Works
540 days
HEMRL PUNE
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,000
Yes
CCE R AND D WEST
₹33.6 L
Yes
10 Oct 2022
28 Apr 2022
13 May 2022
29 Apr 2022
12 May 2022
5 May 2022
29 Apr 2022 - 4 May 2022
Amount
SUBHEAD -I SITE CLEARENCE
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 1Km outside the periphery of the area cleared.
SUB HEAD - II, EARTH WORK EXCAVATION
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in?charge.
All kind of soil
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in.Ordinary rock
Ordinary rock
Hard rock (Blast Prohibited)
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m. All kinds of soil.
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. a) Ordinary rock :
b) Hard rock (blasting prohibited) :
Filling available excavated earth (Excluding Rock) in trenches,Plinth sides of foundations etc,in layers not exceeding 20cm in depth consolidating each diposited layer by ramming and watering,lead upto 50meter and lead upto 1.5meter
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.
Hard rock
Supply and filling approved morrum obtained from outside MOD land for formation of sub base including spreading in layers not exceeding 200mm in thick necessarywatering, consolidation to the reqired level in gradient & cambere with 8 to 10 tonne road roller to achieve minimum of optimum moisture conditions to give at least 95% of the maximum dry density (proctor density) (Voids 5% to be deducted)
Supply of good earth of approved quality obtained from outside MOD land filling in layers not exceeding 20cms thick at all heights and depths in foundations, pits, trenches, sewer lines around structures and foundation under floors other places including dressing and levelling watering, consolidation to achieve minimium of 95% proctor density etc., complete as per drawing specifications, payments shall be made for the quantity after deducting the voids.
Credit For Hard Rock
SUBHEAD-III :ANTI TERMITE TREATMENT :
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for POSTCONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall & rodding etc. complete:With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration
Treatment of Soil under the floor using chemical emulsion @ 1litre per hole 300mm apart including drilling 12mm diameter holes and pluging with cement mortar 1:2 (one cement : 2 sand) to match the existing floor With Chlorpyriphos/Lindane E.C. 20% with 1% concerntration
SUBHEAD-IV : PLAIN REINFORCED CEMENT CONCRETE.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -Flooring:1:3:6(1 Cement : 3 Coarse sand(zone-iii) : 6 graded stone aggregate 20 mm nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work up to plinth level :1:4:8 (1 Cement : 4 Coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing:
1:2:4 (1 Cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size).
Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification.
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth.
Providing and fixing up to floor five level precast cement concrete string or lacing courses, copings, bed plates, anchor blocks, plain window sills, shelves, louvers, steps, stair cases, etc., including hoisting and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), cost of required Centering complete.
1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20mm nominal size).
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :II)1:2:4 (1 cement : 2 coarse sand(zone-III): 4 graded stone aggregate 20mm nominal size)
Providing, fixing and stripping off all types of shuttering using steel / plywood form work for the following items of RCC works at the heights and depths mentioned against each item etc.,complete as per specifications and as directed by the engineer in charge.
a) Foundations & footings & bases of columns
b)Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
c)Suspended floors, roofs, landings, balconies and access platform
d)Lintels, beams, plinth beams, girders, bressumers and cantilevers
e)Columns, Pillars, Piers, Abutments, Posts and Struts
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and de-centering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).
Supplying, fabricating and fixing in position reinforcement bars at all levels and positions including the cost of steel, straightening, cutting, bending, binding and placing in position etc., as per drawings and specifications including the cost of binding wire, labour etc., all complete for reinforced concrete.
a) TMT bars of grade Fe-500
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum.Excess/less cement used as per design mix is payable/recoverable separately).
All works Upto plinth level
All works above plinth level upto floor V level
Add/Deduct for using extra cement in the items of design mix over and above the specified cement content there in.
SUB HEAD V- STONE & BRICK MASONRY.
Brick work with common burnt clay modular bricks of class designation 7.5 in foundation and plinth in:Cement mortar1:6(1 cement: 6 coarse sand)
Brick work with non modular fly ash bricks conforming to IS:12894,class designation 10 average compressive strength in super structure above plinth level up to floor V level in:
Cement Mortar 1:6 (1 Cement : 6 Coarse sand)
Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in :Cement mortar 1:6 (1 cement : 6 Coarse sand)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :
Cement mortar 1:6 (1 cement : 6 coarse sand)
SUBHEAD-VI : PLASTERING & SURFACE TREATMENT :
6mm thick plastering in cement mortar 1:3 (1cement: 3 fine sand) at all levels and locatiions for all concrete surfaces of columns, beams and slabs finished smooth and even.
12mm thick cement plaster with cement mortar 1:4 (1cement: 4 fine sand) on internal surfaces of walls (brick or concrete surfaces) finished smooth with trowel including scaffolding, curing etc., complete at all heights in cement plaster work in proportion recommended by the manufacturers.(Internal surfaces)
12mm cement plaster of mix: II)1:6(1 cement:6 fine sand)
15mm thick cement plaster on the rough side of single or half brick wall of mix: 1:4(1 cement:4 fine sand)
15mm thick cement plaster with cement mortar 1:4 (1cement: 4 fine sand) on internal surfaces of walls (brick or concrete surfaces) finished smooth with trowel including scaffolding, curing etc., complete at all heights,including mixing of water proofing material in cement plaster work in proportion recommended by the manufacturers.
15 mm cement plaster with cement mortar 1:6 (1cement : 6 coarse sand) on external surfaces of wall (brick or concrete surfaces) finished smooth with trowel including scaffolding,curing etc , complete at all heights in cement plaster work in proportion recommanded by the manufacturers.
Pointing on stone work with cement mortar 1:3(1 cemet :3 fine sand)Flush/Ruled Pointing
White washing with lime to give an even shade :
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.
New work (two or more coats) over and including water thinable priming coat with cement plaster.
Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm)
Finishing walls with premium acrylic smooth exterior paint of Apex Ultima of M/S Asian paints or equivalent make & of required shade : New work (Two or more cots [email protected] ltr./10.0 sqm over & including priming coat of exterior coat applied @2.20 kg /10.0 sqm.
Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/ 10 sqm over an under coat of primer applied @ 0.80 ltr/ 10 sqm of approved brand and manufacture
Providing and applying two coats of fire retardant paint on cleaned wood / ply surface @ 3.5 sqm per litre per coat including preparation of base surface as per recommendations of manufacturer to make the surface fire retardant.
Providing and applying two or more coats of synthetic enamel paint of approved brand and shade including a coat of approved steel primer on steel surfaces.Two or more coats on new work
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
SUBHEAD-VII : FLOORING :
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer?in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. Tile Size:300 x 450 mm
52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
Cement plaster skirting up to 150mm height, with cement mortar 1:3 (1 cement : 3 sand), finished with a floating coat of neat cement.18 mm thick
Marble stone flooring with 18 mm thick marble stone, as per sample of marble approved by Engineer-in-charge, over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry, including rubbing and polishing complete with :
Black Zebra
Udaipur Green Marble
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
25mm thick
Providing and laying Non skid Ceramic floor tiles of size 450x450 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc with skirting., complete.
Size of Tile 600X600 mm.
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete: Size of tile 600x600 mm
Surface prepairation and levelling course with moisture barrier .Prepare the concrete surface using grinding to remove any loose material ,contaminations and laitance to provide a sound ,fine gripping surface.Clean the entire floor area using a powerful industrial vaccume cleaner .M&L for providing and applying 2 part water dispressed epoxy resin primer sika floor -80 primer of sikka or equivalent over the primed surface providing and applying 3 part ,self smoothing underlay screed sika floor 82 epocen of sika or equivalent to a thickness of 3mm @6.75 kg/m2/mm having carbon dioxide diffusion coefficient 4168 as per klopfer engel fried method water vapour diffusion coefficinet new H2O=252 as per DIN 52615,water absorption coefficient W=0.02kg/m2 as per BIN 52617 when applied at minimum 3mm thickness it colud be laid over high moisture content subsrate and most be used when substrate moisture is more than 4%
Supply and application of antistatic Epoxy flooring system in the following sequence M&L for providing and installing of Electrodes sika earthing KIT of sika floor Leitset (earthing kit)@1 no electrode/300 sqm area including interconnecting the electrodes with copper wires.(Note:Per room,atleast two earthing points are required ).Providing & applying ESD Epoxy top coat of 2mm thick with sika floor 262 AS N of Sika or equivalent having 97% (by volume )solid content including taking the conductivity measurements of top coat applied over conductive under coat or sika floor 220watt of sika or equivalent @0.10kg/sqm including testing the resistance of under coat over application of a primer sika floor 161 HC epoxy primer of sika or [email protected]/sqm including prepairarton of.
Laying of vaccum Dewatered concrete flooring of 100mm thick laid in RCC(1:2:4) using 20mm and down graded aggregates metal laid in panels of size not more than 3m x 4m or as per internal floor area.Concrete shall be laid and finished with screed borad vibrator ,vaccum dewatering process and finally finished by floating ,brooming with wire brush etc.Complete as per specifications and directions of iengineer -in-charge .(The panel shuttering work shall be paid for separately).including labour and floor hardener material .(Note:-cement content considered in this item is @ 330 kg/cum.Excess /less cement used as per design mix payable/recoverable separately). a] Cutting grooves of the floor area upto 4mm width and 20mm depth with diamond core cutting machine. b] Cleaning of the surface from dirt, dust and other contaminations. c] Providing and application of structural graded high build epoxy mortar /concrete treatment with - ROOFCRETE EP / ZORICRETE EP/ POWER n CRETE EP (Armstrong /PMCC / EBT) to finish the damaged edges of joint and making the groove upto the depth of 20mm. d] Providing and application of one coat of polysulphide primer – ROOFSEAL PRIMER / ZORISEAL PRIMER / POWER n SEAL PRIMER (Armstrong / PMCC/ EBT ) on inner edges of Joint. e] Providing and application of Two part Polysulphide sealant - ROOFSEAL PS / ZORISEAL PS POWER n SEAL PS (Armstrong / PMCC /EBT) to a width of 4mm and 20mm depth with putty knife and neat finish.
Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge.ii) In flooring on a bed of 10mm thick mortar 1:4 (1 acid proof cement:4 coarse sand)Acid and alkali resistant tile.
In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand).Acid and alkali resistant tile.
SUBHEAD-VIII : STEEL, JOINERY & WOOD WORK.
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings /wooden frames with rawl plugs screws etc.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-incharge. (Glazing, paneling and dash fasteners to be paid for separately) : a) For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
b) For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron
Providing and fixing pressed steel door frames conforming to IS 4351 manufactured from commercial mild steel sheet of 1.25mm thickness, including jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50 x 25mm, or base ties of 1.25mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb with mortar guards, lock strike plate and shock absorbers including filling with cement concrete 1:5:10 complete as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-Charge.
a) Single rebate of size 105X60mm.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):a) With float glass panes of 4.0 mm thickness
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters :
(a) 35 mm thick including ISI marked with Stainless Steel butt hinges with necessary screws
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90mm x 45mm having single rebat of 32mm x 15mm to receive shutter of 30mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fibre glass from all sides. MS stay shall be provided at the bottom to steady the frame.
Providing and fixing 30mm thick Glass fibre reinforced plastic (FRP) paneled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5mm thick FRP laminate for panels conforming to table -3 of IS: 14856 : 2000, complete as per direction of Engineer-in-charge.
Providing and fixing the following hardware fittings of approved make. a) Providing & fixing alluminium tower bolts, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS:1868) transparent or dyed to required colour or shade,with necessary screws etc. all complete. i) 200mm, long 10 mm dia
ii)100 mm long,10 mm dia
b) Providing & fixing Aldrop 300mm long with 16mm dia rod, required colour or shade with necessary screws etc., complete
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing chromium plated brass 100 mm mortice latch and lock ISI marked with six levers and a pair of lever handles of approved quality with necessery screw etc.complete.
Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
Providing and fixing the following hardware fittings of approved make :a)Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete : i) Size 125 x 64 x 1.9 mm
Providing ,fitting,fixing of 40mm thick M.S.Door shutter comprising following specifications: Outer Sheets : 1.25 mm thick Mild steel OR galvanised steel sheet. Insulation:First class quality ckwood/Honey comb core. Internal stiffness:Braced with 1mm MS channels @ 300mm cc for reinforcement . Hardware receiving:3-4 mm thick MS plates with hole and taping done welded inside to insure fixing of door hardware like hinges,door closer,locks etc . Made from:1.25mm thick mild steel sheet/Galvanized steel sheets. Profile of frame:A type 100 x 60 mm Door Finish:Fire Resistant Paint.
Using M.S. angels 100x100x6 mm for diagonal braces
Structural steel work to be riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
SUBHEAD- IX: ROOFING , WATER PROOFING & MISCELLANEOUS
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. The job shall be inclusive of providing & fixing of accessories confirming to IS 13592. a)110 mm dia
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with I.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4stone dust) and making good the wall etc. complete.110mm
Providing and fixing to the inlet mouth of rain water pipe PTMT (an Engineering Thermoplastic) grating square (Slit) 150 mm square with a height of 8 mm and weighing not less than 100 gms.
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs,balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixedwith water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in- charge.
(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin- charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 m square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge :
With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Providing corrugated GS sheet roofing including vertical.=/curve surface fixed with polymer quoted J or L hookes bolts and nuts 8mm dia with bitumen & G.I limpet washers or with G.I.limpet washers filled with white lead including a coat of approved steel primer and 2 coats of approved paint on overlapping of sheets complete(upto any pitch in horizontal/vertical or curved surface),excluding the cost of purlins rafters and trusses and including cutting to size and shape wherever required.
0.63mm thick with zink coating not less than 275 gm/m2
SUB HEAD -X:SANITARY SERVICES
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I.brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floorswherever required :W.C. pan with ISI marked white solid plastic seat and lid. Hindware and Cat no: SLICK 20011 or equivalent.
( a ) Star White glazed European water closet with wash down pattern of approved make with P or S trap fixed to floor with necessary teak wood plugs, CP brass screws, etc.
( b ) 10 ltrs. capacity PVC low level flushing cistern made of corrosive resistant materials fixed to wall with necessary brackets and screws, and plugs with matching chromium plated flush bend with float valve and flushing arrangements of slimline or equivalent.
( c ) 15 mm heavy quality flexible PVC inlet connection with brass hexagonal check nuts with washer at both ends.
( d ) Approved make plastic seat and cover (Commander or equivalent make) to match the colour of water closet and CP hinges fixed to water closet.
( e ) 15 mm CP brass Angular stop cock fixed between GI outlet and PVC inlet.
Hindware Cat No. 20012 or equivalent.
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with fittings,standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required .Single half stall urinal with 5 litre P.V.C. automatic flushing cistern :make : Hindware-61002, star white OR Equivalent.
Providing and fixing wash basin with CI brackets,32mm CP brass waste of standard pattern, including painting of fittings and brackets,cutting and making good the walls wherever required. W.B Hindware model 10080 /Parryware or Equivalent White vitreous china wash basin(round/oval under counter) size 580 mm x 430 mm with 15mm C.P. brass pillar tap Jaguar Model No CON-359KN & Bottle trap-Jaquar model no. ALD 769/CERA or approved equivalent, 15mm PVC connection pipe with angle valve and CP waste coupling -Jaquar model no. ALD 709/CERA orapproved equivalent).
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to European type W.C. of quality and make as approved by Engineer - in - charge.
Providing and fixing toilet paper holder :
Providing and fixing toilet paper holder : CAT No- ACN-CHR-1151N of Jaquar/Equivalent.
Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms.
Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : 15 mm nominal bore
Providing,fitting and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 15 mm nominal bore
Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing : Rectangular shape 600x450 mm
Providing fixing C.P. brass towel rail of size 600 mm long fixed to wooden cleats with CP brass Screws complete as per instructions of the engineer-in-charge .Cat No- AKP-CHR-35781P of Jaquar make/ Equivalent design & make.
Providing and fixing 15 mm nominal bore C.P. brass short body two way bib cock of approved quality conforming to IS : 8931 .make of Jaquar cat no-FLR-5041 N/equivalent .
Supplying & Fixing C P Soap Dish of approved make complete as directed Make :- Jaquar or equivalent) Catno-ACN-1131 N
Providing and fixing CP brass grating with frame of approved design including setting in floor with cement motor to match with floor finish as per architect requirement. a) Size 100 mm X 100 mm
SUB HEAD-XI: INTERNAL WATER SUPPLY SERVICES:
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00m spacing this includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-charge. Concealed work, including cutting chases and making good the walls etc.
a) 15 mm nominal dia Pipes
b) 20 mm nominal dia Pipes
c) 25 mm nominal dia Pipes
Providing & fixing full way lever operated forged brass ball valve of brass body with forged brass hard chrome plated steel ball tested to a pressure not less than 15 Kg / sqcm with threaded / flanged joints complete with nuts, bolts, gaskets, washers etc.
a) 15 mm dia
b) 20 mm dia
c) 25 mm dia
Providing and fixing Butterfly valve (upto 150mm dia with band lever operation & above with gear box operation) with SS-304 disc. Tested to a pressure not less than 15 Kg/sq.cm including rubber gaskets, flanges, nuts, bolts, washers & painting complete as required.
a) 25 mm dia
Providing and fixing unplasticised P.V.C connection pipe with PTMT Nuts coller and bush of approved quality and colour. With 15mm nominal bore with 45cm length
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
SUB HEAD-XII: INTERNAL ELECTRIFICATION,POWER WIRING,FLP FIXTURES & CABLING :
INTERNAL ELECTRIFICATION
Point wiring for light points, fan points, exhaust fan points, 6A plug and socket with 2 runs of 1.5 Sq. mm FRLS PVC insulated, multistranded, copper wire of 1100V grade laid in and including 25 mm dia. heavy gauge FRLS PVC conduit in concealed in ceiling / walls conforming to IS 732 including one run of 1.5 sq.mm FR PVC insulated, multistranded, copper earth wire of 1100V grade including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, electronic fan regulator etc. (Including sub main wiring of 2 runs of 2.5 sq.mm & 1 x 1.5 sq.mm FR PVC insulated, multistranded, copper wire of 1100V grade in 25 mm dia heavy gauge PVC conduit with conduit accessories etc. complete).
One light point controlled by one 6A switch
Two light point controlled by one 6A switch
Three light points controlled by One 6A switch
Four light points controlled by One 6A switch
Five light points controlled by One 6A switch
One exhaust fan point controlled by one 6A switch with 6A rated ceiling rose
One 3 pin 6A socket controlled by one 6A switch (Dependent)
Supply and wiring for 6A Socket outlet with 2runs of 1.5sq.mm FRLS insulated multistranded copper conductor wire and 1run of 1.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall/ceiling along with required accessories, supply and fixing of 6A 3 pin modular type socket with switch in anodised GI box and front plate complete with fixing accessories including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. as required. (Independent)
Supply, installation, testing and commissioning of 6 / 16A, 5 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 2runs of 2.5sq.mm FRLS insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (Independent)
METAL CLAD POWER SOCKETS (Make : Legrand / Schneider)
Supply, installation, testing and commissioning of factory made 16A, metal clad socket outlet controlled by 16A, 10kA, SP MCB, in and including MS painted box in concealed manner of adequate sizes including plug top with necessary accessories including wiring with 2runs of 4.0sq.mm FR insulated multistranded copper conductor wire and 1run of 2.5 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.
Supply, installation, testing and commissioning of factory made 32A, 3Phase+N+E, socket outlet controlled by 32A, 4P RCBO, 100mA in and including MS painted box in concealed manner of adequate sizes including plug top with necessary accessories Cutting, chases in wall and making them good after fixing in sheet steel boxes , etc. complete as required.
Supply, installation, testing and commissioning of factory made 63A, 3Phase+N+E, socket outlet controlled by 63A, 4P RCBO, 100mA in and including MS painted box in concealed manner of adequate sizes including plug top with necessary accessories including wiring with 4runs of 10.0sq.mm FR insulated multistranded copper conductor wire and 1run of 6.0 sq.mm earth wire laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. etc. complete as required.
Supply, Installation & testing of 300mm dia, 900 RPM Exhaust fan suitable for suitable for single phase 230/240V, AC Supply complete with motor MS louvers , mounting brackets, all accessories etc complete as required. Equivalent to CG / BAJAJ / HAVELLS
Supply, Installation & testing of 400/450mm wall bracket fan(FLP Type) suitable for use on single phase, 230 volt, 50Hz AC supply complete with all accessories as required
Supply, Installation & testing of 380mm 900 RPM Heavy Duty Exhaust fan suitable for use on single phase, 230 volt, 50Hz AC supply complete with all accessories as required Equivalent to CG / BAJAJ / HAVELLS
Supply, installation, testing and commissioning of following light fittings complete with low loss electronic ballast, lamp holder, electrical connections by providing 3C x 1.5sqmm Cu. multistranded flexible wires, fixing & mounting accessories. All the fittings to be supplied with rated power lamps/CFL/LED etc., complete. Make : Philips/ Wipro/ Havells
Water proof LED luminaire surface/suspended mounted LED fitting 2x19 watts, Make- Philips model no- TCW450 P 2xTLED 19W P3397
38 W,LED Surface mounted light fittimg(2'x2') with Metalic CRCA powder coated body having 3500Lumen output similar /equivalent to make:Philips,Cat No.Fullglow RC380B LED25S-6500G4 L60 W60 PSUOO
15 W,LED Surface mounted down lighter with die cast aluminium constructuion having 1000Lumen output similar/equivalent to Make:Philips ,Cat No-DN170C LED10S-3000PSU WH 2560
9W, warm white, wall mounted LED batten with polycarbonate housing & integrated electronic driver,having 840 Lumen output similar / equivalent to Make : Havells cat No. LHEXBQP5IN1W009
36W, LED Surface mounted street light with die cast aluminium construction having 100Lumens/watt output, outdoor type, IP-65. similar / equivalent to Make : Philips, Cat No. BRP052 LED036 CW HP SLAFGS1PSUGR.
Bulk head LED for 6 watt,IP-66,surface mounted light(Ref Make-Philips,Cat No-WT20WLED6SNWPSU S2 PC)
POWER WIRING
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
(a)2 runs of 2.5 Sq.mm wires with 1 run of 1.5 Sq.mm in 25mm dia Conduit
(b)2 runs of 4 Sq.mm wires with 1 run of 2.5 Sq.mm in 25mm dia Conduit
Cable Trays
Supply and fixing of following size GI peroforated cable tray made out of 2mm thick MS sheet and the tray covered with 2mm thick MS cover including MS supports, Tee, bend, reducer for fixing the tray, anchor fasteners and including 2runs of 25 x 6mm GI strip along with cable tray etc., complete as required.
100mm W x 40mm H (1.6 mm)
150mm W x 40mm H
300mm W x 50mm H
Providing, laying and fixing 50 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required
Providing, laying and fixing 80 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required
Wiring for FLP Fixtures
Supply and wiring for 6A Socket outlet with 3core of 1.5sq.mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall/ceiling along with required accessories, supply and fixing of 6A 3 pin modular type socket with switch in anodised GI box and front plate complete with fixing accessories including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. as required. (FLP Type)
Supply, installation, testing and commissioning of 6/16A, 5 pin shuttered type socket controlled by one 16A modular switch of combination type with indication lamp including wiring with 3core of 2.5sq.mm FRLS insulated multistranded copper conductor cable laid in and including heavy gauge 25mm dia PVC conduit concealed in wall / ceiling along with required accessories from DB to socket, including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI switch box with modular switch, socket and the box covered with front plate. Cutting, chases in wall and making them good after fixing modular type switches as per requirement in sheet steel boxes of adequate sizes to accommodate switches, sockets, etc. complete as required. (FLP Type)
Supply and Wiring with the following size 1100V grade XLPE insulated Aluminium / Copper armoured conductor cables with FRLS outer sheath conforming to IS 7098 Part II on wall / ceiling / tray / pipe sleeves and excavated trenches including all accessories such as Flame proof junction boxes etc complete as required.
a)3C x 1.5sq.mm armoured (Copper)
b)3C x 2.5sq.mm armoured (Copper)
Provding end terminations for the cable specified below with Double compression type gland, Bi-Metalic lugs using crimping tool, Insulation tape, Identification tags etc. including end termination.
a)3C x 1.5sq.mm armoured (Copper)
b)3C x 2.5sq.mm armoured (Copper)
FLP FIXTURES & CABLING
FLP Fixtures
Supply, Installation, testing and commissioning of following FLP/Well Glass fixtures made out of Cast Aluminium alloy, toughened clear glass cemented into a bazel ring which is bolted to the body, and lamp holder with Insulator mounted on a bush plate and secured with screws. The body shall be finished with epoxy Grey stove enamelled outside and White inside. The fixture shall be inclusive of all accessories including lamp & control gear box containing Choke, condencer & igniter suitable for Lamp (Make : Sudhir/ Baliga/Shyaam)
a) FLP Bulk head LED for 20 watt with all fixing accessories, (Ref Make-Sudhir, Cat. No.FF/0124)
b) FLP Tube light LED for 2X18 watt with tube hanging & supporting rod accessories, (Ref Make-Sudhir, Cat. No.FF/1272 )
Supply, installation of 8 mm dia, MS hook in the slab for mounting FLP Well glass fixtures
Supply, installation, testing and commissioning of following rating FLP socket / switch Fuse units in FLP enclosure and plug top on angel iron frame work & other MS support structure complete with all fixing accessories, hardware etc. complete as required The FLP Sockets / SFUs shall be confirming to IP-65. (Make : Sudhir/ Baliga)
20A Single Phase 250V Grade FLP Socket with switch
32A THree Phase 500V Grade FLP Socket with switch
63A THree Phase 500V Grade FLP Socket with switch
100A Three Phase 500V Grade FLP Socket with switch
Supply & installation of FLP 4way Junction box of size 125 dia x 100mm depth suitable for 3/4" dia cable entries
Supply & installation of FLP 4way Junction box of size 200 dia x 150mm depth suitable for 1.25" dia cable entries
63A THree Phase 415V Grade FLP Switch Fuse Unit
32A THree Phase 415V Grade FLP Switch Fuse Unit
Supply, Installation, testing & commissioning of 305mm Sweep FLP Grade Exhaust fans with gravity louvers shutters including electrical connection, all fixing accessories/ installation materials as required, complete. (Make : Sudhir/ Baliga/Shyaam)
Supply, installation, testing and commissioning of 380mm sweep FLP Grade Wall Mounted fans including electrical connection, all fixing accessories/ installation materials as required, complete. (Make : Sudhir/ Baliga/Shyaam)
Supply, installation, testing and commissioning of SPN / TPN MCB Double Door Distribution Boards dust, water proof and vermin protected and rated for AC supply operation as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in flush with wall including cutting , chasing of wall make them good after fixing and other required civil works, all fixing materials required. MCBs shall conform to IS : 8828 and RCBO shall conform to IS : 12640. All MCBs shall be C Curve.
8 Way TPN MCB DB - FLP Type with 63A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 24 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way TPN MCB DB - FLP Type with 40A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 4 nos. 6 to 32A SP MCBs as outgoings as per SLD.
4 Way TPN MCB DB - FLP Type with 32A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
12 Way SPN MCB DB (Total 14way) - FLP Type with 63A, 30mA 2Pole RCBO as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
8 Way SPN MCB DB (Total 10way) - FLP Type with 40A, 30mA 2Pole RCBO as incomer and 8 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way SPN MCB DB (Total 8way) - FLP Type with 32A, 30mA 2Pole RCBO as incomer and 6 nos. 6 to 32A SP MCBs as outgoings as per SLD.
6 Way TPN MCB DB - Normal Type with 40A, 4P MCB, 3 nos 30mA DPole RCCB as incomer and 4 nos. 6 to 32A SP MCBs as outgoings as per SLD.
12 Way SPN MCB DB (Total 14way) - Normal Type with 63A, 30mA 2Pole RCBO as incomer and 12 nos. 6 to 32A SP MCBs as outgoings as per SLD.
MV Panels
Supply, installation, Testing and Commissioning of 3 phase and Neutral 415V 4 wire Free Standing Floor mounted MV panel made out of 14 SWG MS sheet after seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and colour coded with Heat shrinkable sleeves. The Metering shall be provided as specified.
Note:The capacitor panel shall also stipulate the following
All the capacitors shall be suitable for 525 V
Necessary control and firing card with proper wiring and lugs of the required rating to be provided.
Heavy duty exhaust fans to be provided for cooling Contactor
LED indication for number of capacitor banks ‘ON & Power Factor lagging or leading as per SLD.
The APFC shall be protected from following
ON, OFF indication and Push button to be provided as per SLD.
* over-voltage & voltage unbalance
* Over temperature-system should be in standby mode and automatically restart after above condition restored.
* Total Harmonic Distortion
* The capacitor panel shall be as per specifications.
Emergency push button and breaker control switch as per SLD
Supply, installation, testing & commissioning of MDB-Synthesis and instrumentation facility Block as described below :
INCOMER
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One(1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (MFM 6400 of Conzerv or equivalnet).
BUS-BAR
1 Set of 800A TP & 300amp for Neutral Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
5 No. 63A TPN MCB
9 Nos. 32A TPN MCB
2 Nos. 32A DP MCB
5 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 32A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 200A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 200/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 200A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
2 nos of 40 amp 25kA TP MCCB complete each with the following for 2x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB-Scale Up Facility - I & Scale Up Facility - II Blocks panel including Capacitor panel as described below:
INCOMER
1 No. 630A FP ATS with inbuilt controller (25 KA) ASCO-500 Series or equivalent.
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (MFM 6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
5 No. 63A TPN MCB
9 Nos. 32A TPN MCB
4 Nos. 32A DP MCB
6 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 32A TPN MCCB with VFD
CAPACITOR PANEL AS PER SLD.
INCOMER, METERING & INDICATION
1 Nos. 250A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 250/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 250A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
1 no of 63 amp 25kA TP MCCB complete each with the following for 1x20 kVAR capacitor bank.
1 no of 40 amp 25kA TP MCCB complete each with the following for 1x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 20 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB-SUFB panel as including capacitor panel described below: (One building additional same as SIFB)
INCOMER
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
5 No. 63A TPN MCB
9 Nos. 32A TPN MCB
4 Nos. 32A DP MCB
6 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 32A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 250A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 250/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 250A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
1 no of 63 amp 25kA TP MCCB complete each with the following for 1x20 kVAR capacitor bank.
1 no of 40 amp 25kA TP MCCB complete each with the following for 1x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 20 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - CPFB Sub Panel including capacitor panel as described below:
INCOMER
1 No. 630A FP ATS with inbuilt controller (25 KA) ASCO-500 Series or equivalent.
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
4 No. 63A TPN MCB
1 No. 40A TPN MCB
7 Nos. 32A TPN MCB
2 Nos. 32A DP MCB
7 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 63A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 200A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 200/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 200A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
2 nos of 40 amp 25kA TP MCCB complete each with the following for 2x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - FFB Panel including capacitor panel as described below:
INCOMER
1 No. 630A FP ATS with inbuilt controller (25 KA) ASCO-500 Series or equivalent.
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
3 No. 63A TPN MCB
1 No. 40A TPN MCB
10 Nos. 32A TPN MCB
5 Nos. 32A DP MCB
8 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 63A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 250A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 250/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 250A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
1 no of 63 amp 25kA TP MCCB complete each with the following for 1x25 kVAR capacitor bank.
1 no of 40 amp 25kA TP MCCB complete each with the following for 1x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 25 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - PETLFB Panel including capacitor panel as described below:
INCOMER
1 No. 630A FP ATS with inbuilt controller (25 KA) ASCO-500 Series or equivalent.
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
4 No. 63A TPN MCB
7 No. 40A TPN MCB
2 Nos. 32A DP MCB
6 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 63A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 160A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 160/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 200A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
2 nos of 63 amp 25kA TP MCCB complete each with the following for 2x25 kVAR capacitor bank.
1 no of 40 amp 25kA TP MCCB complete each with the following for 1x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 20, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - ECFB Panel including capacitor panel as described below:
INCOMER
1 No. 630A FP ATS with inbuilt controller (25 KA) ASCO-500 Series or equivalent.
1 No. 630A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 800A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
2 No. 63A TPN MCB
2 No. 40A TPN MCB
15 Nos. 32A TPN MCB
2 Nos. 32A DP MCB
8 Nos. 63A TPN RCBO(300mA)
2 Nos. 32A TPN RCBO(300mA)
1 Nos. 63A TPN MCCB with VFD
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 200A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 200/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 250A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 160 amp 25kA TP MCCB complete each with the following for 1x50 kVAR capacitor bank.
3 nos of 40 amp 25kA TP MCCB complete each with the following for 3x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of MDB - MTFB Panel including capacitor panel as described below:
INCOMER
1 No. 400A FP MCCB (25 KA) micro processor based with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.
1 set of 400/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
METERING & INDICATION
1 set of R,Y,B phase indicating lamps
1 Set- of ON/OFF/TRIP indicating lamps.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
BUS-BAR
1 Set of 500A TPN Aluminium Bus Bar with colour coded heat shrimkable PVC Sleeves
OUTGOINGS
All MCCB & MCB outgoing feeder shall be provided with ON/OFF indication lamps. The Number of outgoing feeders shall be as follows and as per SLD:-
1 No. 63A TPN MCB
14 Nos. 32A TPN MCB
2 Nos. 63A DP MCB
1 Nos. 40A DP MCB
2 Nos. 63A TPN RCBO(300mA)
CAPACITOR PANEL .
INCOMER, METERING & INDICATION
1 Nos. 160A TPN MCCB (25 KA)
1 No. 4 step-Microprocessor APFC controller/Relay shall continuously monitoring all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232/RS 485 port. Controller should mounted on the front side of the panel Capacitor bank having 3 phase MPP based mix dieelectric low loss ISI marked power capacitor.
One (1) No. multifunction meter (MFM) with Rs- 485 port suitable for measurement of voltage, current, power factor, frequency, Power (kW,kVA, kVAR), Energy (kWH, KVAH, KVARH) and Harmonics (EM-6400 of Conzerv or equivalent).
One (1) set 3 Nos. CT's of ratio 160/5A,15VA, Class 1.0 as required.
Terminals to receive XLPE insulated Aluminium cables
BUS-BAR
1 Set of 200A TPN Aluminium Bus Bar with colour coded PVC heat shinkable Sleeves
METERING & INDICATION
1 set of R,Y,B indicating lamps as per SLD each with 3 nos. 2A SP MCBs.
1 Set- of ON/OFF indicating lamps.
OUTGOINGS
1 no 100 amp 25kA TP MCCB complete each with the following for 1x25 kVAR capacitor bank.
2 nos of 40 amp 25kA TP MCCB complete each with the following for 2x10 kVAR capacitor bank.
1 no 20 amp 25kA TP MCCB complete each with the following for 1x5 kVAR capacitor bank.
3 pole capacitor grade contactor suitable for automatic switching of 50, 10 & 5 kVAR capacitor bank
Indicating lamp to give status of the circuit as per SLD
Manual/auto changeover switch
Hermetically sealed metallized polypropylene (MPP type) capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc. complete as required
Supply, installation, testing & commissioning of DG Panel (For Building no - 1,2 &3) Near Building-3
INCOMER FROM DG Set-300 kVA
1 Nos. 630A 4 pole , microprocessor based MDO, ACB with protection.
1 set of 630/5A, 15 VA, class-1 CTs for APFC relay
One (1) Set of SPD TYPE-2
Earth Fault, under voltage and over voltage protection to be considered in MCCB.
PLC, battery with charger shall be included as per SLD
1 Set- of ON/OFF/Trip/ Spring Charged & Trip circuit healthy indicating lamps.
240 V AC Motor wound spring closing mechanism
Phase sequence relay as per SLD
1 - 24 volts DC shunt trip coil
12 nos NO/NC contacts for remote opening & closing
Terminals to receive XLPE insulated Aluminium cables
1 No. reverse power relay.
Control wiring provision to sense the EB supply to start the DG set if the EB power is not available.
BUS BARS
Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 1600 amps having a maximum current density of 1 amp per sq mm suitable to withstand symmetrical fault level of 36 kA at 415 volts. The neutral busbar is to be of 50% capacity.
OUTGOINGS
2 Nos. 400A TPN MCCB (25 KA) - Micro Processor Based
1 Nos. 160A TPN MCCB (25 KA) - Thermal Magnetic based
1 Nos. 100A TPN MCCB (25 KA) - Thermal Magnetic based
Indication, protection and meter shall be as per SLD
Supply, installation, testing & commissioning of LT Isolator - Outdoor Type
OUTGOINGS
2 Nos. 400A TPN MCCB (25 KA) - Micro Processor Based
1 Nos. 160A TPN MCCB (25 KA) - Thermal Magnetic based
1 Nos. 100A TPN MCCB (25 KA) - Thermal Magnetic based
Indication, protection and meter shall be as per SLD
Supply, installation, testing & commissioning of LT Isolator - Outdoor Type
630A MCCB Isolator
1 no 630 Amps, 25 kA 4-P MCCB Isolator with suitable incomer and outgoing bus bar link and comprising of the following:
1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-630A) Ammeter with ASS with 3 nos. 630/5A Cl 1.0 CT's
Incoming and Outgoing Terminals to receive XLPE insulated aluminium conductor cables.
Suitable legs for mounting the panel.
Digital electronic KWH meter with RS 485 port.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc complete as required
Supply, installation, testing & commissioning of LT Isolator - Outdoor Type
400A MCCB Isolator
1 no 400 Amps, 25 kA 4-P MCCB Isolator with suitable incomer and outgoing bus bar link and comprising of the following:
1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-400A) Ammeter with ASS with 3 nos. 400/5A Cl 1.0 CT's
Incoming and Outgoing Terminals to receive XLPE insulated aluminium conductor cables.
Suitable legs for mounting the panel.
Digital electronic KWH meter with RS 485 port.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc complete as required
630A MCCB Isolator
1 no 630 Amps, 25 kA 4-P MCCB Isolator with suitable incomer and outgoing bus bar link and comprising of the following:
1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-630A) Ammeter with ASS with 3 nos. 630/5A Cl 1.0 CT's
Incoming and Outgoing Terminals to receive XLPE insulated aluminium conductor cables.
Suitable legs for mounting the panel.
Digital electronic KWH meter with RS 485 port.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc complete as required
Supply, installation, testing & commissioning of LT Isolator - Outdoor Type
400A MCCB Isolator
1 no 400 Amps, 25 kA 4-P MCCB Isolator with suitable incomer and outgoing bus bar link and comprising of the following:
1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-400A) Ammeter with ASS with 3 nos. 400/5A Cl 1.0 CT's
Incoming and Outgoing Terminals to receive XLPE insulated aluminium conductor cables.
Suitable legs for mounting the panel.
Digital electronic KWH meter with RS 485 port.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels etc complete as required
MV Cables
Supply, laying, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium/copper conductor cable, in built up cable trench/ already laid RCC hume pipe / cable tray with all installation materials. When the cable is to be laid in ground, the same shall be laid at a depth of 750mm below ground level including excavation in all kind of soil, SDR & HR, refilling of earth after cables are laid, providing protection with sand cushioning at bottom and bricks at sides & top, cable route markers at every 15mtr. interval also at the turnings & joints and identification tag at both the ends etc., complete. The cable shall conform to IS 7098/ Part II
3.5C X 300 Sq.mm aluminium armoured laid in ground
3.5C X 240 Sq.mm aluminium armoured laid in ground
4C X 16 Sq.mm Copper armoured
4C X 10 Sq.mm Copper armoured
4C X 6 Sq.mm Copper armoured
3C X 10 Sq.mm Copper armoured
3C X 6 Sq.mm Copper armoured
3C X 4 Sq.mm Copper armoured
Control Cable
4 C x 2.5 sq.mm control cable(LS)
7 C x 2.5 sq.mm control cable(LS)
12 C x 2.5 sq.mm control cable(LS)
Providing end terminations for the cable specified below with Double compression type gland, Bi-Metalic lugs using crimping tool, Insulation tape, Identification tags etc. including end termination.
3.5C X 300 Sq.mm aluminium armoured
3.5C X 240 Sq.mm aluminium armoured
4C X 16 Sq.mm Copper armoured
4C X 10 Sq.mm Copper armoured
4C X 6 Sq.mm Copper armoured
3C X 10 Sq.mm Copper armoured
3C X 6 Sq.mm Copper armoured
3C X 4 Sq.mm Copper armoured
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
a) 150mm dia
b) 300mm dia
TOTAL OF SUB HEAD XIV
SUB HEAD-XIII: LIGHTNING CONDUCTOR
Lightning Protection System
Supply and installation of vertical air termination with 40mm dia copper hollow sphere with spikes, fixed on 1000mm length 25mm dia Copper rod including PCC block and all fixing accessories.
Supply and fixing of weather proof 14 SWG GI test link box of size 150 x 100 x 100 mm along with all fixing accessories etc., complete.
SUB HEAD XIV : TELEPHONE & LAN WIRING
Supply and installation of 50 Pair Krone connectors in MS box complete as required.
Supply and installation of 20 Pair Krone connectors in MS box complete as required.
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate etc. complete as required
Supply and laying of 50 pair 0.5mm dia Copper conductor, Jelly filled, armoured cable including excavation brick protection, backfilling, sand cushioning with all accessories complete etc., (Assumed Length - From Nearest Telephone Exchange)
Supply and laying of 20 pair 0.5mm dia Copper conductor, Jelly filled, armoured cable including excavation brick protection, backfilling, sand cushioning with all accessories complete etc.,
Supply and laying of 2 Pair 0.5mm dia PVC insulated unarmoured copper conductor Telephone wire conforming to DOT Specifications in existing /already laid PVC pipes.
Supply & fixing of UTP Cat-6 1 Module Socket with shutter in a box with front plate and concealed in manner by cutting chasing in walls and making them good after fixing socket, etc., complete as required.
Supply and laying of CAT-6 UTP data cable (Yellow) conforming to DOT Specifications in existing /already laid PVC pipes.
Supplying and fixing of 20 MM Dia. of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (For 2 Pair Telephone Cables)
Supply & fixing of 1" Casing Caping / Flexible / PVC Pipe for LAN Cabling
Supply , Installation, Testing and Commissioning of Core Switch should have Min 24 x100/1000X SFP port , Min 8x10/100/1000T port , Min 4 X 10 G Based SFP+ port, 2x Stacking port comprising 128 Gbps of stacking bandwidth from day 1, Support less than 50 Millisecond convergence based of RFC 3619./REP/G.8032, Min Operating temp 0-500 C, Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB, CE.2 and CB certified.
Supply, Installation, Testing & Commissioning of Access switch should have 16 x10/100/1000T port , Min 8 x1 G SFP port , should be upgradable to Min 4x 10 G based SFP+ port , 2x Stacking port comprising 40 Gbps of stacking bandwidth from day 1, Support less than 50 Millisecond convergence based of RFC 3619/REP/G.8032, Min Operating temp 0-50 Degree C, Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and CB certified.
Supply, Installation, Testing & Commissioning of fiber Modules 1000 Base.
Supply, Installtion, Testing and Comissioning of armoured 6 core Singlemode OFC cable for interfloor switches connectivity.
Supply , Installtion, Testing and Comissioning of 16 port loaded LIU with LC adaptor plates, pigtel cables etc complete as required.
Supply , Installtion , Testing and Comissioning of 24 port loaded LIU for with LC adaptor plates , pigtel cables for core switch to access switch connectivity over fiber.
Supply, Installtion, Testing and Comissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity.
SUB HEAD-XV:FURNITURE & FURNISHING
Supply of computer chair of size 510 X 410 X 800mm high having with PU arms seatwith moulded 12mm hot pressed ply with 50mm thick cushion in seat & Back.upholstered with approved qualty of fabric,mounted on five castors hydraulic gas lift pedestal etc,all complete.(M/s Gradej 7046 R OR Equivalent)
Supply of computer table of size 1200 x 600 x 750 made out of 18mm thick plywood with 1 mm thick lamination of approved shade and top to have 18mmthick postformed board of approved shade with keyboard slide and provision for CPU with one draw and one cupboard complete with spirit polish.
Supply of office table of size 1350 x 600 x 750mm height made out of 14mm thick plywood plastic board of both sides,. 1 Nos drawers ride on telescopic channels ,one cupboard with locking arrangement and foot rest,all exposed edges with wooden lipping and spirit polish etc,complete.
Supply of standard steel Almirah large of size 1980 x 910 x 480mm with multibend construction and interlocking design and full length overlapping doors.Almirah to be finished with enamel paint top,bottom LH & RH sides and back material to be with 22 gauge MA sheets .Door to have stiffner material and almirah to have adjustable shelves made of 20 gauge MS sheet with locking arrangement complete.
Supply of standard steel Almirah medium of size 1266 x 750 x 430mm with multibend construction and interlocking design and full length overlapping doors.Almirah to be finished with enamel paint top,bottom LH & RH sides and back material to be with 22 gauge MA sheets .Door to have stiffner material and almirah to have 3nos shelves made of 20 gauge MS sheet with locking arrangement complete.
Slotted Angle Steel racks 2000x900x400
Supply of High Back Chairs with synchronized tilting mechanism ,360 revolving and titling type with multiple locking systems , fixed back, fixed arms , gas lift for height adjustment, including approved castors etc complete. i) High back (Featherlite )or equivalent model of Godrej make/equivalent make.Model No-PCH-9200R)
Laboratory work bench of size 600mm X 770mm with storage unit under the worktop with Wooden Stool size of 300 x 300 x 750 mm as per instructed by Engineer-In Charge
Providing and supplying working tables of specified size of 1199 x 590 x 750 mm made of 18 mm thick Commercial plywood for top, side support, drawer unit, drawer facia. 12 mm thk. commercial plywood for table appron, drawer sides and back, 6 mm thk. commercial plywood for drawer bottoms. All internal surfaces of table, appron, drawers, (all sides, bottom and top ) drawer box to be finished with 0.8 mm thk. approved floor white colour laminate. All external surfaces of Table including top, sides, drawer box, drawer facia to be finished with approved colour and design with 4 mm thk. veneer finished with 2 coats of melamine polishing work finished in partly glossy as per manufacturers specifications. All drawer to run on approved quality telescopic drawer channels of HAFELE, HETTICH , EBCO or approved equivalent etc Complete in all respect including approved quality metal keyboard with telescopic channel, Godrej/ Ebco drawer locks, 'D' shape .S.S. brass bush finished handles for drawers.foot rest with melamine polishing as per design/ drawing and instructed by Engineer-In Charge
SPECIAL ITEM OF WORK
SUB HEAD-XVI: AIR CONDITIONING
EQUIPMENTS (VRV/VRF) :
Variable Refrigerant Flow System with Heating & Cooling both
SITC of Complete VRV/VRF system with Comprising of Indoor & Outdoor units complete with insulated copper refrigerant piping, cabling electrical switch gear, drain piping, testing & CFC free gas charging .Scroll compressors shall be hermetically sealed Inverter driven type, with electronic controls capable of loading & unloading approx. between 10% capacity to 100% capacity of the unit, condenser coils with anti corrosive blue fins, axial flow fans, microprocessor based controller, etc. shall be fully weather proof , factory assembled & prewired with all accessories & electronics & refrigerant controls housed in a powder coated MS sheet metal housing of the following actual capacity Outdoor units shall be capable to operate at Ambient Condition of 105.0ºF DB/76.0ºF WB (As per Pune).The Units Shall be capable to provide cooling & heating . The Units Should be as per detailed technical specification & drawings including first topup of refrigeratore
Notes:
Outdoor Unit
Outdoor units shall have cooling & heating mode, consisting of one/multiple modules with digital vapour injection/inverter scroll technology based compressor and environment friendly refrigerant R-410A only. The unit should have COP as per ASHRAE 90.1 (Latest standard) . The C.O.P confirmation should be from the O.E.M letter, for the following capacities.The cost shall include the cost of Cabling from MCB/ELCB/isolator to the outdoor unit. (Cable Length to be as per drawing).Isolator cost shall also include.The unit shall be provided with its own microprocessor control panel with provision for integration with the building management system for Air-conditioning system.The units shall be suitable for 415V±10%,50 Hz. supply & complete with electrical controls & panels. Cost of Cowl with Birdscreen(If Required ) for Top Discharge outdoor unit shall also include ,requirement of cowl to be verified by the HVAC Vendor as per drawing /site conditions &cost of MS stand for ODUs should also considered. Below Outdoor units are Top Discharge ,However HVAC Vendor is suggeted to verify their performance .
ODUs NO= ODU-01 ; Capacity(MODULE)= 32HP( 18+14) ; Serving Area/Mode = Synthesis & instrumentation facility ; Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-02 ; Capacity(MODULE)= 28 HP (14+14) ; Serving Area/Mode = Scale up facility , Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-03 ; Capacity(MODULE)= 18HP ; Serving Area/Mode = Utility room ; Purpose = Cooling ; Category of indoor units = VRF ductable units
ODUs NO= ODU-04 ; Capacity(MODULE)= 46HP(16+16+14) ; Serving Area/Mode = Performance evalution tesing facility ; Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-05 ; Capacity(MODULE)= 40 HP (14+14+12) ; Serving Area/Mode =Mechanical testing facility ; Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-07 ; Capacity(MODULE)= 30 HP (16+14) , Serving Area/Mode = filling facility ; , Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-08 ; Capacity(MODULE)= 12HP , Serving Area/Mode =Utility room ; Purpose = Cooling ; Category of indoor units = VRF ductable units
ODUs NO= ODU-09 ; Capacity(MODULE)= 40 HP (14+14+12), Serving Area/Mode =Composition preparation room ; Purpose = Cooling & heating ; Category of indoor units = DX- FMAHU
ODUs NO= ODU-11 ; Capacity(MODULE)= 20HP , Serving Area/Mode = Environmental chamber facility , Purpose = Cooling ; Category of indoor units = VRF ductable units
Ceiling Mounted VRF Cassette/VRF Ductable (Indoor Unit)
Supply,Installation, Testing & Commissioning of cassette/VRF ductable type indoor units equipped with all accessories including drain pump kit including supporting arrangement etc. as per specifications & drawings.The cost shall include the cost of power & control cabling & earthing from ODUs to Indoor Units as as per drawing including plug top suitable for 15 A/3 pins socket. Indoor unit should have capability to provide cooling only.
The units shall be suitable for 230V±6%, 50 Hz. supply & complete with electrical controls & panels.
Area= Scale up facility ; Location= Utility room , Deh. CFM - 2541 ; TR - 7.96 ; Type = ductable
Area= Mechanical Testing facility ; Location= Control room , Deh. CFM - 1376 ; TR - 4.0 ; Type = ductable
Area= Mechanical Testing facility ; Location= Operator room , Deh. CFM - 1376 ; TR - 4.0 ; Type = ductable
Area= Mechanical Testing facility ; Location= Tower Control room , Deh. CFM - 1376 ; TR - 4.00 ; Type = ductable
Area= Filling facility ; Location= Control room , Deh. CFM - 1050 ; TR - 4.00 ; Type = cassette
Area= Filling facility ; Location= Engg. room , Deh. CFM - 1050 ; TR - 4.00 ; Type = cassette
Area= Composition Preparation room ; Location= Control room , Deh. CFM - 917 ; TR - 3.10 ; Type = cassette
Area= Composition Preparation room ; Location= Operator room , Deh. CFM - 917 ; TR - 3.10 ; Type = cassette
Area= Composition Preparation room ; Location= Engg. room , Deh. CFM - 1050 ; TR - 4.00 ; Type = cassette
Area= Environmental Chamber facility ; Location= Control room , Deh. CFM - 2541 ; TR - 7.96 ; Type = ductable
Area= Environmental Chamber facility ; Location= Operator room , Deh. CFM - 1376 ; TR - 4.00 ; Type = ductable
HORIZONTAL AIR HANDLING UNITS WITH VFD (FLOOR MOUNTED DOUBLE SKIN WITH THERMAL BREAKS) & COMPATIBLE WITH VRV/VRF:
Supply, Installation, Testing & Commissioning of double skin floor mounted Air Handling unit having following specifications:-
All the AHUs shall be VRV/VRF Compatible.
Customized AHU unit should have capability to provide cooling(Summer) ,heating (winter) & reheat along with cooling(monsoon) .
Casing & Fan Section
Double Skin with 0.63 mm thick galvanized steel sheet inner skin and 0.63 mm thick Pte-coated sheet outer skin floor mounted air handling units with thermal break profile with 43 mm thick PUF insulation panel having density 38-40 kg/m3 consisting of direct Centrifugal plug fan (spark proof),motor -IE02(flame proof), motor mounting arrangement and vibration insulators, fire retardant double flexible connections as required etc complete as per specifications and drawings. All AHUs shall have stainless steel drain pan with sandwiched insulation. Filter shall be washable type. AHU should be provided with mixing box having same casing thickness as for AHU.
Cooling Coils :
Air Filter :
Filter section with Washable type Pre filter having efficiency 90% down to 10micron @ 500FPM velocity. Filter shall be UL 900 listed class 1 or class 2.
Fine filter with efficiency of 99% down to 5 micron as per EU Class 7
Customized AHU unit should have capability to provide cooling & Heating both .
Accessories:
VFD,Fire retardant & water proof double flexible connection between fan outlet & duct, vibration isolator, weather proof light in fan section, limit switch, wire guard, glass window in fan section box, & AHU kit connection compatible to connect with VRV/VRF based outdoor units & all other necessarily accessories required to operate the unit.
Humidification section: AHUs shall be provided with humidification section at discharge side
Reheating Section: AHUs shall be provided with reheating section with tubler heater (flame proof juction box) just after DX coil. These tubler heater shall be suitable for explosive area. Same shall be controlled with humidistate.
AHU-No = FM AHU-01 ; TYPE = Customized FM AHU; Space Name = Synthesis & Instrumentation Facility ; Deh. Deh. CFM = 5350 ; TR= 41.00 ; Reheat(KW) = 4.00 ; SP mm wg= 100
AHU-No = FM AHU-02 ; TYPE = Customized FM AHU; Space Name = Scale Up Facility ; Deh. CFM = 5350 ; TR= 41.00 ; Reheat(KW) = 4.00 ; SP mm wg= 100
AHU-No = FM AHU-03 ; TYPE = Customized FM AHU; Space Name = Performance evalution testing facility ; Deh. CFM = 13500 ; TR= 65.00 ; Reheat(KW) = 11.00 ; SP mm wg= 100
AHU-No = FM AHU-04 ; TYPE = Customized FM AHU; Space Name = Mechanical testing Facility ; Deh. CFM = 10900 ; TR= 54.00 ; Reheat(KW) = 9.00; SP mm wg= 100
AHU-No = FM AHU-05 ; TYPE = Customized FM AHU ; Space Name = Filling Facility ; Deh. CFM = 8600 ; TR= 40.00 ; Reheat(KW) = 7.00; SP mm wg= 100
AHU-No = FM AHU-06 ; TYPE = Customized FM AHU ; Space Name = Composition Preperation Facility ; Deh. CFM = 7500 ; TR= 55.00 ; Reheat(KW) = 6.00 ; SP mm wg= 100
HORIZONTAL FLOOR MOUNTED EXHAUST FAN SECTION :
EFS-No = EFS-01, TYPE = Floor Mounted , Space Name = Synthesis & Instrumentation facility, Deh.CFM = 6200 , SP mm wg = 35
EFS-No = EFS-02, TYPE = Floor Mounted , Space Name = Scale up facility, Deh.CFM = 5350 , SP mm wg = 35
EFS-No = EFS-03, TYPE = Floor Mounted , Space Name = Performance evalution testing facility, Deh.CFM = 6750 , SP mm wg = 35
EFS-No = EFS-04, TYPE = Floor Mounted , Space Name = Mechanical testing facility, Deh.CFM = 5450 , SP mm wg = 35
EFS-No = EFS-05, TYPE = Floor Mounted , Space Name = Filling facility, Deh.CFM = 4300 , SP mm wg = 35
EFS-No = EFS-06, TYPE = Floor Mounted , Space Name = Composition preperation facility, Deh.CFM = 7500 , SP mm wg = 35
ULTRASONIC HUMIDIFIER :
Supply, installation, testing and commissioning of Ultrasonic humidifier constructed out of 1.5 MM thick SS sheet complete with level switch, filter assembly, motorised valve with timer for auto flushing, and mist outlet fan. Unit to be supplied with control panel, all necessary safety interlocks, instrumentation digital humidistat and display.
UH-No = UH-01 ; TYPE = Ultrasonic ; Space Name = Synthesis & Instrumentation facility ; Capacity = 32 KW
UH-No = UH-02 ; TYPE = Ultrasonic ; Space Name = Scale up facility ; Capacity = 32 KW
UH-No = UH-03 ; TYPE = Ultrasonic ; Space Name = Performance evalution testing facility ; Capacity = 38 KW
UH-No = UH-04 ; TYPE = Ultrasonic ; Space Name = Mechanical testing facility ; Capacity = 32 KW
UH-No = UH-05 ; TYPE = Ultrasonic ; Space Name = Filling facility ; Capacity = 22 KW
UH-No = UH-06 ; TYPE = Ultrasonic ; Space Name = Composition preperation facility ; Capacity = 40 KW
REFRIGERANT PIPING:
Supply, Installation and testing of interconnect refrigerant copper piping with fitting duly insulated with 19/13 mm thick closed cell Class O elastometric nitrile rubber tubular insulation of minimum density not be less than 33+/- Kg/ cum between each set of indoor & outdoor units as per specification. All copper tubes shall be coated with transparent anti corrosive primer before insulation.Covered Cable tray should be used for exposed refrigerant copper piping and tightened with self threaded screw. The insulation should be mechanically protected with a coat of polyshield of approved colour (starbond 30-36 or equivalent) of minimum 5 mil thickness.
9.53 mm dia with 13mm thick nitrile rubber insulation
12.7 mm dia with 13mm thick nitrile rubber insulation
15.86 mm dia with 13mm thick nitrile rubber insulation
19.05 mm dia with 13 mm thick nitrile rubber insulation
22.2 mm dia with 19 mm thick nitrile rubber insulation
28.52 mm dia with 19 mm thick nitrile rubber insulation
34.9 mm dia with 19 mm thick nitrile rubber insulation
41.3 mm dia with 19 mm thick nitrile rubber insulation
DRAIN PIPES OF INDOOR UNITS :
Supplying, laying, fixing, testing & commissioning of composite UPVC pipes (Upto floor level for AHU/CSU ) Density not less than 10kg/m3 complete with 6 mm thick nitrile rubber insulation & all necessary fittings such as elbows, tees, reducers U-trap, supports, clamps etc. as per specification & drawings.
Note: Drain pipe shall run on GSS drain pan for preventing from the water leakage on floor
25 mm dia
32 mm dia
40 mm dia
50 mm dia
Corded Remote controller with controls of temperature/RH set up, louver set up airflow mode for FMAHU,FMTFA.
Corded Remote controller with controls of temperature set up, louver set up airflow mode for CSAHU,CSTFA & Ductable Units.
Installation, Testing & Commissioning of Imported Control Systems & Y-Joints :
Y-Joints & Headers -ODU -IDU
T-Joints & Headers -ODU -IDU
Centralized Remote Controller Touch Screen type suitable for operating all the IDU's through this controller &.compatible to BMS
2 Core Shielded communication wire in Conduit between each and every outdoor to indoor units .
AIR DISTRIBUTION:
SHEET METAL DUCT
Supply, fabrication, installation and testing of factory fabricated sheet metal ducts of following thickness including necessary wire supports, hangers, nut & bolts, gaskets, splitter dampers, vanes, etc complete as per specifications in accordance with the approved shop drawings factory fabricated as per IS:655/SMACNA Standard.
24 gauge galvanised sheet
22 gauge galvanised sheet
18 gauge galvanised sheet
VOLUME CONTROL DAMPER:
Supply, Installation and Testing of GI volume control dampers having 20 Gauge GI frame & 24 Gauge Louver within ducts complete with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of air distribution system..
MOTORISED SMOKE & FIRE DAMPER (UL555 & UL555S) :
Supply, installation & testing of motorised smoke cum fire dampers of approved make with a temperature upto 300C for 2 hours fire rating as per the specifications. The fire damper shall be complete with electronic temperature sensor and electrically operated actuator. The fire damper shall be located in the supply/return air ducts. The control panel will be such located that the reset can be done easily.
Fire Dampers
Actuators
SUPPLY AIR GRILLE (DOUBLE DEFLECTION LOUVERS) :
Supply, Installation, Testing and Balancing of Aluminum extruded powder coated grills with key oprated volume control dampersas per approved shop drawings & approved samples having 20 Gauge GI frame & 24 Gauge GI louvers.
RETURN AIR GRILLE (SINGLE DEFLECTION LOUVERS) :
Supply, Installation, Testing and Balancing of Aluminum extruded powder coated grills with key oprated volume control dampersas per approved shop drawings & approved samples having 20 Gauge GI frame & 24 Gauge GI louvers.
INSULATION:
ACOUSTIC LINING :
Supply, Installation & Testing of acoustic lining within supply and return air ducts as per detailed specifications. All ducts shown cross hatched on the approved shop drawings shall be provided with acoustic lining with 25 mm thick resin bonded fibre glass insulation of density 32 Kg/m3 over GI frame work & covered with 26 gauge perforated aluminium sheet of 30% perforation with GI screws.
25 mm thick acoustic lining
THERMAL INSULATION:
Supply, Installation & Testing of thermal insulation on Air Conditioning ducts with Class O closed cell Elastomeric Nitrile Insulation duly mechanically protected with factory laminated glass cloth density 40 to 60 kg/cum. Thermal conductivity 0.033w/m deg C at 0 degC. Temperature range 40 to 105deg C. Thickness of insulation shall be as under:-
Return Air ducts within the Building - 13mm thick
Supply Air ducts within the Building - 19mm thick
All exposed ducts within the Building - 25mm thick
SPLIT UNITS Supply, Installation, testing and commissioning of following capacity Hi Wall type split air-conditioning unit suitable to operate between 180-260 volt, 50 Hz, 1 phase power supply, with air-cooled evaporator with coil, fan, and fan motor, air-cooled condenser with hermetically sealed rotary/ scroll compressor(with R-410a/R-32/R-407c/R-134a), condenser coil, propeller fans controls, control panel between ODU to IDU, including control wiring,cordless remote, Necessary supporting arrangement for indoor unit, M.S. frame duly Powder Coated/ Epoxy painted as per approved shade by architect to locate Outdoor Unit with necessary vibration isolation arrangement as per site condition etc. The Unit should be at least 3 Star rated (on the date of procurements, the minimum EER value of the units should be as per ECBC-2017). The Refrigerant pipe size and gas quantity should suit to the copper pipe length at actual. The capacity guarantee should be ensured by the manufacturer. The provided unit should have inbuilt automatic voltage stabilizer with time delay realy.
Civil Work such as wall hole making , wall chisling ,refilling of chiseling part with mortar etc as per site condition. Nitrogen pressure testing for leakages & flushing during installation & after commissioning between IDU & ODU with flare nuts The Outdoor unit Compressor must be provided with 5 Year Warranty Period. 1.5 TR Split A/c
Civil Work such as wall hole making , wall chisling ,refilling of chiseling part with mortar etc as per site condition. Nitrogen pressure testing for leakages & flushing during installation & after commissioning between IDU & ODU with flare nuts The Outdoor unit Compressor must be provided with 5 Year Warranty Period. 2.0 TR Split A/c
SUB HEAD-XVII: WATER COOLERS
Aquagard Cooler cum purifier providing seven styage purification , the newAquagard pure chill to storage cooler cum purifier with is one of a kind purification technology (RO), with cooling and storage solution of following specification Approximate External Dinension (WXDXH) 640*450*1350mm Running Curent in Amps (Max)-4.5+10% Power in watts (Max)-700+10%Water Storage Tank Capacity -80 Ltr Capacity with Comfoooor level Water Oultel Temperature at 17C +1 C 60 Ltr. Cmpressor -Maake Copeland or tecumesh refigerant- Freon22 StaggeDDeltails- 1 Particculate FFilter 2. Precarbon Block Filter3. Anti Scakant filter 4. Sediment Filter 5. Reverse Osmisis Membrane filter 6. Post Carbon Block Filter 7. Nano Dilver Leaching filter RO membrance Rating 4 no X 75 GDP or Quivalent Make-Eureka forbes/vottas/Blue Star/Usha
SUB HEAD-XVIII: SPECIAL EARTHING
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt complete as per manufactureres specifications & as directed by Engineer-in-charge. (For ESDS, PSDS Systems, PLC Room, Control Block, 2 Nos. Extra For Future Expansion)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt complete as per manufactureres specifications & as directed by Engineer-in-charge. (For Electrical systems, Lightning Protection system, 2 Nos. Extra For Future Expansion)
Supply and laying of following size earth strips including excavation at a depth of 500mm and refilling of earth when laid in ground and with all fixing accessories including DMC insulators, 150 x 150 x 100mm PCC blocks wherever required when laid on the wall / Ceiling / Surface with necessary interconnections by providing GI bolt & nuts with earth station, joints and equipment's etc., complete.
25 X 3 mm CU Strip laid in ground
25 X 3 mm CU Strip laid in ground through 75mm HDPE Pipe
25 X 3 mm CU Strip conductor with DMC Insulated Supports
50 X 6 mm GI Strip laid in ground
32 X 6 mm GI Strip laid in ground through 75mm HDPE Pipe
32 X 6 mm GI Strip conductor with DMC Insulated Supports
32 X 6 mm AL Strip conductor with DMC Insulated Supports
8 SWG GI wire
6 Sqmm. Cu. Multistrand Flexible wire
25 X 3 mm GI Strip laid in ground
Supply and fixing of Static Discharge Handles made out of 32mm dia Copper rod fixed on wall with brass spacers and conected to 25x3mm copper strip by brazing.
Supply, installation, testing and commissioning of Static Discharge Meter fixed on wall with 25x3mm copper strip by brazing etc., complete
SUB HEAD -XIX : DG SET
Supply, installation, testing & commissioning of 200 KVA continuous rating (Prime power), 415 V, 3 phase, 4 wire, 50 Hz at 0.8 P.F, 1500 RPM, radiator cooled, silent diesel generating set along with complete fuel piping with accessories, anti vibration mounts, base frame, required hardware, Batteries, Engine control panel with accessories, residential silencer, flexible connection, bellow/expansion joints etc. with all associated equipment/work as per specifications to make the DG set installation complete in all respects as per site requirement.
Supply, installation, testing & commissioning of 100 KVA continuous rating (Prime power), 415 V, 3 phase, 4 wire, 50 Hz at 0.8 P.F, 1500 RPM, radiator cooled, silent diesel generating set along with complete fuel piping with accessories, anti vibration mounts, base frame, required hardware, Batteries, Engine control panel with accessories, residential silencer, flexible connection, bellow/expansion joints etc. with all associated equipment/work as per specifications to make the DG set installation complete in all respects as per site requirement.
Engine & Alternator to be designed for 40 degree ambient temperature and the Alternator shall be with H class insulation.
Silencer shall be with 75mm thick insulation.
Note: Crane / Scaffolding as required for installation of the DG set & flue pipes shall be considered in scope.
DG set shall be supplied with built-in acoustic enclosure as per latest pollution control board norms and as per specifications, complete in all respects.
The DG Set shall be complete with PCC (Power Command Control) or equivalent DG Controller module suitable for AMF (auto-mains failure), Auto Load Sharing, electro-mechanical interlock & Interface with ATS & MCCB switching, Auto load sensing and Auto load Management, including communication card and networking gateway and software as required.
Supply, installation, testing & commissioning of additional 990 liters capacity day oil storage tank (External) fabricated from 4 mm thick MS plates. Tank shall include 450 mm manhole cover, level indicator with duly calibrated scale and flanged connection for inlet, outlet, overflow, drain and probe provision for level controller & breather.
Supply, installation, testing & commissioning of MS Class-B (Medium) exhaust pipe (5 mts length from DG set canopy top) as per IS:1239 and all fixing accessories and hardware. The exhaust pipes shall be insulated with required thickness rockwool mattress / blanket insulation wrapped in chicken mesh and cladded with required gauge aluminium sheet including all structural supports as required for site condition and as per calculations / specifications. Support of the exhaust pipe as per CPCB norms shall be inclussive.
SUB HEAD-XX: FIRE ALARM SYSTEM
Supply ,erection ,testing and commissioning of G.I. Above ground pipes ,for delgue system,as per IS 1239(H) upto 150NB including fittings,accessories etc,complete of following sizes:-
Supply ,erection ,testing and commissioning of M.S. Above ground pipes ,for delgue system,as per IS 1239(H) upto 150NB including fittings,accessories etc,complete of following sizes:-
Supply and laying of 25mm dia MS conduit 16SGW concealed in wall /ceiling/floor including all accessories such as junction boxes conduit bends etc completed as required etc.
Supply,erection testing and commisioing of 80 NB D-Pack deluge system (skid mounted pre assembley deluge system enclosed in a cabinet with front opening)consisting of delgue valve with all accessories ,pressure gauge,solenoid valve,water motor gun,2 isolation valve and one by pass butterfly valve internal piping and common drain etc complete UL/FM approved with all accessories etc complete.
Supply,erection, testing and commisioing of 50 NB D-Pack deluge system (skid mounted pre assembley deluge system enclosed in a cabinet with front opening)consisting of delgue valve with all accessories ,pressure gauge,solenoid valve,water motor gun,2 isolation valve and one by pass butterfly valve internal piping and common drain etc complete UL/FM approved with all accessories etc complete.
Supply,erection, testing and commisioning of MV water spary nozzles ,for the deluge system suitable to provide water spray at minimum 2.5 radius at inlet pressure of 2.5 to 3kg/cm2 stainless steel constructuion,K factor 80 ,threaded inlet,spray angle-100 deg ,complete UL/FM approved.
Supply, installation, testing and commissioning of HV water curtain nozzles, for the deluge system, inlet pressure of 2.5-3 kg/cm2,stainless steel constructuion, K-factor - 80, threaded inlet, complete UL/FM approved.
Supply,erection,testing and commissioning of manual call point
Supply,erection ,testing and commissioning of hooter
Supply, Erection, Testing and Commissioning of horizontal mounted Siren, 2.5 Km radius including Electrical connections etc., complete.
Supply, Erection, Testing and Commissioning of analogue addressable Fire Alarm control Panel (UL-FM approved) with integrated PA system. The fire alarm panel is designed to detect the fire through the fire detectors and process them into suitable audio – visual alarms, activate devices related to fire extinguishing systems, communicate to other Fire Alarm panels on peer to peer basis suitable for single mode optical fiber connectivity all necessary module/converter to be added for OFC connection.etc complete
Supply and laying of armoured FRLS Cables for detectors to FA Panel, Panel to hooters, manual call points, deluge valves, siren etc and of size 4c x 1.5 sqmm twisted pair shielded Copper armoured cable including termination, electrical connection etc complete.
Supply, Erection, Testing and Commissioning of C.I. Butterfly Valves, of NP 1.6 class complete with GI coated bolts and nuts and rubber insertions all etc., complete.
Supply and erection testing and commissioning of gun metal gate valve of size 50mm with all accessories etc complete
Supply, Erection, Testing and Commissioning of combined UV/IR detectors (UL-FM approved), 120º cone of vision, Range min. 15Mtr, explosion proof construction, 24 V DC, Aluminium Housing complete with swivel mount, output module etc., complete.
SUB HEAD-XXI: CCTV System
Supply, installation, testing & commissioning of Vandal resistant IP 67 mini IR Dome Network camera Full HD 5 MP, ONVIF profile S , G& T ,UL , CE , FCC Certified ,1/2.8” Progressive Scan CMOS ,2.7 mm to 12 mm motorized varifocal lens , Quad stream with each stream support H.265+ compression simultaneously ,min illumination : 0.01 Lux @ (F1.2,AGC ON), 0 Lux with IR , Shutter speed : 1 / 5s ~ 1 / 100,000 s ,120 dB WDR , Compression : H.265+ ,H.265 ,H.264+ H.264 .SD card support upto 128GB , Alarm trigger - 1 input / 1 output , frame rate : Main stream should support 25 fps@5MP ,Edge analytics : line crossing , perimeter intrusion ,Face detection(deep learning) , pedestrian detection ,cross counting , stationary object , In built IR LED , IR Distance upto 40 meters , IK10 ,POE.
Supply, installation, testing & commissioning of Vandal resistant IP 67 mini IR Bullet Network camera Full HD 5 MP , ONVIF profile S ,G & T . UL , CE , FCC Certified ,1/2.8” Progressive Scan CMOS ,2.7 mm to 12 mm motorized varifocal lens , Quad stream with each stream support H.265+ compression simultaneously ,min illumination : 0.01 Lux @ (F1.2,AGC ON), 0 Lux with IR , Shutter speed : 1 / 5s ~ 1 / 100,000 s ,120 dB WDR , Compression : H.265+ ,H.265 ,H.264+ H.264 .SD card support , Alarm trigger - 1 input / 1 output , frame rate : Main stream should support 25 fps@5MP , Edge analytics : line crossing , perimeter intrusion ,Face detection (deep learning) , pedestrian detection ,cross counting , stationary object , In built IR LED , IR Distance upto 50 meters , IK 10 housing , POE.
Supply, Installation ,Testing and Commissioning of 48" LED, Full HD TV monitor for Live View and Replay of Recorded View. LED shall support H.264/265 resolution. 2HDMI port enable, VGA port, headphone jack and USB enabled operating temperature -20 +400C Complete with all mounting accessories required for completion. The price shall be including HDMI cable for connection between NVR to CCTV screen.
Supplying, installing, Testing and commissioning of CCTV workstation complete with client software installation as follow, 4 GB RAM, upgradable upto 8 GB, 1TB HDD SATA Drive extendable upto 8 TB, i7 Processor, 3.5 GHz, Intel HD Graphics 4000, DDR3 LAN/Ethernet :2 x 10 Gbit CNA via Midplane to Ethernet Connection, with 26" LED Monitor.
Supplying, installing, Testing and commissioning of 32 channel NVR , ONVIF profile S & G , recording bandwidth 640 Mbps , output interface 1 HDMI (up to 4K), 1 VGA , Alarm in/out :16ch in / 4ch out , 1 X RJ45 ethernet , iOS smartphone support , 8 HDD support and inclusive 4 nos. 6 TB HDD , each HDD slot support upto 8 TB HDD , RAID support , 1x3.0 USB for backup /upgrade , 2x 2.0 USB for mouse , ArtificaI Intelligence Support having face recognition with compatible deep learning supported cameras, AI-Face registered quantity upto 10,000 ,A.I maximum captured quantity 200,000. UL,CE,FCC certified. OEM Should not be blacklisted globally.
The price shall be included software, Client licenses and required Camera licenses complete as per technical specifications and as required. All the components to be of same make as Camera. NVR shall be BIS certified.
The recording and storage shall be minimum 30 days with motion/continuous.
NVR Client software shall have the following option:
Video Operation Codec Management, Recording and Processing Software (VOCMRPS).
Each NVR/Client software Shall have 10% expansion capability
Software shall be provided with the License copy and License copy shall be available with client.
All future upgrades configuration in software shall be made free of cost and software must be upgraded time to time whenever any new releases is received during warranty period and after warranty it has to be inform to the client before any activity/up gradation.
Recording shall be configurable at 30 fps 4CIF
Supply, installation, testing & commissioning of manageable PoE+ Layer-2, 24 Port 4uplink port 10/100/1000 copper ports Base-T rack mounted switch, Web user, traffic manage HTTP/HTTPS web brows minimum IE5.5, Cat-6 RJ-45 connector supported, including 2 port 1G SFP module, maximum 75W power consumption. inbuilt fan, Storage temperature -200C-700C, Operating temperature 00C - 400C, Operating humidity 10% 90%, Complete with all rack mounting accessories for completion.
Supply, installation, testing & commissioning of manageable PoE+ Layer-2, 16 Port 4uplink port 10/100/1000 copper ports Base-T rack mounted switch, Web user, traffic manage HTTP/HTTPS web brows minimum IE5.5, Cat-6 RJ-45 connector supported, including 2 port 1G SFP module, maximum 75W power consumption. inbuilt fan, Storage temperature -200C-700C, Operating temperature 00C - 400C, Operating humidity 10% 90%, Complete with all rack mounting accessories for completion.
Supply, installation, Testing & Commissioning of 4pair 8wire color identification, 22-26 AWG, solid copper conductor unshielded armoured Cat-6 cable, storage temperature -400C- +850C, operating temperature -50C - +750C Complete with all mounting accessories required for completion.
Supply, installation, Testing & Commissioning of 2 x 2.5sqmm thinned coppoer conductor Fire survival armoured power cable 16AWG, PVC insulated Complete with all mounting accessories required for completion (For CCTV room near server).
Supply, installation, testing and commissioning of 6 core 9/125μm, OS2, glass optical type, Armoured single mode optical fibre color identification cable, storage temperature - 300C - +700C, operating temperature -400C - +700C with all Complete mounting accessories required for completion.
Supply, installation, testing and commissioning of optical fiber multi/single mode Line interface unit, Din rail mounting, support 6/8core 9/125μm, OS2 fiber cable with media convert module Complete with all mounting accessories required for completion.
Supply , Installtion , Testing and Comissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity.
Supply , Installtion , Testing and Comissioning of CAT6 information outlet (I/O) for Camera at user end.
Supply , Installtion , Testing and Comissioning of loaded 16 port CAT6 jack panel for CAT6 cable termination at rack end.
Supply , Installtion , Testing and Comissioning of loaded 12 port CAT6 jack panel for CAT6 cable termination at rack end.
Supply , Installtion , Testing and Comissioning of CAT6 patch cord 3 feet for rack side switch to jack panel connectivity.
Supply , Installtion , Testing and Comissioning of CAT6 patch cord 7 feet for information outlet (I/O) to end user device connectivity.
Supply , Installtion , Testing and Comissioning of 1, 2 and 4 port face plate white for I/O fixing at user side.
Supplying, installing and jointing of MS conduits on surface or concealed complete with MS junction boxes, cover plates, MS bends, MS flexible conduit, GI saddles, base and other accessories all made in MS with GI screws as required to complete the job. Exposed conduiting shall be painted with red enamel paint for identification.
25 mm MS Conduit
Supply, installation, testing and commissioning of wall/floor mounted cabinet with drawer shelves and wiring channels to accommodate CCTV system equipment and accessories as mentioned in the BOQ above and including all connections and terminations as required fabricated from minimum 2 mm thick CRCA sheet including power coating after surface treatment complete as required.
12U rack.
6U rack for the Network Switch
Providing, laying and joint DOUBLE WALL CORRUGATED HDPE pipe including jointing as per IS 14930 for crossing (under pavement/side berms or ramps etc.) for electrical cables and opening in the masonry wall for pipe entry. (Cost of excavation & filling and disposal of surplus excavated soil shall be inclusive).
32 OD mm dia DWC HDPE
External Services
SUB HEAD-XXII: ROAD WORK& HARD STANDING
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
Providing, laying and making kerb channel 30 cm wide and 50 mm thick with cement concrete 1:3:6 (1 cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth etc. complete and as per direction of Engineer-in-charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
SUB HEAD-XXIII : WATER SUPPLY
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
All kinds of soil
Pipes, cables etc, not exceeding 80 mm dia.
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.
External work
25 mm nominal outer dia Pipes
32 mm nominal outer dia Pipes
40 mm nominal outer dia Pipes
50 mm nominal outer dia Pipes
Painting GI pipes and fittings with two coats of anti corrosive bitumastic paint of approved quality
25 mm dia, nominal bore
32 mm dia, nominal bore
40 mm dia, nominal bore
50 mm dia, nominal bore
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete :
25 to 40 mm nominal bore
50 to 80 mm nominal bore
Providing and fixing brass bib cock of approved quality :
20 mm nominal bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
32 mm nominal bore
40 mm nominal bore
Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
SUB HEAD-XXIV : EXTERNAL ELECTRIC SUPPLY & AREA LIGHTING
Supply, Installation, testing and commissioning of BIS approved 40 W, LED Post top lantern 85-95 lm/W, 5700K/ 4000K/ 3000K Decorative Suspended four faced Luminaire with frame and top made up of Die Cast Al and a PMMA protector sealed on to the body and tool free access to control gear with integrated lenses for Asymmetric and Symmetric optics to cover larger area with increased pole span and reduced no. of luminaires with uniform light distribution, Optical tightness is IP66 and Control Gear tightness is IP65, IK06, CRI >70, PF > 0.90, THD <10% and Driver Efficiency >85%, Operating temp. range up to 50degree and designed for efficient thermal management, Surge protection of 10kV, lumen maintenance L70@ 50000Hrs. Submission of LM 80-08 from LED source manufacturer and LM 79-08 from third party NABL approved lab. Manufacturer mandatory. i/c connection wire and testing etc. to complete the job., 2 years Warranty certificate from manufacturer. The fixture shall be including all the fitting and supporting accessories to fix with required pole and to complete the system. Decorative GI - PU Painted MS pole. Classic pole- 3mt. With Base plate & foundation bolt Make : Keselec, Philips, LT, Ligman, Bega, NERI Make : Keselec. CAT ITEM - RILA POST TOP- 40 W NW or equivalent. POle Make : Keselec. CAT ITEM - Classic Pole- 3 Mt or equivalent.
Supply, Fixing, Testing & Commissioning of LED Aviation Light including necessary hardware fabrication on 3mtr long 50mm dia class B GI pipe wih two coats of primer redoxide and two coats zinc chromate aluminium paint, required PCC foundation above ground level coping upto 300mm, terminal box with MCB, 2C x 1.5Sqmm unarmoured cable and end termination of same at both side by providing necessary gland lugs etc. complete.
Provision of spiral earthing with 8 SWG GI earth wire including spreading of salt and charcoal as per IS 3043/87 with latest amendments
Supply, laying, testing and commissioning of 4C X 10 Sq.mm size of 1100V grade XLPE insulated armoured Aluminium conductor cable, the cable is to be laid in ground, the same shall be laid at a depth of 300mm below ground level including excavation in all kind of soil, SDR & HR, refilling of earth after cables are laid, including brick protection and send cusioning
Providing cable end terminations for 4C X 10 Sq.mm Al Arm. Cable with aluminium/ copper lugs, double compression type cable gland with neoprene gasket using Insulation tape, crimping tool etc., complete as required.
Providing cable end terminations for 3C X 2.5 Sq.mm Cu Arm. Cable with aluminium/ copper lugs, double compression type cable gland with neoprene gasket using Insulation tape, crimping tool etc., complete as required.
SUB HEAD-XXV : FIRE FIGHTING SYSTEM
Supply,laying, testing and commissioning of centrifugally cast Ductile iron pipe 150 NB conforming to IS 8329 class K9, with cement mortar lining inside suitable for socket and spigot type joints and of following sizes including supply and fixing of all push on type/ mechanical joints conforming to IS 13382 along with jointing materials such as Bends, Elbows , Tees, Flanged spigots, collars etc and making tyton joints to DI pipes, Specials, including cost of jointing materials such as rubber gaskets and labour charges, testing the joints for leakage and makng good if any for hydrant system.
a) Supply , laying , testing and commissioning of C- class 80 NB MS pipes confirming to IS 1239 upto 150 NB and IS 3589 from 200 NB including all required bends, fittings, flanges, bolts, nuts, welding of joints and painting with two coats of postal red enamel paint over one coat of primer etc., complete and of following sizes
b) Class - C 150 NB
Supply , erection, testing and commissioning of 80 NB Cast iron Butterfly valves (PN 1.6) conforming to IS:14846 of following sizes with necessary flanges, bolts , nuts etc., complete
Supply , erection, testing and commissioning of 150 NB Cast iron Sluice valves (PN 1.6) conforming to IS:14846 of following sizes with necessary flanges, bolts , nuts etc., complete
Supply , erection, testing and commissioning of single headed internal hydrant valve with 63 mm female instantaneous outlet in oblique type complete with cap & chain generally as per IS 5290 type A
Supply and fixing of hose reel of 30m long of thermoplastic synthetic hose (IS : 12585) of 19mm dia including swinging type drum with all necessary bolts, nuts etc, complete.
Supply & fixing 63mm dia cotton synthetic fibre (RRL) woven rubber lined fire hose delivery treated against rot with MYSTOX, with male and female instantaneous G.M couplings and of length of 30M each
Supply and fixing of Gun metal branch pipe 63mm dia, male and female threaded outlet complete with hexagonal base bore nozzles as per IS 903
Supply and fixing of Fire Hose Box of MS of size 30" x 24" x10" to accommodate two numbers of 30 M length hoses and branch pipe, glass fronted , double door with lock painted fire red outside with suitable structural support complete but including civil works
Providing MS supports in angles/ iron plates / pipes / channels /beams etc., as per drawings / Instructions at site including 2 coats of synthetic enamel paint over a coat of primer.
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :(ordinary rocks)
Supply and spreading of sand in layers not exceeding 100 mm thick in excavated trenches as sand cushion for pipes all as specified and directed
Providing anti corrsive wrapping and coating with 4mm thick bitumastic membrane (Pypcoat) for 100 mm dia MS pipe laid below ground including all materials with minimum overlapping of 30mm
Constructing masonry Chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :
SUB HEAD-XXVI :SEWAGE DISPOSAL
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
All kinds of soil
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete
150 mm dia
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design :
150mm dia sw pipe
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
150 mm dia. R.C.C. Pipe
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455 x 610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra for depth for manholes :
Size 90x80 cm
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete
For pipes 100 to 250 mm diameter
Providing ,fitting of factory made RCC septik tank of size 1m dia and length 2.4m ,Capacity 2000 ltrs having 3 chambers , 2 man holes inlet & outlet.The ready made tank shall be made using optimum quality basic material which shall be procured from the trusted vendors.
Constructing soak pit 1.20x1.20x1.20 m filled with brickbats including S.W. drain pipe 100 mm diameter and 1.20 m long complete as per standard design.
COLLECTION CHAMBER 2.5x2.5x0.85 SIZE(0.23M THICK WALL)
Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge.
SUB HEAD-XXVIII: FENCING AND GATE
Chain link fencing & Gates
Supplying and fixing at site Angle iron post & strut of required size including bottom to be split and bent at right angle in opposite direction for 10 cm length and drilling holes upto 10 mm dia. etc. complete.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.
Made of G.I. wire of dia 4 mm
VISHAL BUILDERS
NIMMA NARAYAN ENGINEERS & CONTRACTORS
PMR CONSTRUCTIONS
QUICK BUILDERS
Surendra Infrastructure Pvt. Ltd.
RMS CONSTRUCTION PVT. LTD.
Parth Infrastructure Pvt. Ltd.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid