Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.1 LAccepted-AOC 131 SANGAM NAGAR OPP NATIONAL SCHOOL SANGHVI PUNE 411027 | PUNE | MAHARASHTRA | 411027 | L1 | Accepted-AOC Bidder quoted L1 rates | |
| 2 | L2₹29.2 L+₹3.8 L (15.0%)Rejected-AOC OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L2 | Rejected-AOC Bidder not quoted L1 rates | |
| 3 | L3₹29.3 L+₹3.8 L (15.1%)Rejected-AOC | L3 | Rejected-AOC Bidder not quoted L1 rates | |
| 4 | L4₹29.9 L+₹4.5 L (17.8%)Rejected-AOC | L4 | Rejected-AOC Bidder not quoted L1 rates | |
| 5 | L5₹31.5 L+₹6.1 L (24.0%)Rejected-AOC 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L5 | Rejected-AOC Bidder not quoted L1 rates |
Tender Value
Refer Docs
EMD Value
₹78,000
Closing Date
24 Apr 2021, 6:00 pmClosed
GE SOUTH PUNE
NO 1 GENERAL BHAGAT MARG PUNE 411040
8247 REPAIRS / MAINTENANCE / REPLACEMENT OF CABLE, MCCB PANEL, EXTERNAL ELECTRIC SYSTEM, PROTECTIVE SYSTEM AND MISC WORK IN AREA No. 1 AND OTHER CONNECTED AREA UNDER AGE EM SOUTH PUNE
2021_MES_432127_1
8247 GE SOUTH PUNE
Open Tender
Civil Works
Item Rate
273 days
GE SOUTH PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE SOUTH PUNE
₹78,000
Yes
14 Aug 2021
20 Mar 2021
26 Apr 2021
20 Mar 2021
24 Apr 2021
10 Apr 2021
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for taking out cable etc and repairs / laying cables etc and getting out in following type of strata complete all as specified and as directed :-
Soft/Loose soil
Hard Dense soil
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed.
Removal of excavated material [soil] to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete, complete all as specified and directed.
M & L for plain cement concrete (1:4:8) type D-2 using 40mm graded stone aggregate as in base of pole or in any situation all as specified and directed
M & L for plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregate as in coping including necessary form work or in any situation all as specified and directed
M&L for straight through joint kit heat shrinkable suitable for the following size LT under ground cable 1100 volt grade armoured with aluminium conductor including necessary lugs etc all as specified and as directed. [Make - M- Seal/Danson/Raychem] [Note - (i) Excavation and earth work will be measured separetely] (ii) Taking out / Relaying of old cable cover/Bricks deemed to be included in the rates.]
LT cable 4 core 10 sqmm
LT cable 4 core 16 sqmm
LT cable 3.5 core 25 sqmm
LT cable 3.5 core 35 sqmm
LT cable 3.5 core 50- 70 sqmm
LT cable 3.5 core 95 sqmm
LT cable 3.5 core120- 150 sqmm
LT cable 3.5 core 240 sqmm
M&L for laying of Reinforced concrete pipes,class NP2 of dia 100 mm, 2 nos half round ( for bottom and top )and before laying exacaved area shall be levelling complete all as specified and directed.
M&L for taking out old unserviceable MCB/MCCB TP/TPN from existing LT panel board and supply and fix MCCB TP 63 amps capacity ,Adjustable Thermal Magnetic, rup capacity 16 KA at 415 volt 50 Hz AC supply including necessary modification in panel board if required to fix the MCCB complete with replacement of brunt lugs and wire/cable pieces etc as required at site complete all as specified and as directed. [Make- L&T (d sine) /Siemens (3 VA ) /Schneider (CVS ) /Legrand ( DX3 )/C&S]
All as per Item No. 9.00 above but 100 amps capacity FP complete all as specified and as directed.
All as per Item No. 9.00 above but 200 amps capacity FP rup capacity 35 Ka complete all as specified and as directed.
All as per Item No 9.00 above but 400 amps capacity FP rup cap 35 Ka at 415 volt complete all as specified and as directed.
All as per Item No 9.00 above but 125 amps capacity FP complete all as specified and as directed.
All as per Item No 9.00 above but 250 amps capacity FP rup capacity 35 Ka complete all as specified and as directed.
All as per Item No 9.00 above but 160 amps capacity FP rup capacity 35 Ka complete all as specified and as directed.
M&L for taking out unserviceable contactor ML-3 TP from panel board and supply and fix power contactor ML-3 TP 40 amps capacity suitable for operation on 415 volt 50 Hz AC supply complete all as specified and as directed. [Make -L&T/Siemens/Schneider/C&S]
M&L for taking out unserviceable contactor ML-4 TP from panel board and supply and fix power contactor ML-4 TP 70 amps capacity suitable for operation on 415 volt 50 Hz AC supply complete all as specified and as directed. [Make -L&T/Siemens/Schneider/C&S]
Supply and fix in repairs Capacitors APP type for improvement of power factor ultra heavy duty of 25[5 KVAR x 5 Nos] KVAR suitable for 440 Volt 50 HZ 3 phase AC supply complete all as specified and as directed. [Make - L&T/Neptune/GE/Havells]
All as per Item No. 18.00 above but of capacity 10 KVAR Capacity complete all as specified and as directed.
M&L for repairs to LT panel boards complete with necessary welding works to doors, replacement of unserviceable hinges and aldrop bolt complete and painting with one coat of synthetic enamel paint of approved color internally and externally all as specified and as directed.
M&L for prepration of old painted surface of LT panel board /Bus Bar boxes etc and applying one coat of synthetic enamel paint complete all as specified and as directed
Supply and fix in repairs danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with screws on LT panel boards of size 20x15 cm complete all as specified and as directed.
M&L for pin point of fault in LT/HTunderground cables by using high voltage fault detector machine as and when required at site complete all as per the direction complete all as specified and as directed.
M&L for disconnecting burnt LT cable from MCCB/Main switch/Transformer etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands and insulating exposed inner core of the cable with insulation tape etc for the following size cables per the direction :-
LT under ground cable 16 sqmm 4 core
LT under ground cable 25 sqmm 3.5 core
LT under ground cables 50 sqmm 3.5 core
LT under ground cables 95 sqmm 3.5 core
LT under ground cable 120 sqmm 3.5 core
LT under ground cable 150 sqmm 3.5 core
LT under ground cable 185 Sqmm 3.5 core
Supply Laying, joint, test and commission in repairs LT under ground cable 1100 V grade, XLPE insulated, armoured and sheathed with Aluminium conductor of following sizes including cable glands, lugs, jointing materials etc laid in trenches / floors / ducts all as specified and directed. (Note: Earth work and excavation shall be measured and paid separately.)
240 Sqmm 3.5 core
185 Sqmm 3.5 core
150 Sqmm 3.5 core
95 Sqmm 3.5 core
70 Sqmm 3.5 core
50 Sqmm 3.5 core
35 Sqmm 3.5 core
25 Sqmm 3.5 core
16 Sqmm 4 core
10 Sqmm 4 core
Taking down old unserviceable APFC panel and Design, supply,install, test and comissioning of weather proof, dust and vermin proof Automatic power factor control panel 200 KVAR out door installation factory made both front and rear side double door system, fabricated with 3 mm thick CRCA sheet for load bearing members and 2 mm thick for doors and covers and shall be painted witrh epoxy powder paint by means of electro static gun after rigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. The panel shall consist of 600 ,Amps rating TPN bus bars of high conductivity aluminium alloy and shall be provided with colour coded heat shrinkaable sleeves,with more depth for accommodating Capacitor bank 14 Nos inside of the panel. The panel shall be modular/cubical trype with bus chamber cable allyand provided with separate fully compartments for each switch including instrumentation such as Ampere Meter, Volt meter, Phase indicating lamp with double stud hinged door , front and rear openable with locking arrangement and suitable for 1100 Volts grade , 3 phase 415 Volts , 50 cycles , AC Supply and to with stand short circuit fault level of not less than 10 KA and degree of protection shall be IP 54 . The panel shall be fixed with angle iron frame made of angles of size 50x50x6 mm , embedded 200 mm below ground level in PCC 1:2:4, Type B1 using 20 mm grade stone aggregate , 600 mm above ground level and comprising the following including taking out of old panels etc , removing of cables and connecting to new panels with all required material such as glands, lugs etc
Design, supply, install, test and commissioning of free standing weatherproof, dust and vermin proof LT cubical panel outdoor type both front and rear side double door system (front side : main panel door and compartmentalised door for each cubical rear side main panel door and bolted door for each cubical) dust, vermin, water proof, fabricated with 3 mm thick CRCA Sheet for load bearing members and 2mm thick for doors and covers and shall be powder coated after seven tank process. The panel shall consist of 600 Amps rating TPN bus bars of high conductivity Aluminium alloy and shall be provided with colour coded heat shrinkable sleeves, minimum depth of panel shall be 400 mm minimum. The panel shall be modular / cublical type, with bus chamber, cable ally OFF/On button and provided with separate fully compartments for each switch, multi meter etc. with double stud hinged door, front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 Phase, 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10KA and degree of protection shall be IP 54. The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B-1 using 20mm grade incl. dismantling Old panel all as directed, 600 mm above ground level and comprising the following :including taking out of old panels etc, removing of cables and connecting to New panels with all required material such as glands, lugs etc
(a) MCCB 4 pole with RHOM control , Adjustable Thermal Magnetic ,rup capacity 50 KA at 415 volt of capacity 320 amps Icu=Ics = 100% - 01 No incoming (b) MCCB TP with RHOM control , Adjustable Thermal Magnetic , rup capacity 36 KA at 415 Volt of capacity 200 Amps Icu=Ics = 100% -02 No Outgoing (c) MCCB TP with RHOM control , Adjustable Thermal Magnetic , rup capacity 25 KA at 415 Volt of capacity 63 Amps Icu=Ics = 100% -02 No Outgoing (d) Multifunction Meter -1No. Make -L&T( MFM 4410 LED meter Cl 0.2S with RS485 ) equivalent in SIEMENS / Schneider (e) LED lamp RYB [Make- L&T(DV/D-sine) /Siemens (3 VA ) /Schneider (CVS) / Legrand (DX3)/C&S and LT Panel - Manufactures those panels are type tested by CPRI
Design, supply, install, test and commissioning of free standing weatherproof, dust and vermin proof LT cubical panel outdoor type both front and rear side double door system (front side : main panel door and compartmentalised door for each cubical rear side main panel door and bolted door for each cubical) dust, vermin, water proof, fabricated with 3 mm thick CRCA Sheet for load bearing members and 2mm thick for doors and covers and shall be powder coated after seven tank process. The panel shall consist of 500 Amps rating TPN bus bars of high conductivity Aluminium alloy and shall be provided with colour coded heat shrinkable sleeves, minimum depth of panel shall be 400 mm minimum. The panel shall be modular / cublical type, with bus chamber, cable ally OFF/On button and provided with separate fully compartments for each switch, multi meter etc. with double stud hinged door, front and rear openable with locking arrangement and suitable for 1100 Volts grade, 3 Phase, 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10KA and degree of protection shall be IP 54. The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B-1 using 20mm grade incl. dismantling Old panel all as directed, 600 mm above ground level and comprising the following :including taking out of old panels etc, removing of cables and connecting to New panels with all required material such as glands, lugs etc
(b) MCCB 4 pole with RHOM control , Adjustable Thermal Magnetic ,rup capacity 36 KA at 415 volt of capacity 250 amps Icu=Ics = 100% - 01 No incoming (c) MCCB TP with RHOM control , Adjustable Thermal Magnetic , rup capacity 25 KA at 415 Volt of capacity 125 Amps Icu=Ics = 100% -02 No Outgoing (d) MCCB TP with RHOM control , Adjustable Thermal Magnetic , rup capacity 25 KA at 415 Volt of capacity 63 Amps Icu=Ics = 100% -02 No Outgoing (e) MCB TP 40 Amp 415 Volt- 04 Nos outgoing (e ) Multifunction Meter -1No. Make -L&T( MFM 4410 LED meter Cl 0.2S with RS485 ) equivalent in SIEMENS / Schneider (f) LED lamp RYB [Make- L&T(DV/D-sine) /Siemens (3 VA ) /Schneider (CVS) / Legrand (DX3)/C&S and LT Panel - Manufactures those panels are type tested by CPRI
Supplying and laying GI pipe, 40mm dia, Light grade for cable protection at road crossing etc including necessary road cutting and making good with PCC 1:2:4, Type B-1, using 20mm graded stone aggregate, 100mm thick or fixing on wall / poles of any type, secured with clamps complete all as specified and as directed.
Supplying and laying GI pipe, 80 mm dia, Light grade for cable protection at road crossing etc including necessary road cutting and making good with PCC 1:2:4, Type B-1, using 20mm graded stone aggregate, 100mm thick or fixing on wall / poles of any type, secured with clamps complete all as specified and as directed.
Supplying and laying GI pipe, 100 mm dia, Light grade for cable protection at road crossing etc including necessary road cutting and making good with PCC 1:2:4, Type B-1, using 20mm graded stone aggregate, 100mm thick or fixing on wall / poles of any type, secured with clamps complete all as specified and as directed.
Supply and fix in repairs digital Voltmeter 0-500 volt square type complete with necessary fixing complete all as specified and as directed.
Supply and fix in repairs digital ammeter 0-100 amps square type complete with necessary fixing and 3 Nos of CTs all as specified and as directed.
Supply and fix in repairs digital ammeter 0-200 amps square type complete with necessary fixing and 3 Nos of CTs all as specified and as directed.
Supply and fix in repairs ammeter 0-400 amps square type complete with necessary fixing and 3 Nos of CTs all as specified and as directed.
M&L for scrapping existing deteriorated old aluminium paint by brushing and painting of steel tubular poles of 8.5/9.0/11 mtr length ( tubular/ J type) aluminium paint (two coats) over one coat of red oxide primer including cross arms, angles, nut, bolts, clamps & junction box all as required on site complete all as specified and as directed.
M&L for PCC 1:3:6 type C1 20 mm graded aggregate in coping of pole complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of plate not less than 1.50 m below normal ground level connected to GI earth strip 25x4 mm connected to the plate by means of GI bolts & nuts complete all as per Electrical plate No. 5 of SSR Part - I, connected to earthing test point including testing on completion including main earthing, charcoal, common salt, PCC 1:3:6, Type C-2 earth pit with RCC cover, MS funnel with GI watering pipe, wiremesh, earth work excavation etc complete all as specified and as directed. (Note - G I earth strip and protection pipe will be measured and paid seperately beyond 7.50 mtr)
M&L for cleaning of 2/4 pole structure/sub station /OHR/UG sumps/Pump house surrounding by surface dressing including removing shrubs, grass, miniplants and other unwanted materials and levelling and removing the excavated materials not exe. 50 mtr complete all as specified and as directed.
M&L For Cutting/trimming of tree branches up to 80mm dia along overhead Electric lines which are growing/touching or falling on ACSR conductor /poles or near by substn etc., at any hight upto 11 mtr from ground level and making sufficient clearence(1.5mtr) from ACSR conductor /poles /structure and taking down the same on the ground carefully &take all safety precaution to avoiding the damage and removing to a distance where directed.
Supply and fix in repairs APFC relay 12 stage for automatic correction of power factor suitable for 415 volt 3 phase power supply complete with necessary fixing. L&T Cat No. ERPML08D500 or equivallent in Siemens/Schneider
Supply and fix in repairs Capacitor Duty Contactors suitable for 5 KVAR capacitor complete (L&T Type MO C25 or same type in Siemens/Schneider)
Attending fault APFC pannel including Repair to APFC pannel replacing burned out wiring, setting and adjusting APFC relay etc complete and making APFC pannel servicable complete all as specified and directed.
S&F Capacitor duty contactor for 10 KVAR capacitor complete all as specified and as directed.
Supply and replacement, fixed compensation complete from APFC panel consisting of cylindrical capacitor 3 KVAR -01 and with capacity duty contactor and MCB TP of suitable capacity with two number LED and necessary copper wiring including making addition /alteration suitable way complete all as specified and as directed.
M&L for taking out old unserviceable Change over switch and supply and fix new auto transfer switch ATS] with automatic/Manual control with inbuilt time delay etc complete with enclosure 200 amp 4 pole including necessary arrangements to fix the ATS on wall with necessary bus bar and cable end boxes to connect incoming cable and out going cables conforming to Havells Cat No. IHYFCDE200 or equivalent in all respect such as construction, functioning etc of make L&T/Schneider
M&L for taking out old unserviceable Change over switch and supply and fix new auto transfer switch[ATS] with automatic/Manual control with inbuilt time delay etc complete with enclosure 125 amp 4 pole including necessary arrangements to fix the ATS on wall with necessary bus bar and cable end boxes to connect incoming cable and out going cables conforming to Havells Cat No. IHYFCDE125 or equivalent in all respect such as construction, functioning etc of make L&T/Schneider complete all as specified and as directed.
Supply and fix in repairs Analog Timer switch for street light control of 16 amp capacity complete all as specified and as directed. (Make- cat part No DHTED15016 of Havells or equivalent in L&T/ siemens/ Schneider/C&S)
Supply and replace door of out door LT pannel made out of CRCA Sheet 3.15mm thick bend on side to match the existing door duly powder coated and with new hinges -2 Nos. to suit any size / shape of pannel all as specified and as directed.
M&L in replacement for heat shrinkable end termination jointing kit for HT 22 KV XLPE cables up to 120 Sqmm 3 core including all accessories required complete all as specified and as directed. [Make :- Denson/M Seal/3M.]
M&L in replacement for heat shrinkable Straight through jointing kit for HT 22 KV XLPE cables up to 120 Sqmm 3 core including all accessorie required complete all as specified and as directed. [Make :- Denson/M Seal/3M]
Supply and fix Multifunction Meter- (Make -L&T( MFM 4410 LED meter Cl 0.2S with RS485) equivalent in SIEMENS / Schneider) with required wiring and CT including taking down any type of meter complete all as specifed and directed
Supply and replace indicator LED lamp any colour complete all as specified and as directed.
M & L for Attending the fault in UPS -10/15/20 KVA of any Make and Servicing of the UPS including setting the UPS for proper function including replacing small parts below Rs 300/- repairing and blowing out dust from inside the ups complete all as specified and directed.
Supply and fix on wall / ceiling Multi core flexible copper conductor pvc insulated and sheathed cable 4 Core 16 Sqmm, 1100 volt conforming to IS:694 including taking down existing aluminaum cable connecting to UPS/MCCB/DB and other equipment with lugs, glands and necessary jointing material all as specified and directed.
Supply and fix on wall / ceiling Multi core flexible copper conductor pvc insulated and sheathed cable 4Core 10 Sqmm,1100 volt conforming to IS:694 including taking down existing aluminaum cable connecting to UPS/MCCB/DB and other equipment with lugs, glands and necessary jointing material all as specified and directed
Supply and replace on load change over switch disconnector in Sheet metal enclosure 400Amps, 415 Volt 4 Pole complete all as specified and as directed.
Supply and replace on load change over switch disconnector in Sheet metal enclosure 200 Amps 415 Volt 4 Pole all as specified and directed.
Taking down broken/damaged RCC pole and Supply & fix steel tabular swaged poles with CI base plate, finial tape plug, bolts, nuts & screws, type 410 SP-31 (9.0 meters long) etc complete all as specified and directed.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25x4mm dia galvanised iron strip, complete all as specified and directed.
Taking down defective LED street/security light / flood light fittings of any capacity from height upto 9 mtr from pole/ wall etc for repairs and refixing the same/other location after replacing defective accessories like PVC insulated sheathed copper conductor etc.or replacing fitting complete all as directed. [NOTES (a) Cost of the electronic drivers and Surge protection Device (SPD) will be paid for separately as supply only. (b) Scope of work includes for minor stores i.e. pvc insulation tapes, screws, insulation sleeves, nuts, bolts, washers and flexible cable 23/0.0076 (for internal wiring) etc as required at site.]
Supply and fix in repairs electronic driver suitable for 20/25 Watt LED street light fittings complete for 230 volt 50 Hz AC Supply complete all as specified and as directed. (Make - Crompton / Havells / Wipro)
Supply and fix in repairs electronic driver suitable for 60 to 90 watt LED street light fittings complete for 230 volt 50 Hz AC Supply complete all as specified and as directed. (Make- Crompton / Havells / Wipro)
Supply and fix in repairs electronic driver suitable for 100/150 watt LED flood light fittings complete for 230 volt 50 Hz AC Supply complete all as specified and as directed. (Make- Crompton/Havells/Wipro)
Supply only Surge protection devices compatible with industrial & out door LED street light fittings upto rated power of 75Watt , 10 KA complete all as specified and as directed.
Supply only Surge protection devices compatible with industrial & out door LED street light fittings above rated power of 75Watt and upto 150W ,10 KA complete all as specified and as directed.
Taking down unserviceable post top/gate light and supply and fix LED Post top light fitting for 360 degree indirect light, IP 65 protection, resistant to impact and corrosion, glare free and better uniformity, including necessary fixing arrangements as required at site complete of capacity 42 watt, all as specified and as directed (Make - Wipro cat No LP02-501-XXX-57-XX or same type in all respect in Havells / HPL / Bajaj / Orient)
Taking down old unserviceable conventional street light fittings from pole/ building and supply and fix street light fittings Pressure die cast aluminium housing, IP 66 Proptection, heat resistance toughened glass with frame LED street light luminaries complete with driver and all standard accessories of capacity 25 Watt LED including necessary fixing arrengements with GI Pipe 25mm and MS clamp 02 Nos, necessary connection etc all as specified and directed (Make :- Havells item description ENDURAPEARLS25WLED757SASYTOPCMP or same type in all respect of Wipro/HPL/Bajaj)
Taking down old unserviceable conventional street light fittings from pole/ building and supply and fix street light fittings Pressure die cast aluminium housing, heat resistance toughened glass with frame LED street light luminaries, IP-66 complete with driver and all standard accessories of capacity 70 Watt LED including necessary fixing arrengements necessary connection etc all as specified and directed (Make - Havells Item description ENDURACITYLINERNEOSL70WLED757PASYBOTG or of equivalent in wipro/HPL/Bajaj)
Taking down old unserviceable conventional street light fittings from pole/ building and supply and fix LED street light fittings, Pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP-66 protection complete and all standard accessories of capacity 90 Watt LED including necessary fixing arrengements, necessary connection etc all as specified and directed (Make - Havells Item description ENDURAPEARLPLUSSL90WLED757PASYTOPCASTHO or of equivalent in wipro/HPL/Bajaj)
Taking down existing conventional flood light fittings and supply and fix LED lamp type flood light fittings, pressure die cast housing with IP 66 protection of capacity 100 watt suitable for operation on 230 volt 50 Hz AC supply complete with all standard accessories and necessary fixing arrangements all as specified and as directed (Make - Havells Items description JETAIRISFLS100WLED757SYMLTG or of equivalent in wipro/HPL /Bajaj/orient)
S&F in replacement MCCB 4 pole 125 Amp, Icu = 18 KA, 415 volts, 50 Hz, type with thermal magnetic release duly connected with copper spreader links 04 Nos and proper size of lugs, nuts bolts and washers for proper connections complete including MS enclosure of suitable size complete all as specified and as directed. (Make : L&T (DBVTL004DD ) or equivalent in Legrand / HPL /C&S)
S&F in replacement MCCB 4 pole 200 Amp, Icu = 18 KA, 415 volts, 50 Hz, type with thermal magnetic release duly connected with copper spreader links 04 Nos and proper size of lugs, nuts bolts and washers for proper connections complete including MS enclosure of suitable size all as specified and directed. [Make :- L&T (DBVTL004DD ) or Equivalent in Legrand / HPL /C&S]
S&F in replacement MCB SP 6-32 Amps,10KA,'C' series complete all as specified and as directed.
S&F in replacement MCB SPN 20-40 Amps,10KA, 240V,'C' series complete all as specified and as directed.
S&F in replacement MCB TP 32/40 Amps ,10KA,415 V,'C' series complete all as specified and as directed.
Notes for item No 1 to 76 above:- contractor will make own arrangement for T&P items like Ladder, Hand gloves, Safety belt etc. as required on site for execution of the work and cost of the same is deemed to be include in the quoted rate.
M/S. Niksun Electro-Infra Private Limited
PURVA ELECTRICALS AND ENGINEERS
REKHA ELECTRICALS
Adinath Technical Services
CHAITANYA WINDWELL
metro electrical services
M/S - SUJIT ELECTRICALS
Rama Electricals
K.K.Enterprises
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .