EXECUTIVE ENGINEER, DIVN V, BICHOILM.
O/O EXECUTIVE ENGINEER, DIVN V, BICHOLIM.
Tender for the work of enhancement of existing 200 KVA DTC to 400 KVA DTC for A.P.S. to 1 no. LTD connection to Shri Susen A. Panjikar, Warchawada Shirgao, for a connected load of 6.12 KW, in the jurisdiction of SO Assonora, under SDI, Bicholim.
2026_ED_28234_1
Tender-84/Div-V (2025-26) Re-Tender
Open Tender
Electrical Works
Percentage
120 days
ASSONORA
AS PER NIT
2 documents required · 2 mandatory
₹500
₹14,901
11 May 2026
13 Mar 2026
23 Mar 2026
14 Mar 2026
20 Mar 2026
16 Mar 2026
Cost of Material
M.S. Distribution Box With 400Amps MCCB and Kit-Kat Fuse
Erection of Single Core 240 sq.mm. XLPE unarmoured cable
Erection of Single Core 300 sq.mm. XLPE unarmoured cable
Crimping of Alluminium Lugs 240 Sq.mm.
Crimping of Alluminium Lugs 300 Sq.mm.
G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
S&E of GI earthing strip of size 25x5 mm for connecting earthing pipe to other equipment
GI Tubular Fencing complete with gate and side dismantling system as per the specification for Distribution Transformer and Feeder Pillars (Size 4M X 3M X2M) with concreting for Gl fencing supports with plinth (0.3x0.3x0.5) Cu.m.x12 nos. Each ratio 1:3:6 and brick masonary [Galvanising should be hot dipped Galvanised as per 18:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT, suitable for high salinity coastal areas]
Supply and Erection of XLPE 16 Sq. mm. 3.5 core cable
Crimping of Alluminium Lugs 120 Sq.mm.
RCC protective covers of size 480mm long x 250mm width and 50mm thick capable of bearing load of 135Kg. And covered with earth/ sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing. (as per CEE approved drawing, enclosed) (180/0.48)
Supplying and filling in plinth under floors, trenches including watering ramming consolidating, dressing, complete. Sand (0.2*0.4*180m)- Cable (0.03cubics*180)
Cost of Erection
400 KVA 11kv/.4kv Distribution Transformers level II losses, Aluminium winding with Bimettalic terminal connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014, suitable for outdoor use and for plinth mounting.
M.S. Distribution Box With 400Amps MCCB and Kit-Kat Fuse
Erection of Single Core 240 sq.mm. XLPE unarmoured cable
Erection of Single Core 300 sq.mm. XLPE unarmoured cable
Crimping of Alluminium Lugs 240 Sq.mm.
Crimping of Alluminium Lugs 300 Sq.mm.
Rmoval and Re-erection of Distribution Transformer Metering unit with DLMS/COSEM protocol energy meter with modem
G.I. Earthing pipe 8' long 40 mm. Dia class B, Fabricated & perforated including alternate layers 30 Cm. Thick of charcoal, salt, & earth (charcoal & salt 10 Kgs. each for per pit) inclusive of excavation, backfilling and spreading of excavated earth evenly.
S&E of GI earthing strip of size 25x5 mm for connecting earthing pipe to other equipment
GI Tubular Fencing complete with gate and side dismantling system as per the specification for Distribution Transformer and Feeder Pillars (Size 4M X 3M X2M) with concreting for Gl fencing supports with plinth (0.3x0.3x0.5) Cu.m.x12 nos. Each ratio 1:3:6 and brick masonary [Galvanising should be hot dipped Galvanised as per 18:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT, suitable for high salinity coastal areas]
Supply and Erection of XLPE 16 Sq. mm. 3.5 core cable
Crimping of Alluminium Lugs 120 Sq.mm.
Earthwork in excavation by mechanical means (hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed in : b) All types of Ordinary rock including all types of laterite rock, blasting prohibited (1.1*0.6*180m)
Refilling the pipeline/foundation trenches plinth sides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 M and all lifts and disposal of surplus earth as directed by Engineer in Charge. Deduct for RCC Slab (0.9*0.6*180m) - (0.48*0.25*0.05*No. of Prot. covers 375)
RCC protective covers of size 480mm long x 250mm width and 50mm thick capable of bearing load of 135Kg. And covered with earth/ sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing. (as per CEE approved drawing, enclosed) (180/0.48)
Rubble packing Double circuit 11 KV Cable trench (0.2x0.9x1.00) i.e. 0.14 per RM
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 23.03 MB
BOQ_28673.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .