Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.0 CrAccepted-AOC 15 16 GANGA COLONY KHATIPURA ROAD JAIPUR RAJ 302012 | JAIPUR | JAIPUR | RAJASTHAN | 302012 | ₹28.0 Cr Quoted ₹28.7 Cr | L1 | Accepted-AOC Being Reasonable and Accepted |
| 2 | L2₹29.4 CrRejected-AOC 223 3 E B 1 MALTI TOWER TARABAI PARK KOLHAPUR 416 003 | KOLHAPUR | KOLHAPUR | MAHARASHTRA | 416003 | ₹29.4 Cr | L2 | Rejected-AOC Other Than L1 |
| 3 | L3₹30.1 CrRejected-AOC | ₹30.1 Cr | L3 | Rejected-AOC Other Than L1 |
| 4 | L4₹30.9 CrRejected-AOC 61 LAALA LAJPAT RAI COLONY BHOPAL M P 462023 | BHOPAL | MADHYA PRADESH | 462023 | ₹30.9 Cr | L4 | Rejected-AOC Other Than L1 |
| 5 | L5₹34.4 CrRejected-AOC | ₹34.4 Cr | L5 | Rejected-AOC Other Than L1 |
| Sl No | Description | Qty | Unit | BHARATSHAH CONSTRUCTION CO L1 | Beejay Associates Contracts Pvt Ltd L5 | Sharda Infratech L7 | Hariom Projects Pvt Ltd L3 | D R CONSTRUCTION L2 | M/s S. R. Constructions L8 | SOOD ASSOCIATES PVT LTD L6 | SHREE KRISHNA INFRASTRUCTURE L4 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00SCH 'A' PART-I To XIII Note: This schedule is not pre-priced by MES and the rate indicated as under Col 5 signifies this fact only | |||||||||||
| 2.00 | Total amount of Sch 'A' Part-I (Building and Structures) | 1 | LUMP SUM | 23,18,50,870 ₹23.2 Cr | 27,03,19,400 ₹27.0 Cr | 31,83,76,045.16 ₹31.8 Cr | 22,50,00,000 ₹22.5 Cr | 22,50,00,000 ₹22.5 Cr | 36,00,00,000 ₹36 Cr | 29,68,73,082.6 ₹29.7 Cr | 24,30,00,000 ₹24.3 Cr |
| 3.00 | Total amount of Sch 'A' Part-II (Area Development, Excavation and Earthwork) | 1 | LUMP SUM | 66,40,751.57 ₹66.4 L | 85,52,483.25 ₹85.5 L | 92,58,842.98 ₹92.6 L | 1,00,61,744.81 ₹1.0 Cr | 1,16,39,700 ₹1.2 Cr | 85,00,000 ₹85 L | 1,12,46,012.17 ₹1.1 Cr | 1,80,00,000 ₹1.8 Cr |
| 4.00 | Total amount of Sch 'A' Part-III (Internal Water Supply) | 1 | LUMP SUM | 17,83,113.82 ₹17.8 L | 27,99,488.7 ₹28.0 L | 21,88,438.5 ₹21.9 L | 17,83,113.82 ₹17.8 L | 24,07,000 ₹24.1 L | 18,50,000 ₹18.5 L | 17,83,113.82 ₹17.8 L | 22,50,000 ₹22.5 L |
| 5.00 | Total amount of Sch 'A' Part-IV (Internal Electric Supply) | 1 | LUMP SUM | 1,06,33,969.43 ₹1.1 Cr | 1,41,78,625.91 ₹1.4 Cr | 1,05,70,519.4 ₹1.1 Cr | 1,17,50,000 ₹1.2 Cr | 1,30,23,860 ₹1.3 Cr | 1,20,00,000 ₹1.2 Cr | 1,06,33,969.43 ₹1.1 Cr | 96,30,000 ₹96.3 L |
| 6.00 | Total amount of Sch 'A' Part-V (Road, Paths & Culverts ) | 1 | LUMP SUM | 1,39,56,702.45 ₹1.4 Cr | 1,86,08,936.6 ₹1.9 Cr | 1,38,19,484.42 ₹1.4 Cr | 1,66,15,121.96 ₹1.7 Cr | 1,96,92,600 ₹2.0 Cr | 1,45,00,000 ₹1.4 Cr | 1,94,39,692.69 ₹1.9 Cr | 1,35,00,000 ₹1.4 Cr |
| 7.00 | Total amount of Sch 'A' Part-VI (Sewage Disposal) | 1 | LUMP SUM | 19,21,154.05 ₹19.2 L | 25,61,538.73 ₹25.6 L | 25,02,302.68 ₹25.0 L | 20,65,757.04 ₹20.7 L | 25,37,600 ₹25.4 L | 22,00,000 ₹22 L | 24,16,935.74 ₹24.2 L | 18,00,000 ₹18 L |
| 8.00 | Total amount of Sch 'A' Part-VII (Area Drainage) | 1 | LUMP SUM | 57,74,635.53 ₹57.7 L | 69,54,399.78 ₹69.5 L | 54,62,380.84 ₹54.6 L | 62,09,285.52 ₹62.1 L | 76,06,975 ₹76.1 L | 65,00,000 ₹65 L | 78,85,792.61 ₹78.9 L | 54,00,000 ₹54 L |
| 9.00 | Total amount of Sch 'A' Part-VIII (Compound wall, Fencing and Gate) | 1 | LUMP SUM | 8,66,819.89 ₹8.7 L | 10,04,538.94 ₹10.0 L | 11,49,266.78 ₹11.5 L | 8,10,112.05 ₹8.1 L | 10,70,000 ₹10.7 L | 8,50,000 ₹8.5 L | 10,28,842.3 ₹10.3 L | 8,10,000 ₹8.1 L |
| 10.00 | Total amount of Sch 'A' Part-IX (External Water Supply) | 1 | LUMP SUM | 6,35,821.89 ₹6.4 L | 7,59,190.32 ₹7.6 L | 9,74,222.5 ₹9.7 L | 4,74,493.95 ₹4.7 L | 6,78,270 ₹6.8 L | 5,50,000 ₹5.5 L | 8,39,854.29 ₹8.4 L | 6,30,000 ₹6.3 L |
Updated dates
Tender Value
₹29.8 Cr
EMD Value
₹15 L
Closing Date
25 Feb 2026, 6:00 pmClosed
Chief Engineer Pune Zone
HQ Chief Engineer Pune Zone Camp, Pune 411001
PROVISION OF 120 DUs ORs MD ACCN (G PLUS 2F) UNDER GE (SOUTH) PUNE
2025_MES_746713_1
84641
Open Tender
Civil Works
630 days
GE South Pune
As per Tender Documents
7 documents required · 7 mandatory
₹3,000
GE South Pune
₹15 L
Yes
26 Mar 2026
14 Jan 2026
4 Mar 2026
14 Jan 2026
25 Feb 2026
11 Feb 2026
15 Jan 2026 - 22 Jan 2026
SCH 'A' PART-I To XIII Note: This schedule is not pre-priced by MES and the rate indicated as under Col 5 signifies this fact only
Total amount of Sch 'A' Part-I (Building and Structures)
Total amount of Sch 'A' Part-II (Area Development, Excavation and Earthwork)
Total amount of Sch 'A' Part-III (Internal Water Supply)
Total amount of Sch 'A' Part-IV (Internal Electric Supply)
Total amount of Sch 'A' Part-V (Road, Paths & Culverts )
Total amount of Sch 'A' Part-VI (Sewage Disposal)
Total amount of Sch 'A' Part-VII (Area Drainage)
Total amount of Sch 'A' Part-VIII (Compound wall, Fencing and Gate)
Total amount of Sch 'A' Part-IX (External Water Supply)
Total amount of Sch 'A' Part-X (External Electric Supply)
Total amount of Sch 'A' Part-XI (DG Set)
Total amount of Sch 'A' Part-XII (TV Conduit)
Total amount of Sch 'A' Part-XIII (Lightening Protection)
SCHEDULE 'A' PART-XIV (MISCELLANEOUS B/R AND E/M WORKS)
S&F Load line distribution board TPN vertical, 8 way double door type, fixed on wall semi flush with and including incoming MCCB 4 poles 125 Amps, 10 KA, 250 Amp rating busbars, neutral link, blanking plates with IP 43 protection and door earthing complete with all accessories complete all as specified and as directed. Make: Havells Cat No DHDLVDRWAOFO08 or techno-commercially equivalent model in C&S/ Indoasian/ Legrand/ ABB/ Schneider
S&F PVC metal braided connection pipes for hot water supply with brass adopters 15 mm dia and 450mm long complete all as specified and as directed.
S&F LED batten suitable for indoor application 20 W, 4' length, wall mounted with polycarbonate housing end cap made of ABS plastic of white colour finish and high efficiency translucence (HET) diffuser and integral electronic driver including two point surface mounting on wall/ ceiling and connecting up with twin core twisted flexible copper conductor cable of suitable size including taking down old complete all as specified and as directed.
S&F LED light fitting 1x9W/ 1x10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F LED batten suitable for indoor application 10 W, 2' length, wall mounted with polycarbonate housing, end cap made of ABS plastic of white colour finish and high efficiency translucence (HET) diffuser and integral electronic driver including two point surface mounting on wall/ ceiling and connecting up with twin core twisted flexible copper conductor cable of suitable size including taking down old complete all as specified and directed. Make:- Bajaj Cat No DAWN PC 10W NW PD or techno-commercially equivalent model in Havells/ Wipro/ Crompton/ Halonix/ Luker.
S&F TV Coaxial Socket 1 Module complete all as specified and directed. Note: TV Sockets (for 01 Nos of TV connection)
S&F CATV Co axial cables electrolytic Grade solid annealed copper conductor jelly field, aluminium foiled and aluminium wire braided complete all as specified and directed.
Supply, install, testing and commissioning Silent type Diesel Engine Generating set with accoustic enclosure 415 volts 15 KVA 3-phase 0.8 power factor 50 Hz, 1500 RPM self exicited self regulated brshless AC generator including accoustic enclosure with AMF panel, suitable for ambient condition at Pune and confirming to condition under IS 4722, 10001/10002, 13364, BS 5514/2613/5000, ECBC 2017 provisions and shall meet the applicable CPCB emission and acoustic norms with the following specifications:- (A) Alternator: Standard design alternator rated at 15 KVA net output after considering derating as per site conditions at 0.8 (lag) power factor AC, 3-phase 4 wire 415 volts 50 Hz, 1500 RPM, self exicited self regulated screen protected dirip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and voltage regulation of +1% at rated voltage from no load to full load. The alternator shall be confirming to BS 2613/5000, IS 13364 and shall be in position to generate supply with frequecy regulation with in +1% tolerance. i) Insulation class - 'H' ii) Temperature rise Class - 'H' iii) Excitation - Self Excited iv) Regulation performance: The voltage is kept constant within+1%, manual voltage adjustment within +5% v) Frequency regulation +1%
(B) Diesel Engine: Adequate capacity of Diesel engine as accepted by the accepting officer based on manufacturers technical details water cooled to drive independently above alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexiable coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS - 10001/10002/ 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under:- i) Fly wheel with housing ii) Cooling system - Moulded radiator with fan & belts iii) Cooling Water pump iv) Exhaust System - Exhaust System with residual type silencer with exhaust piping upto & outside and 1 meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. v) Fuel System - Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governor electronic operated/ (as recommended by OEM) for 1% speed/frequency regulation. vi) Lub oil System with necessary filtering element vii) Air Intake System - dry type air filter viii) governor electronic / (as recommended by OEM) ix) Starting System - Electric Self starter with and including battery charging alternator
x) Batteries - Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multistrand leads of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified xii) Safety Controls - Engine low lube oil pressure high water temperature and over speeding of engine xiii) Coupling - Flexible coupling fly wheel to suit flexible coupling xiv) Accessories - AVM Pads built or separately mounted to manufacturer base frames as per (as recommended by OEM) xv) Base Frame - Made out of ISMC of sturdy design made of MS channel with necessary reinforcement and predetermined holes. xvi) Fuel Tank - Daily service fuel tank (as recommended by OEM) with calibrated level Indicating arrangement, stop cock, drain plug complete on a common base in side the acoustic enclosure (xvii) N-L approved as per CPCB as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board (xviii) The DG Set shall be provided with external Emergency stop push button and necessary arrangement for illumination (xix) The noise level shall be less than 75 Db at 1m under free field conditions (xx) AMF with microprocessor based Relay Control Circuit, 4 pole MCCB 100Amp 415 V, 25 KA, for main supply and DG set supply with HRC back up fuse complete with all DC control relays Line Voltage monitor (LVM) as per OEM specifications incorporating Engine start, stop three attempt starting facility and failure to start etc
Supply, laying and Jointing in trenches DI pipes 100 mm dia class K-7 of standard length spigot and socketed end push type joint with rubber gasket as jointing material, internal cement mortar coating and external surface with bituminous paint ISI marked complete all as specified and directed
Supply, laying and Jointing in trenches DI pipes 150 mm dia class K-7 of standard length spigot and socketed end push type joint with rubber gasket as jointing material, internal cement mortar coating and external surface with bituminous paint ISI marked complete all as specified and directed
M&L Ductile iron fittings of any size, any type with all sockets or socket and spigot fittings such as bends, tapers, collars, Tee's, caps, plugs etc up to 150 mm bore complete all as specified and directed
S&F Valve, reflux, swing check type with by-pass Arrangement, 100 mm dia complete all as specified and directed
S&F Cast iron air release valves with two air outlets (double action) conforming to IS 14845 of size 50 mm dia bore and fixing up in cast iron water supply mains of size 100 mm dia complete all as specified and as directed
Construction of brick masonry valve pit of size 90cm x 90cm X 90 cm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100mm thick PCC 1:4:8 type D2 (using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in benching and coping and 10mm thick cement plaster in CM (1:4) internally and externally upto 15cm below ground level providing valve pit cover 40x40x6mm angle iron frame all-round fixed by means of 4 Nos. holdfast 150mm long made out of flat iron 40x6mm embedded in PCC block (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) of size 230x200x100mm including provn of hinges welded with angle iron frame and MS cover 3mm thick sheet, MS handle of suitable length and size welded with MS cover and suitable locking arrangement and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in all kind of soil complete all as shown on drawing and as specified.
Construction of brick masonry valve pit of size 60cm x 60cm X 60 cm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100mm thick PCC 1:4:8 type D2 (using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in benching and coping and 10mm thick cement plaster in CM (1:4) internally and externally upto 15cm below ground level providing valve pit cover 40x40x6mm angle iron frame all-round fixed by means of 4 Nos. holdfast 150mm long made out of flat iron 40x6mm embedded in PCC block (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) of size 230x200x100mm including provn of hinges welded with angle iron frame and MS cover 3mm thick sheet, MS handle of suitable length and size welded with MS cover and suitable locking arrangement and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in soft/ loose soil complete all as shown on drawing and as specified.
Supply, install, testing and commissioning of centrifugal monoblock pump set, horizontal foot mounted electric motor driven 3 phase, 415 volts, 50 Hz supply induction motor and PCC foundation discharge not less than 1177 LPM ± 10%, at a head not less than 30 mtrs, Insulation Class "F", Degree of protection IP 55, Ambient temp of 50°C conforming to IS 12615-2011, IEC 60034-30-2008, ECBC 2017 norms complete all as specified and directed
S&F Foot Valve conforming to IS 4038, 100 mm (4") dia complete all as specified and directed.
Supply, install, commission and testing cubical type LT panel board indoor type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.00 mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glands complete all as specified and directed with the following accessories INCOMING (a) MCCB 4 pole, 415 Volts, 125 Amps, 16 KA - 01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 63 Amps, 10 KA - 02 Nos (b) Fully automatic star delta starters suitable for 15 HP motors - 02 Nos (c) MCB SPN, 220 Volts, 16 Amps, 10 KA - 02 Nos (Spare - 01 nos) (d) Change over switch front operated 4 pole, 415 Volts, 125 Amps - 01 No (e) Digital VAF meter for basic electric system monitoring - 01 Nos (f) Indicator lamp (RYB) (set of three) - 03 Set
M&L Cable route indicator for HT UG cable with cast iron plate circular or rectangular showing (HT UG cable 11000 V) with angle iron support of size 50X50X6 mm, minimum 0.4 mtr length including fixing nuts and bolts complete all as specified and as directed.
M&L Laying double wall corrugated HDPE pipe, UV stabilized of size 120x103 mm (ODX ID), IS-16205 for cable protection laid in trenches or fixed to walls complete all as specified and as directed.
M&L Laying double wall corrugated HDPE pipe, UV stabilized of size 90x75 mm (ODX ID), IS-16205 for cable protection laid in trenches or fixed to walls complete all as specified and as directed.
S&F GI pipe bracket for street light fittings made out of 32 mm dia GI pipe weight grade 15.7kg bent to required angle/shape with and including necessary clamps, nuts, bolts, & washers of suitable sizes as specified complete all as specified and as directed.
S&F PVC weather proof loop-in loop-out box with 4 pole terminal block mounted on porcelain or bakelite and MCB SP 06 Amps for controlling including necessary clamps for mounting on pole etc complete all as directed as specified. Make: Sintex Cat Part No-GSJB 2014 or technocommercially equivalent model of approved make.
S&F PVC insulated twin core 1100Volts grade 2.5sqmm copper cable including connecting up with loop in box to security light fittings complete all as specified and as directed.
S&F LED post top lantern of 45 W, IP 65 protection with in built electronic driver and aluminium housing in pure polyester UV resistant powder coated black finish, top maintainable product with top opening die cast cover, anti corrosive stainless steel screws & silicon gasket, HET PMMA diffuser conforming to IS 10322 Part 5/Sec 1: 1987, suitable for pole diameter up to 75 mm, cable entry through plate from bottom, 3 way 10 Amps GPP mains connector duly wired upto terminal block complete all as specified and as directed. Make: Bajaj Cat part No: BL ARIAN P Nx40 WWW PD or techno commercially equivalent model in Wipro, Crompton, Havells, halonix.
S&F automatic Street light timer nature switch using Infrared sensor technology based, three phase 5-8 KW with 03 Nos 16 Amps Contactor rating and three Nos Outgoing MCB of 20 Amp, enclosed in a pole wall mounted rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure (with hinged lid) conforming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass operation) and nature switch operation shall be based on natural light lux level i.e. automatic switching ON at Dusk (580 lux) and switching OFF at Dawn (210 lux) including necessary wiring complete all as specified and as directed. Make: Healer Enterprises Model Swadeep-86-5KW3P with Hensel enclosure confirming IP 66 or equivalent make in Havells/Indoasian
Supply, install, testing and commissioning of Automatic power factor correction panel of rated voltage 415Volts, 3phase, 50HZ, delta connection with super heavy duty cylindrical capacitor of capacity 150 KVAR in a stages of 02 (50 kVAr)+01(25 kVAr)+01(10 kVAr)+2 (5 kVAr)+01(3 kVAr)+01(02 kVAr) consisting of main incomer MCCB of 320A having breaking capacity of 35KA and the panel dimensions approx 1175x500x540(mm) of Make: Havells cat code QHKTC65150X0 and equivalent in makes mentioned here in after
Supply, install, commission and testing cubical type LT panel board outdoor canopy type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof, front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.0 mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles, glands complete all as specified and directed with the following accessories: (Main LT Panel at Trx Yard) INCOMING (a) MCCB 4 pole, 415 Volts, 630 Amps, 50 KA -01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 320 Amps, 35 KA -01 No. (for APFC panel) (b) MCCB 4 pole, 415 Volts, 200 Amps, 25 KA -03 Nos (for LT panels 1,2&3) (c) MCCB 4 pole, 415 Volts, 125 Amps, 16 KA -01 Nos (for Pump House Lt Panel) (d) MCCB 4 pole, 415 Volts, 63 Amps, 10 KA -01 No's (for Street light control) (e) Digital VAF meter for basic electric system monitoring-01 Nos (f) Indicator lamp (RYB) (set of three) - 01 Set
Supply, install, commission and testing cubical type LT panel board outdoor canopy type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof, front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.0 mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles, glands complete all as specified and directed with the following accessories: (Main LT Panel 1,2 & 3) INCOMING (a) MCCB 4 pole, 415 Volts, 200 Amps, 25 KA - 01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 63 Amps, 10 KA -05 No (b) MCB TPN, 415 Volts, 32 Amps, -02 Nos (ipara) (c) Digital VAF meter for basic electric system monitoring-01 Nos (d) Indicator lamp (RYB) (set of three) - 01 Set
Supply and fix tamper proof, digital, AC three phase LT/CT Multifunction DLMS compliance energy meter of accuracy class 0.5 s, 3X415 V, 50 Hz with optical & RS 232 port, backlit LCD display, measures & display trivector energy, load survey, TOD energy, tamper detection & logging, power ON/OFF events, instantaneous parameters comprising of active energy (KWH), Apparent energy (KVAH), Average voltage per phase, average current per phase etc. of rating 200/5 A with display in absence of power with 4 CTs of 200:5 ratio including connection with suitable size copper conductor cable complete all as directed by Engineer-in Charge. Make: HPL Cat part No: TLPB2921131000OC00 or equivalent in L&T, Secure.
Supply and fix sheet metal enclosure outdoor type of 60X60X 35 cm size, floor mounted, made out of CRCA sheet of 3.0 mm thick duly painted with two coats of powder coated paint of approved shade, dust & vermin proof, front door operated with necessary locking arrangement and see through glass mounted on 40x40 x 5 mm MS angle iron frame work with necessary foundation work complete all as directed by Engineer-in Charge.
Surface dressing in hard dense soil not exceeding 15cm deep including site clearance, removing small vegetation, grass grubbing of roots etc including watering and removing surplus soil to a distance outside MoD land and making good surface as directed by Engineer in Charge. Note: (i) The bidders are advised to ascertain the distance outside MoD land and at which the excavated material/ debris are to be disposed off. No extra claim what-so-ever shall be entertained on this account. (ii) This item shall be considered as per the requirement at site. (iii) Removed excavated materials shall be dumped outside MoD land.
Please Enable Macros to View BoQ information
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.90 MB
84641-TENDER-IFA.pdf
Tender Documents • 4.57 MB
BOQ_836162.xls
BOQ • 0.90 MB
84641FinalUpdatedDrg.rar
Additional Documents • 10.95 MB
84641-TD-DRAWINGS.rar
Additional Documents • 32.01 MB
Download all tender documents and submit your bid