Executive Engineer, TLMD-V, Jammu
Office of Executive Engineer, TLMD-V, Jammu
Replacement of Indoor/Outdoor Damaged CT, PT, Isolators and LAs at 220/132/66 KV Grid station Hiranagar for buffer stock for winter preparedness
2024_PDD_258494_1
TLMD-V/J/19 of 2024-25 dated 17-09-2024
Open Tender
Electrical Works
Turn-key
90 days
Gss Hiranagar
AS per SBD and NIT
3 documents required · 3 mandatory
₹2,000
Executive Engineer,TLMD-V,Jammu
₹30,000
Office of Executive Engineer, TLMD-V, Jammu
9 Nov 2024
17 Sept 2024
31 Oct 2024
17 Sept 2024
29 Oct 2024
18 Sept 2024
24 Sept 2024
Amount
Supply part: a) Single phase 50 c/s 145 KV CT (1200-600-300/1A) 5 Core or as per site specification 31.5 KA for one second rated dynamic current 100 KA(peak) class A insulation burden20VA.
b) 145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades.
c) 72.5 KV Surge Arrestor Single phase, 50hz, Rated Voltage 60 KV, Outdoor heavy duty, station class, gapless type with leakage current monitor (WITH SURGE COUNTER) with IP66, prospective symmetrical fault current for pressure relief test 31.5 KA RMS for 0.2s and one minute power frequency with stand voltage 185 KV RMS.Polymer type, compitable with CB duty cycle 0-0.3sec-CO-3 min-CO.
d) 145 KV Surge Arrestor Single phase, 50hz, Rated Voltage 120 KV, Outdoor heavy duty, station class, gapless type with leakage current monitor (WITH SURGE COUNTER) with IP66, prospective symmetrical fault current for pressure relief test 40 KA RMS for 0.2s in 220/132 KV sub station and one minute power frequency with stand voltage 275 KV RMS.Polymer type, compitable with CB duty cycle 0-0.3sec-CO-3 min-CO.
CIVICTRA ENGINEERING AND CONSTRUCTIONS (BID ID -2197486)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .