Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.0 CrAccepted-Finance | ₹6.0 Cr | L1 | Accepted-Finance 1st lowest |
| 2 | L2₹6.4 CrRejected-Finance 138 UDYOG BHAWAN SONAWALA ROAD GOREGAON EAST MUMBAI 63 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400063 | ₹6.4 Cr | L2 | Rejected-Finance 2nd lowest |
| 3 | L3₹6.8 CrRejected-Finance A 602 SARITA GARDEN CHS LTD OPPOSITE SBI BANK VAKOLA PIPELINE SANTACRUZ EAST MUMBAI 400055 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400055 | ₹6.8 Cr | L3 | Rejected-Finance 3rd lowest |
| Sl No | Description | Qty | Unit | Ramsangam Projects Pvt Ltd L3 | Comtech Telesolutions Pvt. Ltd. L2 | Super Electric And Co. L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation, Testing and Commissioning of Air cooled Chiller, Screw type Chilled Water Generator with Microprocessor based Panel with BacNet Gateway to Connect to BMS, with VFD and Operating at below parameters Chilled Water Inlet / Outlet - 12 deg. C / 7 deg. C Chilled Water Flow Rate - 667 GPM with Shell & Tube Type Condenser & Evaporator, suitable for Remote Start / Stop and Auto / Manual Operation Fouling Factor
- 0.001 for Condensers in FPS Units Fouling Factor - 0.0005 for Evaporator in FPS Units Pressure drop for Condenser & Evaporator - 5M Max. Ambient Temperature - 42 Deg.C Capacity : Capacity : 250 TR (Air Cooled Screw Chiller) -Twin independednt circuits with equal capacity of compressor (2W + 1SB) | 3 | Nos | 1,69,60,000 ₹5.1 Cr | 1,65,00,000 ₹5.0 Cr | 1,56,00,000 ₹4.7 Cr |
| 2.00 | SITC of Electric Traction Passenger Lift with
· Rated capacity :- 17 Passenger/1088Kg
· Floors :- G+5 floor (6 Stops/6 Landings)
· Travel :- 24 to 25 mtrs
· Location of Lift Machine:- MR/MRL
· Rated speed :- 1.5mps VS
· Car/Landing door clear opening of ......mm wide x 2200 mm high
· Clear Car size of ......mm wide x ......mm deep x 2250mm high
· Lift shaft available having clear size of ......mm wide x ......mm deep,
......mm Pit depth, ………mm Overhead.
· Doors type :- COPO/TOPO Doors with frame made from SS 304 grade
solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing
doors with SS door architraves/frames The lift doors shall have minimum 1
hour fire rating (with submission of necessary valid test certificate issued
by NABL accredited or Independent test laboratory).
· Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of
1.5mm, thick with hairline finish with frame made from MS girders, bracing of
adequate size with minimum safety factor of 5, with Toe Guard Apron, with
necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS
chequered plate flooring, handrails, mirror, emergency light etc. The lift car
interior design shall be done as per the directions of engineer in charge.
· COP with SS face plate having metallic push buttons with Braille code &
luminous indicator around button with FPI, scrolling UP/DN LED indicator &
with / without attendant key switch, OWD with audio-visual alarm, VAS in
Marathi, Hindi & English with intercom system with telephone instrument in Lift
car, LMR & FCC/ground floor.
· LOP with SS face plate having recess/surface push button box for all
landings with scrolling UP/DN LED indicator having metallic push buttons with
Braille code & luminous indicator around button with CPI, Lift car arrival & next
travel direction audio-visual indication at all landings. | 6 | Nos | 28,00,847 ₹1.7 Cr | 24,75,000 ₹1.5 Cr | 21,19,984 ₹1.3 Cr |
Tender Value
Refer Docs
Closing Date
13 Mar 2026, 1:00 pmClosed
Sambhaji Ghorpade
Office of the Executive Engineer South Mumbai Electrical Division P.W.D. Bandhakam Bhavan 1st floor Marzban Road Fort Mumbai 400 001
Est. No. MESD/MS/OW/1329/2024-25 Supplying, Installation, Testing and commissioning of complete Electrical Installation including all services with necessory allied work for proposed New Mantralaya Building(G 7 Upper Floors), Mantralaya,Mumbai.
2026_PWDM_1284463_1
Est. No. MESD/MS/OW/1329/2024-25
Open Tender
Electrical Works
Mantralaya
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
5 May 2026
6 Mar 2026
16 Mar 2026
6 Mar 2026
13 Mar 2026
6 Mar 2026
Supply, Installation, Testing and Commissioning of Air cooled Chiller, Screw type Chilled Water Generator with Microprocessor based Panel with BacNet Gateway to Connect to BMS, with VFD and Operating at below parameters Chilled Water Inlet / Outlet - 12 deg. C / 7 deg. C Chilled Water Flow Rate - 667 GPM with Shell & Tube Type Condenser & Evaporator, suitable for Remote Start / Stop and Auto / Manual Operation Fouling Factor - 0.001 for Condensers in FPS Units Fouling Factor - 0.0005 for Evaporator in FPS Units Pressure drop for Condenser & Evaporator - 5M Max. Ambient Temperature - 42 Deg.C Capacity : Capacity : 250 TR (Air Cooled Screw Chiller) -Twin independednt circuits with equal capacity of compressor (2W + 1SB)
SITC of Electric Traction Passenger Lift with · Rated capacity :- 17 Passenger/1088Kg · Floors :- G+5 floor (6 Stops/6 Landings) · Travel :- 24 to 25 mtrs · Location of Lift Machine:- MR/MRL · Rated speed :- 1.5mps VS · Car/Landing door clear opening of ......mm wide x 2200 mm high · Clear Car size of ......mm wide x ......mm deep x 2250mm high · Lift shaft available having clear size of ......mm wide x ......mm deep, ......mm Pit depth, ………mm Overhead. · Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). · Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. · COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.31 MB
NonCSR.pdf
Tender Documents • 0.92 MB
BOQ_2208885.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid