temporary shifting of electrical utilities from RD 0.5 to RD 1 90 feet Road Soura using HT AB Cable to pave the way for construction of cycle track under smart city project.
2020_PDD_102948_1
EDIV 15
Open Tender
Electrical and Maintenance Works
Turn-key
14 days
SOURA
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
EXECUTIVE ENGINEER EDIV KHANYAR
₹19,120
Yes
6 Oct 2020
26 Aug 2020
3 Oct 2020
27 Aug 2020
1 Oct 2020
29 Aug 2020
28 Aug 2020 - 28 Aug 2020
Supply, installation, testing and commissioning of:
9 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard (poles available at site)
MS Channel iron(ISLC 75 designation) 100x50x50x6 mm 9' long (2 No) duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paintas per REC Standard .
MS Channel iron(ISLC 75 designation) 75x40x40x6 mm 9' long (8No) duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paintas per REC Standard .
MS Channel iron(ISLC 75 designation) 75x40x40x6 mm 6' long (2 No) duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paintas per REC Standard .
MS Angle iron braces (ISA 5050 designation) 50x50x6mm 6' long (4 No) duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paint as per REC Standard
Providing of Chemical Earthing of Sub-Station for neutral earthing 2 mtr long 50mm dia GI to copper with additional 1 length GI pipe 38mm connected with chemical earthing and with extension of GI strip 25*3mm upto all equipments.Earthing has been laid through insulators to avoid with the existing structure for LA.
Galvanized Nuts & Bolts & washers of sorts. (Galavinsied as per IS-2633/1986)
GI Strip for Earthing 25x5mm as per REC Standard
185 mm² PVC single core LT cable connforming to IS 1554 (part -I) 1988 for incoming and outgoing circuits to be connected with LT Network including thimbling with 185 mm sq Al lugs
Bi matellic Clamps19mm².
11KV 400 AMP Gang Operated switch gear
Drop-out set (Horn-gap type) as per REC standard F6
11KV Lighting Arrester Set (Station type) as per REC standard fonforming to IS 3070 part -III and as per REC standard
shifting of 250kVA/100 KVA/ 16 KVA transformer 11/0.433kV, 3-phase Distribution Transformers and with LV Cable Box having detachable Aluminium Gland plate approved by the Department including earthing of Transformer along with fixing of flat iron strip to be fixed on earthling insulating boots of Sub Stations on two poles structure as per REC Standard F1,F2, F3 F4 &F10 ( Transformer's Available at site)
Fuse set
11KV pinwith insulators Brown glazed porcelain insulator confirming to IS-731/1971 Amendments 1 to 5 type B with 320mm minimum creepage distance and with lead/Zinc thimbles suitable for use with G.I forged pin having small steel heads as per IS-4l86 (P.I) 1993 and IS-2486 (P.II)1989 and revision with latest amendments if any as per REC Standard C-1
Danger plate as per REC Standard
Earthing Rods as per REC Standard (J-1) (Spiral Type)
Earthing insulating boots
Providing, Erection, testing & commissioning of MS Angle iron for Transformer Belt (ISA 5050 designation) 50x50x6mm 10' long duly fabricated as per site requirement and painted with two coats of Red oxide and Al. Paint as per REC Standard
Anticlimbing Device as per REC Standard
Sign Board
11 KV 50 mm ² AB cable
11 KV 50 mm ² AB cable kit heat shrinkable outdoor type
Suspension/ tension clamps
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
8 mts steel tubular pole post 410 (SP-33) IS 2713 (part-II) 1990 as per REC Standard
LT Shackles Insulators brown glazed 90X75MM along with mukki clamps clamp
Pole clamps fabricated out of MS channel
Cement bottoming of pole structures as per REC
Painting of poles/ structure with 2 coats of Al. & red oxide paint and painted of orange colouras per REC Standard
Dismantling of 9 mts/8 mts ST/PCC existing poles and carriage to divisional store
Dismantling of conductor and carriage to divisional store
Dismantling of iron/hardware and other allied material
Dismantling of sub stations along with allied material
Relaying of dismantled conduction for stabilization of LT network
I.T ELECTRIC SUPPLIER
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .