| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance | -20.20% | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.2 Cr+₹4,417.19 (0.04%)Admitted-Finance | -20.17% | ₹1.2 Cr+₹4,417.19 (0.04%) | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | - | Rejected-Technical Similar Work Experience as per Tender T C clause No. 1.2.1 a, Page No. 06 not submitted. |
Tender Value
₹1.5 Cr
EMD Value
₹2.9 L
Closing Date
29 Jun 2026, 12:30 pmClosed
EXECUTIVE ENGINEER(CIVIL)
AIIMS BHUBANESWAR
Renewal of damaged vinyl flooring, provision of wooden racks, overhead storage units and installation of new GI ceiling tiles, etc in all ICUs of Hospital Building, AIIMS, Bhubaneswar.
2026_AIIMO_911977_1
AIIMS/BBSR/Engg./006/2026-27
Open Tender
Civil Works
Percentage
180 days
AIIMS BHUBANESWAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹2.9 L
24 Aug 2026
8 Jun 2026
30 Jun 2026
8 Jun 2026
29 Jun 2026
8 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Careful removal of vinyl flooring from floors /wall area and shifting to store including stacking of serviceable material and disposal of unserviceable material within the campus all complete as directed by Engineer-in-charge | 653 | SQM | 61 | ₹39,833 |
| 2 | Providing and laying self levelling compound 2-3 mm make below wooden flooring / vinyl flooring , to achieve perfect level as per the requirements of the Wooden / vinyl flooring all other complete with approved brand and quality as per tender technical specificaiton & the directions of Engineer-in charge. | 327 | SQM | 903 | ₹2,95,281 |
| 3 | Supplying and laying of 2 mm thick static conductive homogenous vinyl flooring over well cleaned, levelled and dried concrete sub surface as per the manufacturer's specification. Copper strip should be laid crossways at the short ends and the mid joints, whereever required and the copper strips shall be connected to the nearby earthing point. The PVC rolls shall be allowed to acclimatise with the temperature of the area of installation for 24 hours atleast. Appropriate grade of rubber adhesives like Fevicol SR 998 or Aerobond 44 adhesive or equivalent should be used as per manufacturer's specification. The surface shall be pressed thoroughly with light floor roller for proper bonding with the floor. The floor finish should pass over a concealed cove as and when required. Continuous roll should be used and all the joints should be welded by heat fusion process to get seamless floor. The make and colour should match with the existing vinyl flooring as directed by Engineer in charge.. | 653 | SQM | 3,155 | ₹20,60,215 |
| 4 | Providing and fixing false ceiling tiles at all heights of size 595X595 mm of approved texture, design and pattern in true horizontal level suspended on already installed frame work/grids. The exisiting framework/grids shall be cleaned before installation of new false ceiling tiles.The work includes taking out the existing false ceiling tiles and stacking the same in the AIIMS campus as directed by the Engineer in charge. With GI Metal Ceiling Lay in plain Tegular edge Global white colour tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. | 2,056 | SQM | 1,233 | ₹25,35,048 |
| 5 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall: 20 mm nominal dia Pipes | 392 | MTR | 325.96 | ₹1,27,776.32 |
| 6 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points for water supply of approved quality conforming to IS:8931:15 mm nominal bore | 112 | EACH | 558.79 | ₹62,584.48 |
| 7 | Providing and fixing C.P. Brass extension nipple (size 15 mm x 50 mm) of approved make and quality as per direction of Engineer-in-charge. | 112 | EACH | 72.78 | ₹8,151.36 |
| 8 | Providing and fixing Polyvinyl Chloride (PVC) pipes. for water supply/sanitation including all fittings i.e.socket, elbow, tee,etc . This includes jointing of pipes, bends & fittings with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 75 mm nominal dia SWR Pipes | 392 | MTR | 489 | ₹1,91,688 |
| 9 | Providing and fixing Polyvinyl Chloride (PVC) endcap including all fittings with one step PVC solvent cement & testing of joints complete as per direction of Engineer in Charge. 75 mm nominal dia | 112 | EACH | 85 | ₹9,520 |
| 10 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. | 20 | CUM | 256.82 | ₹5,136.4 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.04 MB
eNIT006202627.pdf
Tender Documents • 1.03 MB
BOQ_958459.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .