Garrison Engineer Abohar
Garrison Engineer Abohar Pin-152116
Special repairs to package type AC plant installed in Bldg No P-437 and other sanctioned works at Mil Stn Fazilka
2021_MES_416134_2
GE ABH-51/20-21
Open Tender
Civil Works
Item Rate
120 days
Fazilka Mil Stn
MES Registered Contractor enlisted in class E Category c (i) having deposited standing security of Rs 50000 with departments. Contractors not registered in MES should meet the MES enlistment criteria corresponding to appropriate class and category
5 documents required · 5 mandatory
₹500
Garrison Engineer Abohar
₹16,940
Yes
16 Mar 2021
19 Feb 2021
8 Mar 2021
19 Feb 2021
5 Mar 2021
20 Feb 2021
Amount
SCHEDULE 'A' SECTION I (B&R Portion)
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations etc or manholes, cesspits, pipes and cables etc. not exc 10 Sqm on plan and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge.
M&L Cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation, filling and mass concrete all as specified and directed by Engineer - in - Charge
M&L Brick work with sub class 'B' old size burnt bricks, straight or curved on plan exceeding 6 mtr mean radius built in CM 1:6 all as specified and directed by Engineer - in - Charge .
M&L 40mm thick Damp proof course to horizontal or vertical surfaces inculding necessary formwork in PCC (1:2:4) type B-0 using 12.5mm graded stone aggregate
M & L rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finished even & smooth without using extra cement all as specified and directed by Engineer - in - Charge .
Surface excavation not exceeding 30cm deep and averaging 15cm deep and getting out in loose / soft soil all as specified and directed by Engineer - in – Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge.
Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge.
Providing precast cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregate in window or door cills, lintels, bressumers, steps, quoin blocks (for use with masonry), string courses, copings, kneelers, apex stones, pier caps, columns, posts, boundary pillars, bed plates, pintle blocks, anchorage blocks, bonders (for stone walling), corbels, brackets, etc. (of any section indicated), with plain fair faces, including chamfers, weatherings, throating etc. and setting in cement Mortar 1:4 complete with joints to match complete all as specified and directed by Engineer - in - Charge.
M & L RCC 1:1½:3, (nominal mix), Type A-1, using 20mm graded aggregates as in chajjas including TMT bars welded with existing steel all as specified and directed by Engineer - in - Charge.
M & L mild steel TMT bars 10mm dia and over cut to length bent to shape required including cranking, hooking ends and binding with MS wire (annealed) not less than 0.90mm dia all as specified and directed by Engineer - in - Charge .
M&L 18-20mm thick Granite (of any type) tiles machine cut, in skirting/dado laid over cement screed and jointed with grey cement slurry, and pointed with white cement with admixture of pigment to match the shade of granite stone including grinding and polishing complete over and including 15mm thick rendering in cement mortar (1:4) complete all as specified and directed by Engineer-in-charge.
S&F glazed ceramic tiles in vertical surface 350x250x7mm/ 450x350x7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match over 10mm thick plaster in CM(1:4) on fair face of brick or concrete surface all as specified and directed by Engineer-in-charge.
M&L form work to soffits of suspended slabs such as roof slab and similar work not exceeding 200mm thick for rough finished surfaces of concrete all as specified and directed by Engineer-in-charge.
Applying two coats of cement base paint, white or tinted on new wall surface including preparation of surface.
SCHEDULE 'A' SECTION-II (E&M PORTION)
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth or not exceeding 10sqm on plan and not exceeding 1.5m in depth and all as specified and directed by Engineer - in - Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge.
Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge.
Supplying, installing, lowering and connecting up commissioning and testing submersible pumping set of capacity 2.5 HP, electric driven 415V, three phase ac supply coupled to electric induction motor with suitable RPM suitable for 100 mm dia bore well complete all as specified and directed by Engineer-in-charge.
Boring 100mm dia hole with reserve rotary rig/Direct rotary rig drilling method in any kind of strata of soil rock for depth upto 60mtr deep below ground level by keeping sufficient space for pea gravel complete all as specified and directed by Engineer-in-charge.
Supplying, jointing and lowering PVC slotted pipe 100mm dia heavy duty (HDPE) of pressure rating 6 kgf/cm2 including providing suitable jalli on the slotted pipe complete all as specified and as directed by Engineer-in-Charge.
Supplying, jointing and lowering PVC pipe 100mm dia heavy duty (HDPE) of pressure rating 6 kgf/cm2 including fittings like sockets, ends cap bends etc complete all as specified and as directed by Engineer-in-Charge.
Supply and lowering GI hevy grade pipe 50mm bore ISI marked with one end connected to submersible pump for puping out water including nuts, bolt rubber packing and other necessary connected items complete all as specified and directed by Engineer-in-charge.
S & F gunmetal globe or gate valve with iron wheel head, screwed both ends for GI pipes 25mm bore complete all as specified and directed by Engineer – in – Charge.
Developing, testing and stabilizing of borewell with submersible pump set of suitable capacity not less than 24 hours or till clear water is drained whichever is later including necessary T&P required for developing the borewell complete all as specified and as directed by Engineer-in-Charge.
Supplying and lowering submersible copper conductor cable 6 Sqmm 3 core complete all as specified and as directed by Engineer-in-Charge.
Supplying, laying , jointing and testing, commissioning 25sqmm, 3.5 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor & PVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ducts/fixed on poles/ wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. Note:- Excavation, earth work, sand cushioning and brick protection required for item shall be measured and paid separately under respectively items of BoQ
Supplying and fixing outdoor type feeder pilller box 430 V, 3 Phases, 4 wire, 50 Hz made out of 3.15mm thickness CRCA sheet vermin proof of size 50cmx50cmx30cm including painting with synthetic enamelled paint with aluminium busbar 100 Amps with following items complete all as specified and directed by Engineer-in-Charge. (i) MCCB TPN 63 Amps- 01 (ii) DOL starter suitable for 2.5 HP Submersible pump-01 (iii) Indicating Lamps - 03 (iv) Digital Ammeter (0-20A) - 01 No. (v) Digital Voltmeter (0-500V) - 01
Supply, installation and commissioning of Metal Top Deep Freezer of capacity 400 Ltrs single phase 240 volt, 50 Hz all as specified and directed by Engineer-in-charge.
Supply, installation and commissioning of Metal Top Deep Freezer of capacity 320 Ltrs single phase 240 volt, 50 Hz all as specified and directed by Engineer-in-charge.
S&F switch piano type single pole one way 6 Amp, 230AC all as specified and directed by Engineer-in-Charge. Make: Anchor/Havells/Legend
M&L sub main wiring of PVC FRLS insulated unsheathed 2 core 4.0 Sqmm copper multi stranded conductor including one run of single core copper conductor of size 2.5 sqmm as earth wire drawing in concealed PVC conduit complete all as specified and directed by Engineer-in-Charge.
S&F LED step focus light with die cast aluminium housing designed for rugged outdoor usage with IP 65 protection complete all as specified and directed by Engineer-in-Charge. Make: Cart Part No BGSBL 9W LED WW of Bajaj/Halonix cat part No HLOSPL-02-09-Green/Phillips. Note: Warranty and test certificate of LED light fittings to be produced before incorporating.
Supplying, laying, jointing, testing and commissioning 6sqmm, 2 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor & PVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ducts/fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. Note: Excavation, earth work, sand cushioning and brick protection required for item shall be measured and paid separately under respective items of BoQ.
M & L point wiring complete with 1100 volts grade FRLS insulated unsheathed cable of copper conductor cable multi stranded of size 1.5 sqmm single core including PVC rigid concealed conduit medium grade of suitable size (not less than 20mm dia) with all accessories such as bend reducers/MS hooks, MS junction boxes 2mm thick galvanized steel pressed sunken terminal boxes of suitable sizes for mounting of switches sockets, fan regulators etc covered with 2.8mm thick plastic laminate (Hylem/Anchor) top cover including continuous earth wire of size 1.5 Sqmm PVC stranded copper conductor unsheathed, insulated stranded (Green colour) connected to common earth point dolly complete all as specified and directed at site by Engineer – in – Charge.
M&L for carry out the descaling of shells & tubes water cooled type condenser by dis connecting the inlet and outlet water connections and providing of dummy to the inlet & outlet and descaling the condeser by circulating the circulated descaling agent by R-111 or equivalent chemical or organic compound at the proper ratio circulated chemical till remove complete scale deposite inside the copper tubes, and opening the both end cover by the condenser brushing the copper tubes with appropriate size nylon brush remove complete scale,and fluyshing out the tubes,and degreasing with castic soda solution and flushuing and boxing up the both end covers connecting up the water inlet & outlet connections including renewal by damaged rubber gas kets,and leak testing the joints for water leakage for the 3 x 3.5 TR capacity,Make : Voltas, shell and condensers all as directed by Engineer-in-Charge.
M&L for carrying out leak test for the Chiller type system by extracting the existing available Gas from the system to separate cylinder storing,and pressure testing the complete system with Dry nitrogen and check the leaks,identifying the leak,rectification of leaks by brazzing/welding at the leak points/replacing by damaged valve glandpackage/Gas ket Etc, and after rectificatiopn of all leaks,pressure testing the complete system up to 300 Psig at high side,200 Psig at low side of the system,holding the pressure for 24 Hours and vaccumising the complete system after releasing the Dry nitrogen and charging the refrigerent Gas to system and testing&comissioning the plant of capacity 3 x 3.5 TR and checking all controls all as directed by Engineer-in-Charge
M&L for taking down the defective fan motor of flange mounted extended type shaft upto 1 HP, 3 phase, 415 volts,4 Pole,900 RPM,50 Hz, along with fan assembly, and dismantling the motor complete cleaning with CTC, including rewinding the motor with appropriate gauge copper wire, necessary paper, tape, terminal etc., insulation shall be of class ‘F’ and degree of protection shall be IP-55, the work includes renewal of all corroded bolts & nuts, terminal block, and assembling, fixing in position, fixing of fan blade, and alignment of the fan blade for the suitable air throw of the cooling tower, testing & commissioning the cooling tower motor. all as specified and as directed by the Engineer-in-Charge.
M&L for dismantling the defective induction motor of 3 HP capacity of CGL make 415 V, 4 Pole up to1440 RPM,50Hz of any duty or any class of insulation from the bed duly coupled with pump/ compressor/in AHU, transporting to work shop, removing burnt out winding from stator/ motor, rewinding with suitable gauge of super enamelled copper wire of approved make and replacing drive end and non drive end bearings, insulation materials, varnishing, heating, reassembling, testing and commissioning for the following capacities all as directed Note: - Motors removed for rewinding shall be overhauled completely by replacing defective bearings and the quoted rate shall be deemed to be inclusive of the same.
M&L for carrying out the overhauling the package Air conditioning unit of Make : Voltas of capcity 3X3.5 TR Air cooled Package type including taking out the compressor & cooling coil , blower assembly,diconnecting the discharge and liquid lines and dismantling the sheet metal body for carrying out the tinkery, including replacing fully corrorded bottom base plate and tinkering of partialy corrorded sheet/panel and painting , reassembling, connecting up all disconnected lines, cables ducts etc. and pressure testing, vaccumissing, checking of all parametrs and testing & commisioning all as specified as directed by Engr-in-Charge. : (a) Gas filling will be measured and paid separately.
Supply and charge refrigerant gas R-22 / R 407C including leak testing the system, arresting the leaks with necessary materials like gasket/ ‘O’ rings/ washers all as directed by Engineer-in-Charge. Make : Mafron / Freon / Floron
Supply only following spares for carrying out repairs to Package Air conditioning unit of M/s Voltas/M/s Blue Star/M/s Carrier under relevant here in before. (a) Sealed Compressor of capacity 3 X3.5 TR. Make: Voltas
Complete overhauling/ servicing of FRP cooling tower, removal of complete scales, dirt etc. by using chemicals, cleaning the sump louvers, PVC fills, fan assembly, renewal of spray nozzles with connected pipe, renewal of nuts and bolts,leak arresting of the FRP tank, replacing of PVC fills and complete painting of the cooling tower as per the standard practice of any capacity cooling tower including FRP lining to the bottom base, side panels where ever damaged portion and replacing of birds screen mesh at air intake portion of cooling tower all as specified and directed. NOTE:- PVC Fills shall be meaasured and paid separately under relavent schedule item.
M&L valve, butterfly conforming to IS 13095 supplied and installed complete of size 50 mm (2”) dia
Supply , install, testing and commissioning of pressure guage suitable for Package type AC Plant as per existing complete all as directed by Engr In Charge.
Supply , install, testing and commissioning of temperature guage suitable for Package type AC Plant as per existing complete all as directed by Engr In Charge.
Supply , install, testing and commissioning of relay suiatble for Package type AC Plant operating on DC voltage 18 -52 VDC Catt No- 4602411501 as per existing complete all as directed by Engr In Charge.
M/L for carrying out painting to package type Air conditioning plant including compressor, condensers, chillers, Refrigeration lines Condenser water line, pumps, motors foundation frmer valves etc as per the existing colour code all as directed by Engr-In-Charge. .Note:-1. Painting should be done with existing colour codes. 2. Quoted rate shall deemed to be included for preparation of old painted surface and applying zinc chrome primer over rusted portion all as directed.
Supply and fixing of airduct made out of commercial grade GI sheet (Zinc coating 120 gm/sqm) and fabricated as per IS-655, and aluminium for supply air duct for OTs rooms as per relevant ISand 28 SWG Aluminium perforated sheet Ducting wherever passing through unconditioned space only shall be insulated with resin, Aluminium foil (0.05 mm) faced and fixed with PVC a type is passing through condition space return air space. Outdoor insulation will be finished with cement sand plaster. Ducting should be complied with following jobs with complete satisfaction of Engr-in-Charge. Note : (1) Aluminium powder coated grills/diffusers with MS volume control damper for supply air grills/diffusers.(2)Fresh air intake (3)Fusible link operated (UL stand) fire damper made of 16 SWG. (4) GI/CRCA sheet to be provided in main supply air duct and return air duct. (5) Return Air duct with powder coated aluminium section.
Supply and replace brass float valve assembly with polythene float and fly nut complete fpr 25 mm bore/dia of pipe.
S & F rotational moulded polythene water storage tanks, white colour (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR part I of capacity 1000 Litres all as specified and directed by Engineer - in - Charge .
S&F Compressed bonded minler glass wool 50 mm thick between GI ducting sheet frame inccluding securing it on panel by means of necessary adhesive all as directed all as specified and directed by Engr-in-Charge.
Supplying, laying, jointing, testing and commissioning 50 sqmm, 4 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor & PVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. Note :Excavation, earth work, sand cushioning and brick protection required for item shall be measured and paid separately under respective items of BOQ.
Supplying and Fixing TPN 3 pole 32 A , 415 V, 50Hz having breaking capacity 16KA with all fitting accessories complete all as spd and directed by Engg.in.Charge.Make: Indoasian/Havells/HPL/Hager
Supplying and Fixing MCCB 3 pole 63 A , 415 V, 50Hz having breaking capacity 16KA with all fitting accessories complete all as spd and directed by Engg.in.Charge.Make: Indoasian/Havells/HPL/Hager
S&F Distribution board double door made out of CRCA mild steel sheet surface with insulated material like polyester or with powder coating surface mounting TPN 4 way 415 volts with bus bar rating 200 Amps dust and vermin proof suitable for incorporation of MCB's and isolators etc complete all as specified and directed..
Supplying and Fixing TPN 4 pole 63 A , 415 V, 50Hz having breaking capacity 16KA with all fitting accessories complete all as spd and directed by Engg.in.Charge.Make: Indoasian/Havells/HPL/Hager
S & F of MCB suitable for 240 volts AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 KA and 5 to 32 Amps all as specified and directed.
Supplying and fixing in replacement of contactor MNX-18 type complete as specified and as directed by Engg-in-charge.make-L&T or Equivalent to C & S ,HPL and GE.
Supplying and fixing in replacement of preventor SM-301 type complete as specified and as directed by Engg-in-charge.make-L&T/GIC or Equivalent to C & S ,HPL and GE.
M & L for sand cushioning with dry coarse sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable all as specified and directed by Engineer-in-Charge.
HARSH CONSTRUCTION CO.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .