Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹16.7 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹17.2 L+₹45,930 (2.75%)Rejected-Finance 31 TILAK NAGAR SRI GANGANAGAR 335001 RAJ | GANGANAGAR | RAJASTHAN | 335001 | 2 | Rejected-Finance Not Lowest |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
11 Mar 2021, 6:00 pmClosed
Garrison Engineer Abohar
Garrison Engineer Abohar Pin-152116
Repair/Maint and replacement of Sub Main Wiring distribution boards and allied works at Mil Stn Fazilka
2021_MES_421132_1
GE ABH-52/20-21
Open Tender
Civil Works
Item Rate
180 days
Fazilka Mil Stn
MES Registered Contractor enlisted in class E Category b (i) having deposited standing security of Rs 50000 with departments. Contractors not registered in MES should meet the MES enlistment criteria corresponding to appropriate class and category
5 documents required · 5 mandatory
₹500
Garrison Engineer Abohar
₹40,000
Yes
13 Apr 2021
11 Feb 2021
13 Mar 2021
11 Feb 2021
11 Mar 2021
26 Feb 2021
Amount
M&L for submain wiring comprising single core 4 Runs of 10 sqmm nominal cross sectional area multistrand copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia PVC conduits and conduit fittings complete, including provision of 2 x 6 sqmm nominal cross sectional area multistrand copper conductor cable PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 4 Runs of 6 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. PVC conduits and conduit fittings complete, including provision of 2 x 4 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 4 Runs of 10 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia in PVC casing and caping and its fittings complete, including provision of 2 X 6 sqmm nominal cross sectional area multimultistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 4 Runs of 6 Sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC casing and caping and its fittings complete including provision of 2 X 4 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core 2 Runs of 10 Sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC conduit and its fittings complete including provision of 1 X 6.0 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 2 Runs of 6 Sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC conduit and its fittings complete including provision of 1 X 4.0 sqmm nominal cross sectional area multimultistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 2 Runs of 4 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia in PVC conduit and its fittings complete including provision of 1 X 2.5 sqmm nominal cross sectional area multimultistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main complete all as specified and directed by Engr-In-charge. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core ,2 Runs of 10 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC casing and caping and its fittings complete including provision of 1 X 6.0 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 2 Runs of 6 Sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC casing and caping and its fittings complete including provision of 1 X 4.0 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M&L for submain wiring comprising single core, 2 Runs of 4 Sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade drawing in and including appropriate dia. in PVC casing and caping and its fittings complete including provision of 1 X 2.5 sqmm nominal cross sectional area multistranded copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete incl taking down old UNSV sub main all as specified. ( Note :- Extra length of cables/ wire required for connection to MCBs shall not be measured and the rate quoted by contractor for per unit shall be deemed accordingly)
M & L cutting chases, pinning in, making god to facings where reuired and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc ; and cutting chases for concealed water tubing or concealed wiring etc, and making good, cutting not exc 10 cm girth in brick walls complete all as directed by Engr-in-charge .
Taking down existing control board and supplying and fixing CRCA sheet metal board made of 2.0 mm thick metal sheet and painting 2 coats of synthatic enamel paint over a coat of primer inluding copper bus bar and fixed with wall for fixing 04 Nos of meters complete with wiring,fitting and accessories, locking arrangement with handle (not less than size of box 100cmx80cmx25cm and adequate depth for the following equipments,internal wiring and termination of external cables,lugs,glands,wire thimbles and conduit/flexible pipe for finishing as required) comprise of following:- (a) Incoming 63 Amps 4 pole MCCB 25 KA -01 Nos (b) Bus bar of 200 Amps TPN & Earth (c) 40 Amps DP MCB -04 Nos ( for Electric DU Meter) (d) 10 Amps DP MCB - 01 Nos ( out going for Stair case/garage light circuit) (e) Fixing only existing single phase KWH meter -04 Nos after taking out carefully for refixing in panel.
Dismantling of existisng unserviceable MCB distribution board and S&F sheet metal enclouser TPN DB having facility to fix MCCB incomer upto 125Amps and MCBs in outgoing, TPN 4 ways, Double door type complete fitted with bus bars, neutral links, IP-43 protection Isolated Neutral bar,door earthing,cement spill ptorector and blanking plates including making good disturbed surfaces complete all as specified and directed. make- Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells
Dismantling of existisng unserviceable MCB distribution board and S&F sheet metal enclouser SPN DB having facility to fix MCB in incomer and MCBs in outgoing, SPN 12 ways, Double door type complete fitted with bus bars, neutral links,blanking plates including making good disturbed surfaces complete all as specified and directed. make- Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells
Dismantling of existisng unserviceable MCB distribution board and S&F sheet metal enclouser SPN DB having facility to fix MCB in incomer and MCBs in outgoing, SPN 8 ways, Double door type complete fitted with bus bars, neutral links,blanking plates including making good disturbed surfaces complete all as specified and directed. make- Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells
Dismantling of existisng unserviceable MCB distribution board and S&F sheet metal enclouser SPN DB having facility to fix MCB in incomer and MCBs in outgoing, SPN 4 ways, Double door type complete fitted with bus bars, neutral links, blanking plates including making good disturbed surfaces complete all as specified and directed. make- Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells
Supply and fixing Plug and socket type DB (Functional Unit) 20 Amps capacity with provision of single pole 20 amps MCB, plug top and earth plug, grouted flush to walls complete all as specified. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells Schneider/C&S)
Supply and fixing MCCB TPN (4pole) 63 Amps 415 Volts of braking capacity 36 KA (Adjustable Thermal and Adjustable Magnetic Release Setting) complete taking down old unserviceable one and making necessary connections as existing and cleaning the terminals with CTC solutions complete all as specified and directed. Make :IndoAsian Cat No: 830330 to 830335 or equvalent of Havells/LegrandSchneider/HPL/Standard
All as per Ser Item No 18 but 100 Amps with breaking capacity 36 KA.
All as per Ser Item No 18 but 125 Amps with breaking capacity 36 KA.
All as per Ser Item No 18 but 160 Amps with breaking capacity 36 KA.
Supply and fixing MCB TPN 100 Amp, 10 KA 415 Volt in repair. Make : Havells/Legrand
Supply and fixing MCB TPN 63 Amp, 10 KA 415 Volt in repair. Make : Havells/Legrand
S&F TPN, 415 Volts, of 63 amps current rating complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
S&F Isolator TPN, 415 Volts, of 100 amps current rating complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
S&F Isolator, Double pole, 240 Volts, of 32 amps current rating complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
S&F Isolator, Double pole, 240 Volts, of 40 amps current rating complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
S&F Isolator, Double pole, 240 Volts, of 63 amps current rating complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
S&F Miniature circuit breaker (MCB), single pole, 240 Volts, of 6-32 amps current rating and 10 KA breaking capacity, B' series type complete all as directed by Engr-in-charge. Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
Taking out faulty underground 1100 volt grade LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or rerouting after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required complete all as specified and directed. Note:1. New LT cable replace with fault portion ,joints shall be measured and paid separately under respective items of the schdule. 2. Retrived old serviceable bricks will be laid in trenches for cable protection. if extra bricks and sand required at site shall be measured and paid separately under respective items of the schdule. 3. Earth work and excavation will be measured and paid separately under respective items of the schdule.
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable of size 2 core 10 sqmm nominal cross section in service connections of PVC insulated aluminium multi standard conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed complete all as specified and directed by Engr-In-charge.make- Havells/Plaza/Finolex/Kalinga/Kei/Anchor
All as per Item No 31above here-in-before but 2 core 6 sqmm complete all as specified and directed.
All as per Item No.31 above here-in-before but 2 core 4 sqmm complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm 4 core including taking down old unserviceable complete all as specified. Make: Kalinga/Plaza/Gloster/Havells/Finolex/POlycab/Kei or equvalent makes
All as per item No.34 above herein before but the size 25 sqmm 4 core
Excavation in trenches not exceeding 1.5 mtr depth width and not exceeding 1.5m depth for laying under ground cable in loose/soft soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm.
Removal of surplus soil obtained from excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point.
M&L for sand cushioning for protection of PVC cable with screen wash river sand and punning to proper required cover.
M&L for bricks of sub class ‘B’ bricks, for cable protection in trenches laid dry and flat.
Relaying old bricks of any type and size bricks, for cable protection in trenches laid dry and flat.
M&L for PCC preparation including cutting up to 45 cm width and depth of the road/hard standing and making good disturbed surfaces by using PCC type C2(1:3:6) by using 40mm graded stone aggregate for the fixing the pipe/laying cables complete all as directed by the Engr. in Charge.
M&L for 40mm dia steel tubes (light grade) galvanised with fittings, laid in trenches/wall for protection of underground earth strip when crossing the road/fixing on wall as in repair complete all as specified and directed. (MAKE: JINDAL/PRAKASH/SURYA)
M&L for 50mm dia steel tubes (light grade) galvanised with fittings, laid in trenches/wall for protection of underground earth strip when crossing the road/fixing on wall as in repair complete all as specified and directed. (MAKE: JINDAL/PRAKASH/SURYA)
Material and labour for disconnecting faulty/burnt end portion of cable by removing the cable from loop including necessary excavation & earth work, relaying and reconnecting the cable by removing faulty/burnt portion of incoming and out going cables at pole connection/panel boards and preparing fresh terminals with suitable size of thimbles,lugs and glands or gland plates as suitable of any size and number of cables incoming out going at panel board`
M&L for Boring hole across the Road/plinth/hardstanding/path/drain/pavement etc., suitable for inserting HDPE/GI pipe of upto 100mm dia bore pipe for 0.4 mpa working pressure for cable passing without damaging existing Raod/path/hardstanding/floor by trenchless technology or manual using necessary equipment complete all as specified and directed.Make-Legrand/L&T Hager/C&S/INDO KOPP/Indo Asian/Standard/Havells/ Schneider/C&S)
Demolition the broken earth pit chamber and constructing new earth pit chamber and PCC chamber cover only complete as per SSR Pt -I of 1996 including new wire mesh funnel all as directed.
Supply only aluminium lugs suitable for cable of size 10 to 16 sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for cable of size 25 sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for cable of size 35 sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for cable of size 50 sqmm complete all as specified and directed.
Taking down care fully existing burnt/faulty/loose incoming and out going cables connections from building dist panel to pole of any size and removing carefully unserviceable switch gears/DB's and measuring instruments for reuse/refixing of serviceable items and repair/maint and servicing of existing Bldg dist panel by replacing hinges,switch gear compartments with rubber sheal,locks, nuts,bolts and washers and provn of danger notice boards, indicators of three nos with colour coding as existing and tape bus bar with insulation sleeves to three phases and neautral with colour coading and painted with two coats powder coating primer and also reconnecting all cables in same position with suitable glands,gland plates,aluminium lugs, nut bolts and washers after cleaning with CTC solution and apply silica gel to terminal junctions. Note: Supply and fix Switch gears against unserviceable measured and paid separately with relevent items of this schedule.
S&F LED tube light fixture, environmental friendly energy efficient ready to use 18/20W LED 6500K and above (4') complete all as specified and directed by Engr-In-charge. Make:Syska Price SSK-ALB-20W I & SSK-TL-20W I or equvalent of Havells/Crompton Greaves/ Philips/Wipro/Polycab as recommended by Engr-Incharge and approved by GE.
S&F batton for LED tube light fixture with extruded aluminium heat sink, environmental friendly energy efficient ready to use with 18/20 W LED 6000K and above (4') including electric connection with PVC copper flexible twin core cable, 1.0 sqmm from ceiling rose to light fitting complete all as specified and directed by Engr-In-charge. Make: Havells/Crompton Greaves/ Philips/Wipro/Syska/polycab as recommended by Engr-Incharge and approved by GE.
S&F for LED tube light fitting of LED T5 tube lights (6500K) environomental friendly energy efficient of 18/20 Watt LED including electric connection with PVC copper flexible twin core cable, 1.0 sqmm from ceiling rose to light fitting complete all as specified and directed by Engr-In-charge. Make:Syska SSK-SQ2001 20W or equvalent of Havells/Crompton Greaves/ Philips/Wipro/Polycab as recommended by Engr-Incharge and approved by GE.
S & F LED bldg street light luminaires 20/25 watts with IP66 complete with pressure dia cast aluminium housing with GI pipe bracket made out of 25 mm dia medium grade pipe (60 cm long) bend to shape including fixing arrangement to wall with MS flat 25x3mm-2 Nos by nut, bolts and washers including electric connection with PVC copper flexible twin core cable 1.0 sqmm from ceiling rose to light fitting complete all as specified and directed by Engr-In-charge. Make:Syska max glow series SSK-ST25W-MG or equvalent of Havells/Crompton Greaves/ Philips/Wipro/Polycab as recommended by Engr-Incharge and approved by GE.
S & F LED bldg street light luminaitres 15 watts with IP66 complete with pressure dia cast aluminium housing with GI pipe bracket made out of 25 mm dia medium grade pipe (60 cm long) bend to shape including fixing arrangement to wall with MS flat 25x3mm-2 Nos by nut, bolts and washers including electric connection with PVC copper flexible twin core cable 1.0 sqmm from ceiling rose to light fitting complete all as specified and directed by Engr-In-charge. Make:Syska max glow series SSK-MST 15W or equvalent of Havells/Crompton Greaves/ Philips/Wipro/Polycab as recommended by Engr-Incharge and approved by GE.
S&F for Skylux LED efficient LED surface 2'x2' luminaire & glare free soft illumination of capacity 36Watt LED white colour complete all as specified and directed by Engr-In-charge. Make:Bajaj BZSSQL 36W LED WH or equvalent of Havells/Crompton Greaves/ Philips/Wipro/Syska as recommended by Engr-Incharge and approved by GE.
S&F for Galaxy LED suspended type decorative LED low bay luminaire white colour of capacity 24 Watt complete all as specified and directed by Engr-InCharge Make: Bajaj BLSPD LED 24W WH or equivalent in Havlls/Crompton Greaves/ Philips/Wipro/Syska as approved by GE.
S&F for WEE Plus LED bulk head luminaire of capacity 10 Watt an ideal energy efficient solution for upgrading conventional GLS bulkhead luminaires to LED bulk head IP 65 complete all as specified and directed by Engr-InCharge Make: Bajaj BIBWP LED 10W WH or equivalent in Havlls/Crompton Greaves/ Philips/Wipro/Syska as approved by GE.
S&F for LED building street light luminaire of capacity 20 Watt with pressure die-cast housing with individual LEDs as light source and lens embedded PC cover having TOP opening separate driver compartment with IP 66 protection and impact resistance of IK 07 Make: Bajaj BRLEPLED 20W LED V2 or equivalent in Havlls/Crompton Greaves/ Philips/Wipro/Syska as approved by GE.
M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI wire 4 mm dia earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing.( GI wire upto 7.5m including testing consider in this item).
Singla Electricals
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .