Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹29.1 LAccepted-Finance | L-1 | Accepted-Finance Found L-1 | |
| 2 | L-2₹30.3 L+₹1.3 L (4.33%)Rejected-Finance DHALIWAL | L-2 | Rejected-Finance Not found L-1 | |
| 3 | L-3₹31.9 L+₹2.8 L (9.61%)Rejected-Finance | L-3 | Rejected-Finance Not found L-1 | |
| 4 | L-4₹32.1 L+₹3.0 L (10.4%)Rejected-Finance DHALIWAL | SANGRUR | PUNJAB | 148001 | L-4 | Rejected-Finance Not found L-1 | |
| 5 | L-5₹32.1 L+₹3.1 L (10.5%)Rejected-Finance HIMACHAL PRADESH HP | BILASPUR | HIMACHAL PRADESH | 174001 | L-5 | Rejected-Finance Not found L-1 |
Tender Value
₹47.3 L
EMD Value
₹78,432
Closing Date
27 Sept 2023, 5:00 pmClosed
Executive Engineer Jal Shakti Divn No.1 Una HP
Executive Engineer Jal Shakti Divn No.1 Una HP
(Sub Head Laying, Jointing, testing and commissioning of Rising Mains and Supply and Erection of Pumping Machinery)
2023_HPIPH_78959_1
No. JSV-1/TA/ E-tender/23-12249-63 Dated 16-09-23
Open Tender
Civil Works
Item Rate
180 days
Haroli Consty
as per NIT
11 documents required · 11 mandatory
₹800
Yes
Executive Engineer Jal Shakti Divn No.1 Una HP
₹78,432
Yes
4 Dec 2023
18 Sept 2023
28 Sept 2023
18 Sept 2023
27 Sept 2023
18 Sept 2023
18 Sept 2023 - 27 Sept 2023
Amount
Excavation in foundation trenches ( for pipes and pits ) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft / hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts including trimming and dressing of sides, levelling of beds to correct grade including, shoring, strutting, planking, timbering and dewatering, wherever required, stacking the useable and unuseable material/ soil separately and after laying, jointing and testing of pipes returing the useable soil in trenches in 15 cm ( Fifteen centimeter ) layers including consolidating of such deposited layer by ramming and watering and then disposing of all surplus excavated soil /un-useable materials as directed within all leads and lifts including restoration of un-metalled surface to its original condition and including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge.
Laying,Jointing and Testing in trenches Galvanized mild steel flanged/butt welded pipe of below mentioned dia and grade conforming to IS 1239-2004 (with latest ammendments The M.S. flanges are to be provided 5% of total joints as per table below conforming to 6392-1971 ( Latest uptodate ammendments) and welding of M.S. flanges with pipe as per IS: 816-1965 with electrode as per IS: 814-1967 including required Nos. and size of M.S. nuts and bolts as per IS: 1369-1967 and compressed asbestos fibre jointing gaskets sheet not less than 3mm thick as per IS: 27121-1965. The welding of flanges to be done on both faces in three layers in each face to make the joints leak proof including all kind of specials such as bends of all degree to be made from parent tube, short pieces, tail pieces all made from parent tube and to the entire satisfaction of enginer-in-charge. The pipes end should be bevelled suitable for butt welding. The circumferencial butt welded joints ( 95% of the total joints) by electrical arc welding to following dia & class pipes,welding of pipes to be done in three layers to make the joints leak proof and to achieve the minimum effective throat thickness of weld conforming to IS- 816-1969 specifications, by using welding electrodes of 2.5 mm to 6.3 mm of Advani oerlikon (Adore)-CITOJET/ESAB make, conforming to IS 814-1991, at site of work complete in all respects and including DPT test for joints & manual/mechnical handing of pipes. The laying of pipe shall confirm to BIS-5822 (with latest ammendments uptodate), including all kind of specials such as bends of all degree to be made from parent tube, short pieces, tail pieces all made from parent tube within all leads and lifts. ( Earth work in trenches, M.S. flanges and butt welded joints to be measured and paid for separately)
65 mm dia GMS pipe (Heavy Class) for R/Main, from RD. 0/0 to 1510 for Village Chandpur Kalehra Zone A , for R/Main, from RD. 0/0 to 1510 for Village Chandpur and R/Main, from RD. 0/0 to 250 for Village Chandpur & Kulehra Zone B.
100 mm dia GMS pipe (Medium Class) for R/Main, from RD. 0/0 to 150 for Village Badewal Zone A and R/Main from RD 0/0 to 2985 for village Badewal Zone B.
Providing and welding M.S. flanges at suitable point, conforming to following tables as per IS: 6392-1971 (Latest with upto date amendments) with plain end GMS pipe in three number (2 outer and 1 inner) of layers on both faces to make the joint leak proof (The cost of providing and laying of GMS pipes to be measured and paid for seprately). The welding of flanges should conform to IS:816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364. including cost of gasket sheet nuts & bolts. The thickness of gasket sheet not less then 3.00 mm conforming to IS 2712-1998. The work shall be done to the entire satifaction of engineer in charge with in all leads and lifts to the entire satisfaction of Engineer-in-Charge.
65 mm dia Table-17 From RD. 0 to 810 (Zone-A)
65 mm dia Table-5 From RD. 810 to 1510 (Zone A) & From RD. 0 to 250 (Zone-B)
100 mm dia Table-17 From RD. 0 to 1080 Rmts (Zone-B)
100 mm dia Table-5 From RD. 0 to 150 (Zone A) & From RD. 1080 to to 2985 (Zone-B)
Providing circumferencial Butt welded joints by electrical arc welding to following dia & class pipes, welding of pipes to be done in three layes (Two Outer and one inner side) to make the joints leak proof and to o achieve the minimum effective throat thickness of weld conforming to IS: 816-1969 specifications, by using welding electrodes of 2.5 mm to 6.3 mm of Adani Oerlikon (Adore) - CITOJET/ESAB make, conforming to IS:814-1991, at site of work complete in all respects, including DPT test for Joints & manual / mechanical handling of pipes in all leads and lifts to the entire satisfaction of Engineer-in-Charge.
65 mm dia GMS Pipe (H)
100 mm dia GMS Pipe (M)
Submersible Pumping Machinery for T/Well Chandpur
Supply of submersible pumping set of KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ; 9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear. It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable, errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurers certificate o be attached performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) BHP iv). speed v) Insulation
Discharge = (Q) 5.28 LPS
Total Head = ( H) 96.93 Mts.
a) SWL in Tubewell = 57.97 Mtr. bgl.
c) R.L. point of discharge = 396.10 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. = 9.00 Mtrs.
e) Drawdown in Tubewell = 15.25 Mtrs.
f) R.L of lowest point of pumpset installation = 310.93 Mtrs.
g) Static column lift = 85.17 Mtrs.
Rising main.
Length 15 Mtrs.
Dia meter. 80 mm
Class GMS Pipe (MG)
Column Pipe.
Length 92.17Mtr.
Dia 65 mm
Class GMS. (M)
Pumping hours = 8.00 Hours
Altitude of installations above M.S.L. 350 Mtr.
Characteristic of water.
a) Temperature 20 Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well = 203.00 Mtr.
Dia of T/ well assembly 300mm & 200 mm
Length of assembly pipe. 203.00 meter .
Dia of housing pipe 300 mm
Length of housing pipe. meter
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing:- Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation : Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Driver Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Delivery size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments. i) Make : ii) Type : iii) Capacity : 63 amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. Panel/ Switch Board i) Drawing. ii) Layout Plan
MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. i) Make : ii) Type : iii) Range 63 amp. iv) Capacity
ELCB of recommended make L&T /Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63 Amp. iv) Capacity
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500.
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. 3 phase indicators i) Make : ii) Type : iii) Rating
Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452 (P- I&II ) with upto date amendments. 3 Phase indicators
Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range. 4 KVAR
Providing suitable starter of L&T/ Havell's /BHEL make as per IS :13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release, with or without 'initial oil filling as the case may be with Air Break. Type Star Delta with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : iii) Range.
Providing and fixing double flanged Cast iron Sluice valve of Leader / Kirloskar / Kartar/LP/RG Brand make for the delivery line of pump and capable of withstanding the normal seat pressure and as per IS :- 780-1992 with latest ammendments i) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 65 mm dia
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make for the coulmn pipe of pump and capable of withstanding the normal seat pressure and as per IS :- 5312 Part-1 with latest ammendments i) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Rising main 80 mm dia
Providing and fixing pressure gauge of Prega / Precision make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements. i) Make :
Supply of PVC jointless, flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havells/ Finolex make suitable for the pumpsets offered from MCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe, solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor. The type, size and make shall be subject to approval of HPSEB authorities. i) Make : Finolex/ Havells ii) Size 3x 2.50 mm2 iii). type- IV capacity V Core-3
Lowering of GMS Column pipefor assembly 65 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No. 7.02. The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Malahat. Column Pipe 65 mm dia GMS pipe).
Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 (P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply Side From meter of HPSEB to Bus Bar and Switch) i) Size 4.00 mm2 ii) Make Finolex/Havells. iii) Type iv) Capacity v) Core 3.
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 8 SWG upto 15 HP
Submersible Pumping Machinery for T/Well Badewal
Supply of submersible pumping set of KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ; 9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear. It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable, errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate o be attached performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) BHP iv). speed v) Insulation
Discharge = (Q) 14.06 LPS
Total Head = ( H) 201.80 Mts.
a) SWL in Tubewell = 158.53 Mtr. bgl.
c) R.L. point of discharge = 410.45 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. = 9.00 Mtrs.
e) Drawdown in Tubewell = 15.25 Mtrs.
f) R.L of lowest point of pumpset installation = 224.67 Mtrs.
g) Static column lift = 185.78 Mtrs.
Rising main.
Length 15 Mtrs.
Dia meter. 125 mm
Class GMS Pipe (MG)
Column Pipe.
Length 192.78 Mtr.
Dia 100 mm
Class GMS. (M)
Pumping hours = 8.00 Hours
Altitude of installations above M.S.L. 350 Mtr.
Characteristic of water.
a) Temperature 20 Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well = 296.00 Mtr.
Dia of T/ well assembly 300mm & 200 mm
Length of assembly pipe. 296 meter .
Dia of housing pipe 300 mm
Length of housing pipe. meter
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing:- Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation : Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Driver Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Delivery size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments. i) Make : ii) Type : iii) Capacity : 200 amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. Panel/ Switch Board i) Drawing. ii) Layout Plan
OCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. i) Make : ii) Type : iii) Range 200 amp. iv) Capacity
ELR of recommended make L&T /Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELR. Make : ii) Type : iii) Range 200Amp. iv) Capacity
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500.
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. 3 phase indicators i) Make : ii) Type : iii) Rating
Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452 (P- I&II ) with upto date amendments. 3 Phase indicators
Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range. 16 KVAR
Providing suitable starter of L&T/ Havell's /BHEL make as per IS :13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release, with or without 'initial oil filling as the case may be with Air Break. Type Star Delta with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : iii) Range.
Providing and fixing double flanged Cast steel Sluice valve of Leader / Kirloskar/Kartar /LP/RG Brand make for the delivery line of pump and capable of withstanding the normal seat pressure and as per IS :- 780-1992 with latest ammendments i) Make : ii) Type : iii) Make :- Cast steel Class ASA 300 API 600 for Column Pipe 125 mm dia
Providing and fixing of double flanged Cast steel swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make for the coulmn pipe of pump and capable of withstanding the normal seat pressure and as per API-6D with latest ammendments i) Make : ii) Type : iii) Make :- Cast steel Class ASA 150 API 600 for Column Pipe 125 mm dia
Providing and fixing pressure gauge of Prega / Precision make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements. i) Make :
Supply of PVC jointless, flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havells/ Finolex make suitable for the pumpsets offered from OCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe, solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor. The type, size and make shall be subject to approval of HPSEB authorities. i) Make : Finolex/ Havells ii) Size 3x 35.00 mm2 iii). type- IV capacity V Core-3
Lowering of GMS (M) Column pipe for assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No. 28.01. The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Malahat. Column Pipe 65 mm dia GMS pipe (M)
Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 (P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply Side From meter of HPSEB to Bus Bar and Switch) i) Size 70.00 mm2 ii) Make Finolex/Havells. iii) Type iv) Capacity v) Core 3.
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 25x3.00 mm
Centrifugal Pump Set for T/Well Chandpur Zone A
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrange-ment) Single /double /multi stage of Kirloskar / KSB Crompton KSB/Calama/BS/ Groundfos/ Hindustan/ Lubbi make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate to be attached. performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) Rating iv). speed v) Insulation (C) Coupling (D) Base plate
Discharge (Q) = 2.33 LPS.
Total Head (H) = 147.35 Mtrs.
a)LWL In Sump well = 393.10 mtr
b)R.L. of shaft = 393.10 Mtrs.
c)R.L. of discharge Pt. = 509.65 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 116.55 Mtrs.
f) Static Head = Mtrs.
Rising main.
Length = 1510 Mtrs.
Diameter = 65mm. dia
Class GMS Tube(H)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =425 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 Amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 32 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 32 Amp.
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : Amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 3 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 50 mm dia Delivery pipe of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.60 for delivery pipe of pump
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 65 50 mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.60 for delivery pipe of pump
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 80 mm dia having by pass arrangment for the rising Main and capable with standing the normal Seat Pressure as per IS: 5312-1992 part-1 class PN 1.60 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.26.01.( GMS Pipe shall be issued by the department free of cost from Divisional store at Malahat . The size of various components to be as under:-
Suction Pipe 65 mm dia (M)
Delivery pipe 50 mm dia (M)
Comman Header 65 mm dia (H)and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 65 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 2.50 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 4.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 8 SWG upto 15 HP
Centrifugal Pump Set for T/Well Chandpur Zone B
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrange-ment) Single /double /multi stage of Kirloskar / KSB Crompton KSB/Calama/BS/ Groundfos/ Hindustan/ Lubbi make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate to be attached. performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) Rating iv). speed v) Insulation (C) Coupling (D) Base plate
Discharge (Q) = 2.95 LPS.
Total Head (H) = 38.70 Mtrs.
a)LWL In Sump well = 393.10 mtr
b)R.L. of shaft = 393.10 Mtrs.
c)R.L. of discharge Pt. = 420.75 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 116.55 Mtrs.
f) Static Head = 27.65 Mtrs.
Rising main.
Length = 250 Mtrs.
Diameter = 65mm. dia
Class GMS Tube(H)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =425 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 Amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 32 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 32 Amp.
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : Amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 2 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing Hour run meter of recommended make of suitable capacity as per IS :722 (Latest edition) i) Type ii) Make iii) Range
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 50 mm dia Delivery pipe of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 65 mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 65 mm dia having by pass arrangment for the rising Main and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No. 50.02 (GMS Pipe shall be issued by the department free of cost from Divisional store at Malahat. The size of various components to be as under:-
Suction Pipe 65 mm dia (M)
Delivery pipe 50 mm dia (M)
Comman Header 65 mm dia (H) and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 65 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 2.50 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 2.5 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 8 SWG upto 15 HP
Centrifugal Pump Set for T/Well Badewal Zone A
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrange-ment) Single /double /multi stage of Kirloskar / KSB Crompton KSB/Calama/BS/ Groundfos/ Hindustan/ Lubbi make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate to be attached. performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) Rating iv). speed v) Insulation (C) Coupling (D) Base plate
Discharge (Q) = 7.28 LPS.
Total Head (H) = 42.87 Mtrs.
a)LWL In Sump well = 407.45 mtr
b)R.L. of shaft = 407.45 Mtrs.
c)R.L. of discharge Pt. = 443.80 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 36.35 mtrs.
f) Static Head = 36.35 Mtrs.
Rising main.
Length = 150 Mtrs.
Diameter = 100 mm. dia
Class GMS Tube (M)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =425 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having sutable capacity of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : Amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 32 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 32 Amp.
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 3 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing Hour run meter of recommended make of suitable capacity as per IS :722 (Latest edition) i) Type ii) Make iii) Range
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 80 mm dia Delivery pipe of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 100mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 100 mm dia having by pass arrangment for the rising Main and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.74.02 (GMS Pipe shall be issued by the department free of cost from Divisional store Malahat. The size of various components to be as under:-
Suction Pipe 100 mm dia (M)
Delivery pipe 80 mm dia
Comman Header 100 mm dia and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 65 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 2.50 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 4.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 8 SWG upto 15 HP
Centrifugal Pump Set for T/Well Badewal Zone B
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrange-ment) Single /double /multi stage of Kirloskar / KSB Crompton KSB/Calama/BS/ Groundfos/ Hindustan/ Lubbi make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacurer's certificate to be attached. performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) Rating iv). speed v) Insulation (C) Coupling (D) Base plate
Discharge (Q) = 6.78 LPS.
Total Head (H) = 72.84 Mtrs.
a)LWL In Sump well = 407.45 mtr
b)R.L. of shaft = 407.45 Mtrs.
c)R.L. of discharge Pt. = 429.25 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 21.80 mtrs.
f) Static Head = 21.80 Mtrs.
Rising main.
Length = 2985 Mtrs.
Diameter = 100 mm. dia
Class GMS Tube(M)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =425 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 63 Amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 63 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 63 Amp.
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having suitable capacity of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 Amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 4 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 80 mm dia Delivery pipe of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 100mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.00 for delivery pipe of pump
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 100 mm dia having by pass arrangment for the rising Main and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.97.02.(GMS Pipe shall be issued by the department free of cost from Divisional store Badoh (Gagret) Una . The size of various components to be as under:-
Suction Pipe 125 mm dia (M)
Delivery pipe 80 mm dia
Comman Header 100 mm (M) dia and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 65 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 2.50 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 4.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with G.I. plate 600 x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 8 SWG upto 15 HP
M/s Kamla Contruction
Nishant Puri Govt Contractor
Gaurav Attri
Varun Mehan
SG Engineers and Consultants
ShriBalajiEnginearingWorks
Jaiveer Singh
Suresh Kumar Govt Contractor
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .