Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹100.0 LAdmitted-Finance 2ND FLOOR RUSHLENE BAKSHI 4 25 KIRTI NAGAR INDUSTRIAL AREA WEST DELHI DELHI 110015 | WEST DELHI | DELHI | 110015 | L1 | Admitted-Finance | |
| 2 | L2₹1.2 Cr+₹22.9 L (22.9%)Admitted-Finance 309 SKYLARK BUILDING 309 SKYLARK BUILDING 60 NEHRU PLACE NEW DELHI NEW DELHI DELHI 110019 | SOUTH EAST DELHI | DELHI | 110019 | L2 | Admitted-Finance | |
| 3 | L3₹1.5 Cr+₹50.0 L (50.1%)Admitted-Finance PLOT NO 234 BBN ENERGY SYSTEMS PRIVATE LIMITED 234 SECTOR 37 PHASE VI UDYOG VIHAR GURGAON GURGAON HARYANA 122001 | GURUGRAM | HARYANA | 122001 | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Nikom Infrasolutions Pvt. Ltd. L2 | BBN ENERGY SYSTEMS PVT LTD L3 | Labotek L1 |
|---|---|---|---|---|---|---|
| 1.00Sub Head - I (under PLN fund) Supplying, installation, testing and commissioning of 3 x 60 kVA Modular live swappable UPS with (N+1) configuration and each power cabinet shall be consisting of multiple numbers of Live swappable power modules with following specifications. Location: CSC, IIT Delhi Transformer less, IGBT Rectifier & IGBT Inverter Modular Scalable Live Swappable UPS System UPS Modules must be of 30 KW Rating in each 60 KW power cabinet. Input Voltage 380/400/415(Minimum) VAC, three-phase Input Voltage Range 331 to 477 V Input Frequency and tolerance 40 to 70Hz Input Total Harmonics Distortion <1% at 100% load Input Power factor ≥0.99 at full load Back feed protection Overload capability: 150% for 1 minute (normal operation). 125% for 10 minutes (normal operation) Overall UPS efficiency: Greater than 99 % i.e. > 97 % at 50% load Output Voltage 380/400/415 (Minimum) VAC, 3 Phase. Voltage Regulation /Stability ±1% Output Power Factor: Unity Rated Frequency: 50 Hz +-0.1% free running Acoustic Noise (At 1 meter from UPS) at 100% load: Less than 75 dB Output Voltage distortion (THDv)(100% Load):Linear load: <1(%) Non-Linear load: <5(%) Max Input Short Circuit capacity : 65kA Networking Protocol – SNMP, Modbus TCP/IP Operating Temperature: 0 to 40 Deg C | ||||||
| 1.01Humidity 0 to <95% The UPS shall be provided with Phase Sequence Correction at Input i.e., Incase of Phase reversal at Input, UPS shall continue to operate in Double Conversion Mode of operation without going to battery mode. The UPS shall be provided with oscilloscope for measuring and recording input/output voltage & current waveforms in the event of any abnormal or alarming situation arises. In-case it is not available within the UPS, then two numbers of 3 Phase Power Meters (one at Input & one at Output) shall be provided along with the UPS system which can capture the Waveforms Triggered during the failure event. AC/DC capacitor service life shall be minimum 10 years. If less than 10 years capacitors replacement cost must be bourne by OEM/ authorised agency. UPS shall have built-in feature to test UPS at 100% Load without the need of any external Load Bank. In case this feature is not available within the UPS, Vendor shall provide an External Load Bank equal to UPS Capacity which will be kept at the site till the end of Warranty period. The bidder must submit savings on electricity cost for a span on 10 years for each UPS on Class I output mode of operations as per IEC 62040-3 along with UPS type test report from NABL accredited lab w.r.t IEC 62040-3. The UPS must have Inverter-on mode to deliver 99% efficiency along with Class-I output as per IEC 62040-3 Dust filter & Rodent Mesh shall be provided with each UPS Frame Built In Energy Meter shall be provided to display kWh consumption at input & output. Conformal Coating: Critical components like PCBs in UPS shall be conformal coated for protection against dust and other environmental harsh conditions. Ingress Protection – IP 21 (inbuilt) | ||||||
| 1.02 | Make :- APC/ EATON/ Schneider/ Vertiv/ Emerson/ Hitachi.
The UPS battery shall be sized for 30 minutes backup at 0.9 load pf
Battery Chemistry: SMF VRLA 100AH, 12 Volt - 48 Nos
Make:- Exide/ Quanta/ Amarraja/ Amaron.
Battery Warranty :02 years
Cycle life(@25℃,1C/1C,100%DOD) shall be ≥ 2500 Cycles
Each battery cabinet shall feature a DC rated circuit breaker for control and protection. The circuit breaker within the battery cabinet shall only provide protection to the battery string within that battery cabinet.
Battery rack (Customized as per site requirement), Battery interlinks, Battery to battery DC Cable, Battery MCCB, Battery terminal caps for extra safety shall be provided. | 3 | Each | 25,17,908.46 ₹75,53,725.38 Lowest | 31,80,753 ₹95,42,259 | 28,17,996.72 ₹84,53,990.16 |
| 2.00Design, Fabrication, Supplying, testing & commissioning of front operated cubicle type compartmentalised, front access free standing, dust and vermin proof (IP 44) Switch board panel of 1400 x 1050 x 400 mm size suitable for use at 415 volt, 3 phase, 4 wire, 50 hertz system suitable for fault level of required value symmetrical at 415 volts, made out of 2mm thick CRCA MS sheet with hinged, gasketed (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/ T/ Flat/ sections including 3 mm thick gland plates on top and bottom and lifting hooks and GI earth strip of required size with 2 nos. earthing terminal and powder coated paint finish of approved shade over metalsurface cleaned and treated with seven tank process complete with frame duly erection in ground and interconnection with copper conductor etc. as specification, as complete as required confirming to IS8623:93 as below.(Switchgear Make:- Schneider/ Seimens/ ABB/ L & T.) (Panel manufacturer: CPRI Approved) | ||||||
| 2.01 | i) 400 amp, 4P, 36KA, 50HZ, 415V, AC MCCB
with Thermal magnetic release -- 01 Nos.
ii) 160 amp, 4P, 25KA, 50HZ, 415V, AC MCCB
with Thermal magnetic release---03 Nos.
iii) Illuminated Lamp ---03 Nos.
iv) Earth Studs ---- 02 Nos.
v) Danger plate -----02 Nos.
vi) Spreder link-----04 Set.
vii) Rotary handle---- 04 Nos.
viii) 3 phase VAF Meter---01 Nos.
ix) 3 phase SPD type 1+2 ---01 Nos.
Bus bar : 400 amp TPN 415 Colour coded Copper Busbar. | 1 | Each | 2,18,536 ₹2,18,536 | 2,60,000 ₹2,60,000 | 2,04,820.71 ₹2,04,820.71 Lowest |
| 3.00Design, Fabrication, Supplying, testing & commissioning of front operated cubicle type compartmentalised, front access free standing, dust and vermin proof (IP 44) Switch board panel of 1800 x 1200 x 350 mm size suitable for use at 415 volt, 3 phase, 4 wire, 50 hertz system suitable for fault level of required value symmetrical at 415 volts, made out of 2mm thick CRCA MS sheet with hinged, gasketed (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/ T/ Flat/ sections including 3 mm thick gland plates on top and bottom and lifting hooks and GI earth strip of required size with 2 nos. earthing terminal and powder coated paint finish of approved shade over metalsurface cleaned and treated with seven tank process complete with frame duly erection in ground and interconnection with copper conductor etc. as specification, as complete as required confirming to IS8623:93 as below.( Switchgear Make:- Schneider/ Seimens/ ABB/ L & T.) (Panel manufacturer: CPRI Approved). | ||||||
| 3.01 | i) 400 amp, 4P, 36KA, 50HZ, 415V, AC MCCB with Thermal magnetic release -- 01 Nos.
ii) 63 amp, 4P, 10KA, 50HZ, 415V, AC MCB---12 Nos.
iii) 63 amp, 2P, 10KA, 50HZ, 230V, AC MCB---66 Nos.
iv) Illuminated Lamp ---03 Nos.
v) Earth Studs ---- 02 Nos.
vi) Danger plate -----02 Nos.
vii) 3 phase VAF Meter---01 Nos.
Bus bar : 400 amp TPN 415 Colour coded Copper Busbar. | 1 | Each | 3,15,532 ₹3,15,532 | 1,99,230 ₹1,99,230 Lowest | 3,62,223.13 ₹3,62,223.13 |
| 4.00 | Supplying, installation, testing & commisssioning of Inverted Automatic Fire extinguisher MAP 90 based with telescoping wall mounting bracket of 9 Kg capacity. PED approved, discharge mechanissam automatic QBD - 68 d Centigrade. | 6 | Each | 19,994.44 ₹1,19,966.64 | 10,000 ₹60,000 | 9,695.79 ₹58,174.74 Lowest |
| 5.00 | Supplying, installation, testing & commisssioning of 2 Kg, HFC-236 fa Clean agent micro flooding system with Zero Ozone Depletion Potential. Container along with valve assembly - LPCB certified to Standard LPS 1666:Issue 1.0 by LPCB for following type of enclosures : Enclosed, Open with Natural airflow & Open with Forced Airflow with 20 mtr HST tube with all accessories | 3 | Each | 1,55,732.22 ₹4,67,196.66 | 75,000 ₹2,25,000 | 70,004.39 ₹2,10,013.17 Lowest |
| 6.00Supplying, installing, testing and commissioning approved make Microprocessor based Multi-loop, Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 trouble events including 1000 alarm log history events, Self Programmable alphanumeric keypad for programming. The panel should be equipped with sufficient number of loops & each loop shall have a capacity of minimum 125 detectors & 125 other devices excluding 20% spare. The panel shall work in degrade mode in case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition with the charging capacity of 200AH. The panel shall be capable of self programing without any dependancy on dongle or programming software. Quoted rate shall include supply of necessary software & hardware for programming the panel with all necessary licence. Panel shall have Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Complied to meet UL864, 10th Edition and FM Approved. | ||||||
Tender Value
₹1.2 Cr
EMD Value
₹2.4 L
Closing Date
11 Jul 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (ED-I)
Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
Replacement of 3 x 60 kVA Modular live swappable UPS in CSC at IIT Delhi
2024_IIT_813872_1
IITD/WORKS (SP- 4683)/2024
Open Tender
Miscellaneous Works
Works
60 days
Indian Institute of Technology Delhi
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹2.4 L
12 Aug 2024
27 Jun 2024
12 Jul 2024
27 Jun 2024
11 Jul 2024
27 Jun 2024
Amount
Sub Head - I (under PLN fund) Supplying, installation, testing and commissioning of 3 x 60 kVA Modular live swappable UPS with (N+1) configuration and each power cabinet shall be consisting of multiple numbers of Live swappable power modules with following specifications. Location: CSC, IIT Delhi Transformer less, IGBT Rectifier & IGBT Inverter Modular Scalable Live Swappable UPS System UPS Modules must be of 30 KW Rating in each 60 KW power cabinet. Input Voltage 380/400/415(Minimum) VAC, three-phase Input Voltage Range 331 to 477 V Input Frequency and tolerance 40 to 70Hz Input Total Harmonics Distortion <1% at 100% load Input Power factor ≥0.99 at full load Back feed protection Overload capability: 150% for 1 minute (normal operation). 125% for 10 minutes (normal operation) Overall UPS efficiency: Greater than 99 % i.e. > 97 % at 50% load Output Voltage 380/400/415 (Minimum) VAC, 3 Phase. Voltage Regulation /Stability ±1% Output Power Factor: Unity Rated Frequency: 50 Hz +-0.1% free running Acoustic Noise (At 1 meter from UPS) at 100% load: Less than 75 dB Output Voltage distortion (THDv)(100% Load):Linear load: <1(%) Non-Linear load: <5(%) Max Input Short Circuit capacity : 65kA Networking Protocol – SNMP, Modbus TCP/IP Operating Temperature: 0 to 40 Deg C
Humidity 0 to <95% The UPS shall be provided with Phase Sequence Correction at Input i.e., Incase of Phase reversal at Input, UPS shall continue to operate in Double Conversion Mode of operation without going to battery mode. The UPS shall be provided with oscilloscope for measuring and recording input/output voltage & current waveforms in the event of any abnormal or alarming situation arises. In-case it is not available within the UPS, then two numbers of 3 Phase Power Meters (one at Input & one at Output) shall be provided along with the UPS system which can capture the Waveforms Triggered during the failure event. AC/DC capacitor service life shall be minimum 10 years. If less than 10 years capacitors replacement cost must be bourne by OEM/ authorised agency. UPS shall have built-in feature to test UPS at 100% Load without the need of any external Load Bank. In case this feature is not available within the UPS, Vendor shall provide an External Load Bank equal to UPS Capacity which will be kept at the site till the end of Warranty period. The bidder must submit savings on electricity cost for a span on 10 years for each UPS on Class I output mode of operations as per IEC 62040-3 along with UPS type test report from NABL accredited lab w.r.t IEC 62040-3. The UPS must have Inverter-on mode to deliver 99% efficiency along with Class-I output as per IEC 62040-3 Dust filter & Rodent Mesh shall be provided with each UPS Frame Built In Energy Meter shall be provided to display kWh consumption at input & output. Conformal Coating: Critical components like PCBs in UPS shall be conformal coated for protection against dust and other environmental harsh conditions. Ingress Protection – IP 21 (inbuilt)
Make :- APC/ EATON/ Schneider/ Vertiv/ Emerson/ Hitachi. The UPS battery shall be sized for 30 minutes backup at 0.9 load pf Battery Chemistry: SMF VRLA 100AH, 12 Volt - 48 Nos Make:- Exide/ Quanta/ Amarraja/ Amaron. Battery Warranty :02 years Cycle life(@25℃,1C/1C,100%DOD) shall be ≥ 2500 Cycles Each battery cabinet shall feature a DC rated circuit breaker for control and protection. The circuit breaker within the battery cabinet shall only provide protection to the battery string within that battery cabinet. Battery rack (Customized as per site requirement), Battery interlinks, Battery to battery DC Cable, Battery MCCB, Battery terminal caps for extra safety shall be provided.
Design, Fabrication, Supplying, testing & commissioning of front operated cubicle type compartmentalised, front access free standing, dust and vermin proof (IP 44) Switch board panel of 1400 x 1050 x 400 mm size suitable for use at 415 volt, 3 phase, 4 wire, 50 hertz system suitable for fault level of required value symmetrical at 415 volts, made out of 2mm thick CRCA MS sheet with hinged, gasketed (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/ T/ Flat/ sections including 3 mm thick gland plates on top and bottom and lifting hooks and GI earth strip of required size with 2 nos. earthing terminal and powder coated paint finish of approved shade over metalsurface cleaned and treated with seven tank process complete with frame duly erection in ground and interconnection with copper conductor etc. as specification, as complete as required confirming to IS8623:93 as below.(Switchgear Make:- Schneider/ Seimens/ ABB/ L & T.) (Panel manufacturer: CPRI Approved)
i) 400 amp, 4P, 36KA, 50HZ, 415V, AC MCCB with Thermal magnetic release -- 01 Nos. ii) 160 amp, 4P, 25KA, 50HZ, 415V, AC MCCB with Thermal magnetic release---03 Nos. iii) Illuminated Lamp ---03 Nos. iv) Earth Studs ---- 02 Nos. v) Danger plate -----02 Nos. vi) Spreder link-----04 Set. vii) Rotary handle---- 04 Nos. viii) 3 phase VAF Meter---01 Nos. ix) 3 phase SPD type 1+2 ---01 Nos. Bus bar : 400 amp TPN 415 Colour coded Copper Busbar.
Design, Fabrication, Supplying, testing & commissioning of front operated cubicle type compartmentalised, front access free standing, dust and vermin proof (IP 44) Switch board panel of 1800 x 1200 x 350 mm size suitable for use at 415 volt, 3 phase, 4 wire, 50 hertz system suitable for fault level of required value symmetrical at 415 volts, made out of 2mm thick CRCA MS sheet with hinged, gasketed (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/ T/ Flat/ sections including 3 mm thick gland plates on top and bottom and lifting hooks and GI earth strip of required size with 2 nos. earthing terminal and powder coated paint finish of approved shade over metalsurface cleaned and treated with seven tank process complete with frame duly erection in ground and interconnection with copper conductor etc. as specification, as complete as required confirming to IS8623:93 as below.( Switchgear Make:- Schneider/ Seimens/ ABB/ L & T.) (Panel manufacturer: CPRI Approved).
i) 400 amp, 4P, 36KA, 50HZ, 415V, AC MCCB with Thermal magnetic release -- 01 Nos. ii) 63 amp, 4P, 10KA, 50HZ, 415V, AC MCB---12 Nos. iii) 63 amp, 2P, 10KA, 50HZ, 230V, AC MCB---66 Nos. iv) Illuminated Lamp ---03 Nos. v) Earth Studs ---- 02 Nos. vi) Danger plate -----02 Nos. vii) 3 phase VAF Meter---01 Nos. Bus bar : 400 amp TPN 415 Colour coded Copper Busbar.
Supplying, installation, testing & commisssioning of Inverted Automatic Fire extinguisher MAP 90 based with telescoping wall mounting bracket of 9 Kg capacity. PED approved, discharge mechanissam automatic QBD - 68 d Centigrade.
Supplying, installation, testing & commisssioning of 2 Kg, HFC-236 fa Clean agent micro flooding system with Zero Ozone Depletion Potential. Container along with valve assembly - LPCB certified to Standard LPS 1666:Issue 1.0 by LPCB for following type of enclosures : Enclosed, Open with Natural airflow & Open with Forced Airflow with 20 mtr HST tube with all accessories
Supplying, installing, testing and commissioning approved make Microprocessor based Multi-loop, Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 trouble events including 1000 alarm log history events, Self Programmable alphanumeric keypad for programming. The panel should be equipped with sufficient number of loops & each loop shall have a capacity of minimum 125 detectors & 125 other devices excluding 20% spare. The panel shall work in degrade mode in case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition with the charging capacity of 200AH. The panel shall be capable of self programing without any dependancy on dongle or programming software. Quoted rate shall include supply of necessary software & hardware for programming the panel with all necessary licence. Panel shall have Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Complied to meet UL864, 10th Edition and FM Approved.
Two Loop Panel
Supplying, installation, testing & commisssioning of intelligent addressable multi criteria (Smoke + Heat + CO + IR) detector including suitable photo detector complete with base as required. (Acceptable Make:- Johnson Control (IFC)/ Notifier (UL) / Bosch (UL) / Mircom (UL) / Fike (UL).
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. (Acceptable Make:- Johnson Control (IFC)/ Notifier (UL) / Bosch (UL) / Mircom (UL) / Fike (UL).
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.(Acceptable Make:- Johnson Control (IFC)/ Notifier (UL) / Bosch (UL) / Mircom (UL) / Fike (UL).
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and laying of Solid stranded Copper Conductor, XLPE Insulated, Cores Laid Up, PVC Innersheathed, Unarmoured 1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments. on wall surface as required.Upto 35 sq. mm (clamped with 1 mm thick saddle)[conforming to I.S-1554/1/8]. (Make- Havells/ Gloster/ Polycab/ RR kabel/ KEI/ Universal).
1 x 35 sq mm
Supplying, installing, testing and commissioning Real-time monitoring of various critical parameters such as grid earth resistance, earth to neutral voltage, earth integrity and earth leakage current which are of paramount importance to maintain healthy electrical environment in different type of earthed installations viz. TN-S, TN-C-S, TT, TN-C, and IT.( If required system should share data on web and mobile application, wired and wireless conectivity showing real time data & history with diagnosis report with alarming function) (Acceptable Make :- DEHN or equilvalent)
Dismantling and removal of existing UPS panel along with all accessories from the location including removal of cabling, stand, with other wires and accessories etc. complete as directed by the Engineer-in-charge. [Locations:- CSC, IIT Delhi]
Dismantling and removal of existing UPS along with batteries from the location including removal of cabling, stand, control panel with other wires and accessories etc. complete as directed by the Engineer-in-charge. [Locations:- CSC, IIT Delhi]
(-) Less credit for dismantled UPS panel along with its all accessories etc. (Reserve price is Rs.50,000/- for each lifts. Bidder can’t quote below the reserve price set)
(-) Less credit for dismantled UPS along with its all accessories liike batteries etc. (Reserve price is Rs.1,50,000/- for each lifts. Bidder can’t quote below the reserve price set)
Sub Head - II (AMC) [Under NPN fund] Comprehensive maintenance of 3X60 kVA UPS which include routine, preventive and breakdown maintenance for period of five years including repair / replacement of worn out items with minimum downtime and warranty & guarantee of repaired / replaced items after completion of one year guarantee period.[Locations:- CSC, IIT Delhi]
1st Year (Free of cost, being Defect Liability Period)
2nd Year
3rd Year
4th Year
5th Year
6th Year
Nikom Infrasolutions Pvt. Ltd.
BBN ENERGY SYSTEMS PVT LTD
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.82 MB
BOQ_855306.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .