| 1 | L1₹4.6 LAccepted-AOC 225 4 DR A K PAUL ROAD KOLKATA 700034 | KOLKATA | KOLKATA | WEST BENGAL | 700034 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹4.7 L+₹9,950 (2.15%)Rejected-Finance 2 BOSE PARA ROAD BARISHA KOLKATA WEST BENGAL 700008 | KOLKATA | WEST BENGAL | 700008 | L2 | Rejected-Finance Higher Bidder | |
| 3 | L3₹4.8 L+₹15,500 (3.35%)Rejected-Finance | L3 | Rejected-Finance Higher Bidder |
| Sl No | Description | Qty | Unit | P.S.Enterprise L1 | Rajalakshmi Enterprise L2 | Master Electric L3 |
|---|---|---|---|---|---|---|
| 1.00 | SITC of 10 KVA online UPS, 3 Phase input and 3 Phase Output
a)Topology:- IGBT Based DSP Controlled
b)Ratting (KVA/KW):- 10 KVA/9 KW battery bank of 10080 VAH(SMF Battery) 12 V, 3 phase/3 phase output.
c)Input Voltage:-310--400--415 VAC, VolatgeRange:- 320-480 VAC
d)Frequency:- 50 Hz
e)Input PF:- 0.99 with IGBT rectifier
f)Isolation Transformer:- Inbuild Isolation Transformer should be provided at the Input of the UPS. No external, step up Transformer will be accepted.
g) Back feed Protection:-Ups should have back feed protection.
h) DC Ripple:- Residual Ripple voltageshould be < 1%
i)Charging:- Automatic Boots cum float charging capability with settable float and boots charging voltage and current level and boots charger timer.
j)Input Current Distortion:-THDi <=3%
k)Output Voltage:- 380--400--415
l)Output Volage Regulation:- Static Variation ± 1%, dyanamic variation ± 3%.
m)Output Frequency:- 50 Hz (± 0.1%)
n) Output Power Factor:- 0.9
o) Crest Factor:- 3: 1 | 1 | item | 4,62,500 ₹4,62,500 Lowest | 4,72,450 ₹4,72,450 | 4,78,000 ₹4,78,000 |
| 1.01a)THDi < 1% (linear load), < 5% (non linear load) b)Waveform:- Pure Sine Wave c)Bridge:-Microprocessor based and IGBT Technology d)Overload:- 110 % for 10 minutes, 133% for 1 minute, 150 % for 5 Sec, 103% continuous e)Static By Pass:- 100 % rated static switches with fuse protection f)Over load on Bypass:- 100 % g) Overall Efficiency:- Up to95 % ( 90% Efficiency on 100% load) h)Battery Cabinet:-With power coated MS Angle with MS sheet suitable dimension and gage, well air ventilation to ensure the battery optimum life cycle. Using Nyvin cable with proper ratting for interlinks cables and battery input and necessary accessories. i) DC Bus:- Minimum 480 V or above, 30 minuted required (minimum 10080 VAH) Battery. j) Battery make:- Excide/ Amaron k)Protection:- Input & Output Over/ Under Voltage, Single Phasing DC - High/ UnderVoltage, Battery Charging Over Current, Output Over load / ShortCircuit /OverTemp. UPS ON on Mains recovery, Audio Alarm, Mains Fail, Battery low Pre-alarm, Inverter Trip (l) Metering:- Graphical LCD display for Input & Output - Voltage, Current &Frequency, Battery- Voltage & Current | ||||||
| 1.02a)Indications:- Mains- On/Fall/High/Low/ Single Phasing DC- On/ High,Battery- LowPre-alarm/ Low Tip Inverter- On/ Trip/High/Low /OverCurrent b)Switchgear:-MCB/MCCB for Input, Battery, Output & Manual Bypass Switch Termination: Input, Battery, Output & Bypass c)Enclosure:- IP 21 d)Operating Temperature:- 0 to 50 Deg C e)Humidity:- Up to 95 % Rh ( non- Condensing) f)Colling:- Forced Air g)Noise:- < 55dB h)Cold Start : Provided i)Communication: RS 232, RS 485 j)Monitoring Software:-UPS Monitoring Software on Windows XP Platform k)Certification: ISO 9001: 2015, ISO 14001:2004, ISO18001 and OHSAS l)CE Marking: IEC/EN 62040-1-1 IEC/EN 62040-2 (EMC Emission), IEC/EN 62040-3 performance &Design, IEC/EN 50091-1, IEC/EN 60950(Safety), IEC/EN 50091-2,IEC/EN 61000-4 ( EMC Immunity,IEC/EN 60146(Design & Manufacture) Warrnty 3 Years incl battery. (Make :- Numeric - Legrand/ Emerson/ APC/ Power one.) | ||||||
Tender Value
Refer Docs
EMD Value
₹9,280
Closing Date
9 Mar 2024, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Paschim Med. Elecl. Div. PWDte.
Office of the Executive Engineer, Paschim Medinipur Electrical Division, P.W.Dte., Midnapore, Paschim Medinipur.
Construction of Proposed (G plus 2) storied 60 Bedded ward bedded at Garhbeta Rural Hospital, Paschim Medinipur. -- SITC of UPS.
2024_WBPWD_670624_1
WBPWD/EE/PMED/NIQ-31/e-Q /2023-2024
Open Tender
ELECTRICAL WORKS ORG
Item Rate
14 days
Garbeta, Paschim Medinipur.
Please refer Tender documents.
3 documents required · 3 mandatory
₹9,280
Yes
Off. of the EE, Pas. Mid. Elec. Divn. PWDte.
30 Oct 2026
20 Feb 2024
11 Mar 2024
20 Feb 2024
9 Mar 2024
28 Feb 2024
27 Feb 2024
Amount
SITC of 10 KVA online UPS, 3 Phase input and 3 Phase Output a)Topology:- IGBT Based DSP Controlled b)Ratting (KVA/KW):- 10 KVA/9 KW battery bank of 10080 VAH(SMF Battery) 12 V, 3 phase/3 phase output. c)Input Voltage:-310--400--415 VAC, VolatgeRange:- 320-480 VAC d)Frequency:- 50 Hz e)Input PF:- 0.99 with IGBT rectifier f)Isolation Transformer:- Inbuild Isolation Transformer should be provided at the Input of the UPS. No external, step up Transformer will be accepted. g) Back feed Protection:-Ups should have back feed protection. h) DC Ripple:- Residual Ripple voltageshould be < 1% i)Charging:- Automatic Boots cum float charging capability with settable float and boots charging voltage and current level and boots charger timer. j)Input Current Distortion:-THDi <=3% k)Output Voltage:- 380--400--415 l)Output Volage Regulation:- Static Variation ± 1%, dyanamic variation ± 3%. m)Output Frequency:- 50 Hz (± 0.1%) n) Output Power Factor:- 0.9 o) Crest Factor:- 3: 1
a)THDi < 1% (linear load), < 5% (non linear load) b)Waveform:- Pure Sine Wave c)Bridge:-Microprocessor based and IGBT Technology d)Overload:- 110 % for 10 minutes, 133% for 1 minute, 150 % for 5 Sec, 103% continuous e)Static By Pass:- 100 % rated static switches with fuse protection f)Over load on Bypass:- 100 % g) Overall Efficiency:- Up to95 % ( 90% Efficiency on 100% load) h)Battery Cabinet:-With power coated MS Angle with MS sheet suitable dimension and gage, well air ventilation to ensure the battery optimum life cycle. Using Nyvin cable with proper ratting for interlinks cables and battery input and necessary accessories. i) DC Bus:- Minimum 480 V or above, 30 minuted required (minimum 10080 VAH) Battery. j) Battery make:- Excide/ Amaron k)Protection:- Input & Output Over/ Under Voltage, Single Phasing DC - High/ UnderVoltage, Battery Charging Over Current, Output Over load / ShortCircuit /OverTemp. UPS ON on Mains recovery, Audio Alarm, Mains Fail, Battery low Pre-alarm, Inverter Trip (l) Metering:- Graphical LCD display for Input & Output - Voltage, Current &Frequency, Battery- Voltage & Current
a)Indications:- Mains- On/Fall/High/Low/ Single Phasing DC- On/ High,Battery- LowPre-alarm/ Low Tip Inverter- On/ Trip/High/Low /OverCurrent b)Switchgear:-MCB/MCCB for Input, Battery, Output & Manual Bypass Switch Termination: Input, Battery, Output & Bypass c)Enclosure:- IP 21 d)Operating Temperature:- 0 to 50 Deg C e)Humidity:- Up to 95 % Rh ( non- Condensing) f)Colling:- Forced Air g)Noise:- < 55dB h)Cold Start : Provided i)Communication: RS 232, RS 485 j)Monitoring Software:-UPS Monitoring Software on Windows XP Platform k)Certification: ISO 9001: 2015, ISO 14001:2004, ISO18001 and OHSAS l)CE Marking: IEC/EN 62040-1-1 IEC/EN 62040-2 (EMC Emission), IEC/EN 62040-3 performance &Design, IEC/EN 50091-1, IEC/EN 60950(Safety), IEC/EN 50091-2,IEC/EN 61000-4 ( EMC Immunity,IEC/EN 60146(Design & Manufacture) Warrnty 3 Years incl battery. (Make :- Numeric - Legrand/ Emerson/ APC/ Power one.)
Rajalakshmi Enterprise
Master Electric
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .