Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.5 LAccepted-AOC | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹32.2 L+₹6.2 L (23.7%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹33.5 L+₹7.4 L (28.6%)Rejected-Finance | L3 | Rejected-Finance Being L3 |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
9 Nov 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Mhow
HQ CWE Mhow Cantt Mhow 453441
REPAIR MAINT OF HT DISTRIBUTION SYSTEM AND OTHER ALLIED WORKS UNDER GE MCTE MHOW
2020_MES_379115_1
CA No CWE/Mhow/14(T) OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HQ CWE Mhow
Please refer tender documents
9 documents required · 9 mandatory
₹500
Yes
GE MCTE Mhow
₹70,000
Yes
5 Jan 2021
19 Sept 2020
11 Nov 2020
19 Sept 2020
9 Nov 2020
7 Oct 2020
60 days
Amount
Excavation in trenches in hard/dense soil, n. exc. 1.5m wide and n. exc. 1.5m deep and getting out for laying of cables/pipes etc including forming bottom surfaces to the required level/slope complete all as specified and directed.
Returning filling in, including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick in any type of soil complete all as specified and directed.
Removal of surplus excavated soil to a distance n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above starting point complete all as specified and directed.
Material and labour for approved river sand cushioning for under ground cable in trenches 8 cm before laying and 15 cm after laying of cable and punned thickness of sand shall be measured and paid for 18 cm only after punned/consolidated thickness complete all as specified and directed.
Supply laying reinforced precast concrete cable cover, class HV , type-1, flate, size 300mm x 180mm x 40mm all as specified and directed. (Make: Mahtab tiles / Alankar Tiles/Pearlers Industries/SIND Mozaic Gujrat/JJ Concrete Lucknow).
Supply and fix cable jointing kit for 11 KV grade (E) cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm all as directed. ( Make : 3 M/Denson/M seal)
Ditto all as per item No 06 above but for cable 120 sqmm.
Supply and fix cable jointing kit for 11 KV grade (E) cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 sq mm all as directed.
Ditto all as per item No 08 above but for cable 120 sqmm.
Supply and fixing cable jointing kit for 11 KV (E) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor all as directed.
Ditto all as per item No 10 above but for cable 120 sqmm.
Taking down carefully old rusted / damaged switch air break, gang operated any type and size complete all as specified and directed.
Supply,installing, connecting and commissioning switch air break gang operated triple pole for current rating 200 Amp at 11 KV, out door type , mechanically operated, mounted on insulators with 9 insulator and steel frame, with operating mechanism and operating rod of 25mm bore GI pipe medium grade from ground level, with locking arrangements, complete all as specified. (Make : Pactil, Alstom, Jaipuria brothers, BHEL)
Supply and install HT 33KV outdoor type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 insulator and with earth switch upto 200/400 Amps, with suitable GI pipe pipe medium grade required for operation, all as specified and directed. (Make : Jaipuria Brothers / Pactil/ Elpro).
Supply, laying in trenches/through pipes under road, floor/ on wall/on pole or any other indicated place & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored earth, electric power cables (heavy duty)with stranded aluminum conductor, 11000 volts grade, of size 3 core 70 sqmm complete, including taking down existing cable, all as specified and directed.
Ditto all as per item No 15 above but cable 95 sqmm.
Ditto all as per item No 15 above but cable 120 sqmm.
Sppply & Laying XLPE insulated, armoured, electric copper cable of size 2.5 sqmm 4 core with solid copper conductor, 1100 volts grade, laid in trenches, fixed on poles / walls or passing through pipes including provision of necessary lugs and glands & making necessary connection complete all as specified and directed.
Sppply & Laying PVC insulated, unarmoured, electric copper cable of size 25 sqmm 1 core with multi stranded copper conductor, 1100 volts grade, laid in trenches, fixed on poles / walls or passing through pipes & making necessary connection complete all as specified and directed.
Sppply & Laying PVC insulated, unarmoured, electric copper cable of size 10 sqmm 1 core with multi stranded copper conductor, 1100 volts grade, laid in trenches, fixed on poles / walls or passing through pipes & making necessary connection complete all as specified and directed.
Dehydration of HV/EHV grade transformer oil minimum three cycles to achieve di electric strength not less than 40 KV for 1 minute with 2.5mm Gap as per IS - 335 - 1983 for EHV grade including topping up with new transformer oil all as directed. Note :- (i) Centrifuging Machine with all T&P & testing machine of oil, required for dehydration shall be arranged by contractor. (ii) Oil required for topping up the transformer will be measured & paid separately
Supply and filling (topping up) of transformer oil EHV as per IS 335 of 1983 Part II after dehydration & testing complete all as specified and directed.
Material and labour for disconnecting electrical connections of transformer of 11 KV / 433 V of any make & any type, capacity upto 100 KVA loading the transformer on heavy vehicle (open chassis) type from existing platform/four pole structure, by heavy crane long boom type suitable for shifting and loading transformer and transporting of transformer for repair at civil workshop at Indore city from MCTE area Mhow including unloading of transformer from vehicle at workshop & opening up transformer by unscrewing all nuts/bolts and washers of top cover duly draining out complete transformer oil and kept aside for re-use. Disconnecting of all HT/LT wiring tap changer, complete LT/HT bushing, air breather etc and kept aside for re-use the serviceable parts and removal of unserviceable parts and taking out complete core assembly of transformer with help of chain pully to carry out the following works:-
Deslurring of transformer tank by taking out the complete deposited transformer oil sludge and cleaning thoroughly the transformer tank by washing & wiping out all dirt/rust accomolated including making preparation of old painted internal/external surfaces of transformer. Painting the internal surfaces of transformer with two coats of high grade anticorrosive varnishing paint over a coat of red oxide primer. Painting to external surfaces of transformer with two coats of Ist grade synthetic enamelled paint over a coat of red oxde primer, all as shown and directed by Engr-in-charge.
Cleaning the transformer core assembly using electric blower and making the core free from sludge, dirt and any other foreign materials from its surfaces including provision of high grade insulation varnish and raising insulation of the core through heat chamber and raising of IR valve /LV-E > 500 Mega ohms HV-E >1000 Mega ohms
Assembling the transformer complete including supply of complete set including replacement of defective assecessoris such as oil seal , gasket , LT/HT bushing, stud, air breather, tap changer, including making necessary LT/HT wiring as dismantled( New spares as required will be measured & paid separately under relevant items, rate of oil seal & gasket will be deemed included in the quoted rate ). Powering of dehydration/filtered transformer oil (dehydration charges will be measured and paid separately) as obtained during dismantling and top up balance quantum with new transformer oil as required (New transformer oil will be measured & paid under relevant item) after sucessfully repairing the transformer re-loding the same & place to its original location and installation complete including making LT/HT side cable connection, earth connection and testing complete .
Ditto all as per item No 23 above but for transformer of 11 KV/433 Volt capacity upto 250 KVA, of any make & any type all as specified and directed.
Ditto all as per item No 23 above but for transformer of 11 KV/433 Volt capacity from 300 to 630 KVA of any make & any type all as specified and directed.
M & L in replacement of worn out winding made out of paper covered super enamelled copper wire as per existing guage/size all as specified and directed.
M & L in replacement of worn out winding made out of tripple paper covered solid copper wire as per existing guage/size all as specified and directed.
Supply & fixing HV bushing with brass metal connecting rod, nut, bolt and washer suitable for transformer upto 630 KVA 12 KV as per IS 3347/1967 in replacement of worn out stud complete all as specified and directed.
Supply & fixing LV bushing of transformer with brass metal connecting rod, nut, bolt and washer,suitable for 63 KVA to 100 KVA capacity of tranaformer 1100 Volt as per IS 3347/1967 complete all as specified and directed.
Supply & fixing LV bushing of transformer with brass metal connecting rod, nut, bolt and washer,suitable for 200 KVA to 315 KVA capacity of tranaformer 1100 Volt as per IS 3347/1967 complete all as specified and directed.
Supply & fixing LV bushing of transformer with brass metal connecting rod, nut, bolt and washer,suitable for 400 KVA to 750 KVA capacity of tranaformer 1100 Volt as per IS 3347/1967 complete all as specified and directed.
Supply & replacement of silica gel crystal complete in all type of capacity of transformer complete all as specified and directed.
Supply and fixing in replacement of Silica gel breather assembly complete with silica gel crystal complete for the capcity of transformer 50 KVA to 250 KVA complete all as specified and directed.
Supply and fixing in replacement of Silica gel breather assembly complete with silica gel crystal complete for the capcity of transformer 300 KVA to 400 KVA complete all as specified and directed.
Supply and fixing in replacement of Silica gel breather assembly complete with silica gel crystal complete for the capcity of transformer 500 KVA to 750 KVA complete all as specified and directed.
Supply and fix in replacement DO fuse unit 3 pole 11 KV, upto 200 Amp channel mounted complete all as specified and directed.
Supply and fix in replacement DO fuse unit 3 pole 33 KV, upto 400 Amp channel mounted complete all as specified and directed.
Supply and fix in replacement of DO fuse element 5 Amp complete all as specified and directed.
Supply and fix in replacement of DO fuse element 15 Amp complete all as specified and directed.
Supply and fix in replacement of DO fuse element 25 Amp complete all as specified and directed.
Supply and fix in replacement of DO fuse element 35 Amp complete all as specified and directed.
Supply and fix in replacement of DO fuse element 40 Amp complete all as specified and directed.
Supply and fix in replacement of AB switch handle for 11 KV line complete all as specified and directed.
Supply and fix in replacement of AB switch female contact for 11 KV complete all as specified and directed.
Supply and fix in replacement of AB switch male contact for 11 KV complete all as specified and directed.
Supply and fix in replacement of AB switch pipe for 11 KV complete all as specified and directed.
Supply and fix in replacement of AB switch square bar for 11 KV complete all as specified and directed.
Supply and fix in replacement of Rubber mat of size 1M x 2M, 10 mm thick complete all as specified and directed.
Supply & fixing in replacement lightning arrestor suitable for 11 KV grade, thyrester type, complete with all fitting transmission class for outdoor discharge capacity 65 KA complete. (Make :- Elpro/Alstam/Bhel/Pragati/Raychem).
Supply & fixing in replacement lightning arrestor suitable for 33 KV grade, thyrester type, complete with all fitting transmission class for outdoor discharge capacity 65 KA complete. (Make :- Elpro/Alstam/Bhel/Pragati/Raychem).
Supply and fix in replacement disc type insulator, porcelain, vitreous, white brown or green, 145mm high, and 255mm dia ball and socket type single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts grade complete all as directed. (Make : Jaipuria/Bhel/Pactil/Southern Insulators/NGEF).
Supply and fixing in replacement 150 mm high and 150 mm dia pin type porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, suitable for working pressure 11000 Volts grade complete all as directed. (Make : Jaipuria/Bhel/Pactil/Southern Insulators/NGEF).
Supply and spreading graded stone aggregate of size 40 mm for transformer yard complete all as directed by Engineer - in - Charge.
Dismantling and taking out damaged/rusted cross arms, MS channel or angle section etc complete and setting aside for reuse within 50 mtrs .
M&L for cross arms, bracings, supports, clamps and back plates from existing poles and structures and material and labour for cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, complete all as directed.
Fixing only cross arms of any type & size obtained from item No.54 here-in-above.
Material and labour for danger notice plate for HT of size 25cm x 20cm x 1.5mm thick mild steel sheet, synthetic enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts complete all as specified.
Material and labour for painting of 11 m steel pole with cross arms, clamp of any length and shape for HT overhead line with two coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 15 cm dia yellow circle & marking three black & two yellow bands width 30 cm by fluorescent paint, from bottom of pole to 1.5 mtr height, complete all as directed.
Labour charges for servicing/overhauling/repairing & testing of all protection relays , CTs,PTs and 33KV VCB breaker 1250 A out door type, including all circuit control wiring complete all as follows :-
(a) CTs primary current injection test . (CT Testing) (b) Ratio test of PTs (c) Protection relays testing through secondary current injection kit (Relay testing) (d) Voltmeter,ammeter functional tesing (e) Breaker tesing for tripping time, closing time , contact resistance , IR values and physically healthyness of Vaccum interuptor.
Ditto all as per item No 59 and 59.01 above but 11KV 630/800 A (Make : CG) indoor VCB panels all as specified and directed.
Taking out defective/wornout parts from 33 KV VCB at the time of overhauling and S&F new, in replacement (if required) for the following all as specified and directed.
Closing coil
Tripping Coil.
Axullary switch
Spring charging motor assy
PT Fuse
Motor cutoff switch
Breaker control switch
Taking out defective/wornout parts from 11 KV VCB at the time of overhauling and S&F new, in replacement (if required) for the following all as specified and directed.
Closing coil
Tripping coil
PT Fuse Unit
Motor cutoff switch
Breaker control switch
Roller
Cutting & trimming tree branches along HT/LT over head lines after arranging shut down and by taking all precautions while working on lines, clearing of area, cleaning around sub stations, etc by employing sufficient labourers, T&P and safety measures required for the purpose complete for one span of any length and type all as directed by Engineer-in-Charge. Note :-The unit rate will include disposing off debris to nearest waste disposing point of concerned area.
Painting of transformer of capacity upto 250 KVA, 11/.433 KV with two coats synthetic enamelled spray painting after preparation of transformer surface complete all as specified and directed.
Ditto All as per item No 64 above but capacity 300 to 630 KVA 11/0.433 V.
Taking down defective indication lamps and replace with new LED pilot lamps complete .
Supply and errecting LT Panel outdoor type mounted and fixed with PCC foundation, made out of MS sheet factory assembled & factory fabricated out of 3.15 mm thick sheet steel with suitable size MS angel frame duly spray painted with two coats of gray synthetic enamel paint over one coat of re oxide zinc chrome primer after preparatiion of surface, with required civil works & with and including 4 No aluminium bus bars 600 Amps with suitable size porcelain insulators & wiring with copper cable of suitable size, connecting inclduing indicating lamp LED type for each phase, incl in built industiral type locking arrangement, front operated and back openable incl necessry arrengment for fixing with suitable clamps nut bolts etc. The panel pre wired with PVC insulated copper conductor danger notice board, feeders marked, and testing & commissioning, complete consisting of the following :-
Supply, installation¸ testing & commissioning of waterless and maintenance free earthing with earth (grounding) electrodes and PCC pit with cover. (a) Earth Electrode: 17.2 mm dia copper bonded MS rod shall be in-situ cast in electrically conductive concrete earth enhancing material mixed with cement. Size of embedding of electrically conductive concrete earth enhancing material shall be 85 mm dia. The electrode of 3000mm should be able to withstand a fault current upto 35kA (Peak) for 1 second duly tested from recognized National Test laboratories like CPRI, ERDA, ERTL, MSME etc (not more than 18 months old). The ratio of mixing of conductive concrete to cement should be 3:1. Other hardware like nut, bolts and washers should be of stainless steel.
M&L for earthing complete with steel earth plate eletrode 60cm x 60cm x6mm thick buried dirctly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plat not less than 1.5 mtr below ground level connected to GI strip 32 x 6mm by means of bolts. nuts,check nuts and washers etc including protection pipe 15mm dia up to 7.5m length , provision the earth lead to earth connection in ther main distribution box with lugs and GI nuts,bolts, earthing shall be done all as per shown electrical plate No 3 of SSR part 1 Including neccessary excavation in disintergratedand hard soil and 20mm dia GI pipe with funel for watering PCC earth chamber 100mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing in presence of Engr -in -Charge.
S&F MCCB, TPN, fixed type, thermonagnetic release, 415 Volts, including taking out old unserviceable MCCB of any type and make complete of following sizes :- Make : C&S/Havells/Indo Asian/L&T/Legrand
100 Amps 26 kA
160 Amps 26 kA
200 Amps 26 kA
250 Amps 26 kA
300 Amps 37 kA
350 Amps 37 kA
400 Amps 37 kA
S&F in replacement of copper lugs including testing complete of following sizes :-
M&L for chain link fencing and steel sections post with two coats aluminum paint over a coat of red-oxide complete including preparation of old steel or iron surfaces all as specfied and directed.
M&L for painting to old chain link fencing and steel sections post with two coats aluminum paint over a coat of aluminium red-oxide complete including preparation of old steel or iron surfaces all as specfied and directed.
Supply & fix in replacement of Avana meter make 3 OC + 1 EF relay fixed type at 33 KV control panel all as directed.
Auto Traders
Oasis Infosystem Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .