Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.8 CrAccepted-Finance | ₹2.8 Cr | 1 | Accepted-Finance Package Cost Quoted Lowest |
| 2 | 2₹3.2 Cr+₹32.4 L (11.4%)Accepted-Finance | ₹3.2 Cr+₹32.4 L (11.4%) | 2 | Accepted-Finance Package Cost Quoted 2nd Lowest |
| 3 | 3₹3.3 Cr+₹40.4 L (14.2%)Accepted-Finance | ₹3.3 Cr+₹40.4 L (14.2%) | 3 | Accepted-Finance Package Cost Quoted 3rd Lowest |
Tender Value
₹3.4 Cr
EMD Value
₹6.8 L
Closing Date
16 Aug 2022, 4:00 pmClosed
Execurive Engineer Project Div Srinagar left
Execurive Engineer Project Div Srinagar left Peer Bagh near Shalimar Bakery Srinagar
SUBTRANSMISSION WORK (33/11KV) LEVEL UNDER CAPEX AT BUDSHAH NAGAR IN SRINAGAR CITY.
2022_PDD_178563_1
PD/SL/01 of 2022-23
Open Tender
Electrical Works
Turn-key
180 days
Budshah Nagar Srinagar
As per SBD
5 documents required · 5 mandatory
₹5,000
Yes
Accounts officer Projects KPDCL
₹6.8 L
Yes
31 Aug 2022
9 Jul 2022
18 Aug 2022
12 Jul 2022
16 Aug 2022
19 Jul 2022
15 Jul 2022 - 18 Jul 2022
Amount
Supply at site of 33/11kV, 10 MVA ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connectors.
Supply at Site of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for 33/11KV Power Transformer Protection (SCADA Compatible)
Supply at Site of 33 kV C&R Panel along with O/C, E/F (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for Feeder Protection (SCADA Compatible)
Supply, of 33 kV Current Transformer (33 kV, 1Φ, 400-200/5-5-1 A, Outdoor) (1 No. per Φ)
Supply at site of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer/porcelain) gap less
Supply at site of 33 kV, 1250 A, Isolator with Earthing Blade
Supply at site of 33 kV, 1250 A, Isolator without Earthing Blade
Supply at site of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Supply at site of 33 kV DO Fuse, 100 Amp.
Supply at site of T Clamps for Panther Conductor
Supply at site of Single Tension Fittings for Panther Conductor
Supply at site of A.C Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories (for new receiving substation)
Supply at site of DC Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories (for new receiving substation)
Supply at site of Galvanised Steel Structures Duly fabricated as per approved drawings (for 33 KV Transformer Bay, line bay, feeder gantry etc)
Supply at site of GI flat for earthing 50x6 mm (for earthing risers at receiving substations)
Supply at site of Yard Lighting at new Receiving Station using 4 No 12 Mtr Long GI High Mast Poles,Continuosly tapered of Octagonal of cross Section including suitable shallow raft foundation using 8 Nos non integeral flood Light Luminaire with single piece die cast Al.housing and pot optic reflector and toughened glass cover conforming to IP-66 complete with all accessories bearing Cat No SGP 438 1XODM-TT 250Watt GLA/HPL-T 250W Philips Make and Suitable Control Feeder Panel.
Supply at site of Earth Wire 7/4.00 mm sq.
Supply at site of 11 kv Isolator Double break 3 pole ,600A Horizontal mount type with earth switch
Supply at site of Fire Fighting Equipment a) Dry Chemical Powder type (6Kg) for control room:-3No. b) Co₂ Type of 4.5 kg capacity for control room:-4No c) Co₂ type trolly mounted of 22.5Kg capacity for switch yard:-2No (at new receiving substation)
Supply at site of a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . (at new receiving substation)
Supply at site of 11 kV, VCB Panel Board(12KV,1250 Amp, 25 kA for 3 sec Outdoor) with O/C,E/F Relays (IEC 61850) Mimic Diagram Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3Ph Tri vector meter 5Amp DLMS Compliant with RS-485 Port.SCADA Compatible (2 Incomer Panel +5 Outgoing Panel)
Supply at site of 11 KV XPLE Power Cables‐ Single Core 630 mm²
Supply at site of 11 KV XPLE Power Cables‐ 3C 400 mm²
Supply at site of Indoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Supply at site of Outdoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Supply at site of Supply at site of Indoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Supply at site of Outdoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Supply at site of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply at site of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply at site of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply at site of 100 KVA, 33/0.4 KV Stn. Transformer, Copper Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
Supply at site of MCCB ‐ 200 Amps (with Enclosure and pole mounting arrangement)
Supply at site of 120 mm² 3.5 Core LT XLPE Cable
Supply at site of 9 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -33(IS 2713, Pt I, II, III 1980.)
Supply at site of Rubber Mat 1mx2m 19mm thick
Supply of Helmet at site
Supply at site of Rubber Gloves for 33 kV level
Supply at site of Rubber Gloves for 11kV level
Supply at site of Safety Belt
Supply at site of Safety Shoes
Supply at site of Earthing rod (set of 3 rods)
Supply at site of HV Detectors all voltages
Supply at site of Earthing Mat (GI flat 50mm x 12mm)
Supply at site of Earthing Electrode 3m long, 40mm dia GI pipe through GI stirip 50 x6mm
Installation, testing and commissioning of 33/11kV, 10 MVA ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connectors.
Installation Testing and Commisioning of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) (Departmental Supply).
Installation Testing and Commisioning of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for 33/11KV Power Transformer Protection (SCADA Compatible)
Installation, testing and commissioning of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi-Core, Outdoor) (1 No. per Φ) (deptt supply 3 No and TKC supply 6 No)
Installation, Testing and Commisioning of 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ) (Departmental Supply).
Installation, testing and commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer/porcelain) gap less
Installation, testing and commissioning of 33 kV, 1250 A, Isolator with Earthing Blade
Installation, testing and commissioning of 33 kV, 1250 A, Isolator without Earthing Blade
Installation, testing and commissioning of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Installation, testing and commissioning of 33 kV DO Fuse, 100 Amp.
Installation, testing and commissioning of T Clamps for Panther Conductor
Installation, testing and commissioning of Single Tension Fittings for Panther Conductor
Installation, testing and commissioning of A.C Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories (for new receiving substation)
Installation, testing and commissioning of DC Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories (for new receiving substation)
Erection of Galvanised Steel Structures for 33 KV Line bay,Transformer Bay,feeder gantry, station transformer etc (8 MT Deptt supply and 8MT TKC supply)
Installation, testing and commissioning of GI flat for earthing 50x6 mm (for earthing risers at receiving substations)
Installation, testing and commissioning of Yard Lighting at new Receiving Station using 4 No 12 Mtr Long GI High Mast Poles,Continuosly tapered of Octagonal of cross Section including suitable shallow raft foundation using 8 Nos non integeral flood Light Luminaire with single piece die cast Al.housing and pot optic reflector and toughened glass cover conforming to IP-66 complete with all accessories bearing Cat No SGP 438 1XODM-TT 250Watt GLA/HPL-T 250W Philips Make and Suitable Control Feeder Panel.
Installation, testing and commissioning of Earth Wire 7/4.00 mm sq.
Installation, testing and commissioning of 11 kv Isolator Doble break 3 pole ,600A Horizontal mount type with earth switch
Installation, testing and commissioning of Fire Fighting Equipment a) Dry Chemical Powder type (6Kg) for control room:-3No. b) Co₂ Type of 4.5 kg capacity for control room:-4No c) Co₂ type trolly mounted of 22.5Kg capacity for switch yard:-2No (at new receiving substation)
Installation, testing and commissioning of a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . (at new receiving substation)
Installation, testing and commissioning of 11 kV, VCB Panel Board(12KV,1250 Amp, 25 kA for 3 sec Outdoor) with O/C,E/F Relays (IEC 61850) Mimic Diagram Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3Ph Tri vector meter 5Amp DLMS Compliant with RS-485 Port.SCADA Compatible (2 Incomer Panel +5 Outgoing Panel)
laying Testing and Commisioning of 200 sqmm ACSR Conductor (for 33 kV Line bay, 33KV bus and transformer bay) Deptt Supply
Installation, testing and commissioning of 11 KV XPLE Power Cables‐ Single Core 630 mm²
Installation, testing and commissioning of 11 KV XPLE Power Cables‐ 3C 400 mm²
Installation, testing and commissioning of Indoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Installation, testing and commissioning of Outdoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Installation, testing and commissioning of Installation, testing and commissioning of Indoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Installation, testing and commissioning of Outdoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Installation, testing and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation, testing and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation, testing and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation Testing and Commisioning of 11 kV LA Station Type (Departmental Supply).
Installation, testing and commissioning of 100 KVA, 33/0.4 KV Stn. Transformer, Copper Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
Installation, testing and commissioning of MCCB ‐ 200 Amps (with Enclosure and pole mounting arrangement)
Installation, testing and commissioning of 120 mm² 3.5 Core LT XLPE Cable
Erection of 9 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -33(IS 2713, Pt I, II, III 1980.)
Installation, testing and commissioning of Earthing Mat including risers (complete job)
Installation, testing and commissioning of Earthing Electrode 3m long, 40mm dia GI pipe through GI stirip 50 x6mm
Modification/canibalization/rfabrication of Gi items supplied by the deptt (wherever necessary)
Supply of 13 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56 at site
Supply of 11 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56(IS 2713, Pt I, II, III 1980.) at site
Supply and Painting of Red Oxide at site
Supply and Painting of Aluminium Paint at site
Supply of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip at site
Supply of PG Clamps for Panther Conductor at site
Supply of 33kV Polymer composite/Porcelain Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm at site
Supply of 33kV Polymer composite/Porcelain Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm at site
Supply of GI V cross-arm with top Bracket including clamp at site
Supply of GI Channel X-arm including clamps and braces at site
Supply of Galvanised Nuts & Bolts with washers
Supply of 33 kV Danger Plates with Clamps at site
Supply of Anti-Climbing Device (GI Barbed Wire) with Clamps
Supply of Galvanised Stay Set with 50 x 8 mm stay clamp,guy insulator (2Nos.) , anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete at site
Supply of 33 kV XLPE Single Core 630mm Sq Cable at site
Supply of 33 kV heat Shrinkable Single core Cable termination Kit (indoor/outdoor Type) at site
Dismanatling of existing 11mtr poles (loading at working site, unloading at store and transportation)
Erection of 13 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56 at site
Erection of 11 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56(IS 2713, Pt I, II, III 1980.) at site
Laying Testing and Commisioning of 150 sqmm ACSR Wolf Conductor (for 33 kV Line)
Installation,Testing and Commisioning Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip at site
Installation,Testing and Commisioning PG Clamps for Panther Conductor at site
Installation,Testing and Commisioning 33kV Polymer composite/Porcelain Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm at site
Installation,Testing and Commisioning 33kV Polymer composite/Porcelain Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm at site
Installation,Testing and Commisioning GI V cross-arm with top Bracket including clamp at site
Installation,Testing and Commisioning GI Channel X-arm including clamps and braces at site
Installation,Testing and Commisioning Galvanised Nuts & Bolts with washers
Installation,Testing and Commisioning 33 kV Danger Plates with Clamps at site
Installation,Testing and Commisioning Anti-Climbing Device (GI Barbed Wire) with Clamps
Installation,Testing and Commisioning Galvanised Stay Set with 50 x 8 mm stay clamp,guy insulator (2Nos.) , anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete at site
Cement Bottoming1:2:4 mix as per REC Standards at site
Laying,Testing and Commisioning 33 kV XLPE Single Core 630mm Sq Cable at site in trenches as per approved drawings
Installation,Testing and Commisioning 33 kV heat Shrinkable Single core Cable termination Kit (outdoor Type) at site
Dismanatling of existing 11mtr poles (loading at working site, unloading at store and transportation)
NOTE: 1. All the supplies/Erections should be as per the approved drawings. 2. Supply: All inclusive means exworks price, frieght, packaging, insurance, delivery at sites and other applied duties without GST. 3. Installation/testing/commissioning: All Inclusive means erection charges at site including pre-commisioning and final commissioning tests. 4. Intersee position of bidders shall be determined by the total package cost.
M AND COMPANY ENGINEERS AND CONTRACTORS PRIVATE LIMITED
A to Z Service Solution
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .