| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹25.8 LAccepted-AOC | L-1 | Accepted-AOC lowest bidder for the work. | |
| 2 | L-2₹27.1 L+₹1.2 L (4.79%)Rejected-Finance 1442 1 NANADANPURA BABINA CANTT TEHSIL DISTT JHANSI UP | BABINA | JHANSI | UP | L-2 | Rejected-Finance other than the lowest bidder | |
| 3 | L-3₹28.4 L+₹2.6 L (10.1%)Rejected-Finance | L-3 | Rejected-Finance other than the lowest bidder | |
| 4 | L-4₹28.9 L+₹3.1 L (11.9%)Rejected-Finance | L-4 | Rejected-Finance other than the lowest bidder | |
| 5 | L-5₹29.0 L+₹3.2 L (12.3%)Rejected-Finance | L-5 | Rejected-Finance other than the lowest bidder |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
31 Jul 2023, 6:00 pmClosed
Mr Bharat Singh Laspal, SE, CWE Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
PROVISION OF 100 KVA TRANSFORMER AND ALLIED WORKS AT MH NASIRABAD AND UPGRADATION OF EXISTING 100 KVA TRANSFORMER TO 160 KVA TRANSFORMER AT NASIRABAD MIL STN UNDER GE NASIRABAD
2023_MES_597775_2
83843/E8
Open Tender
Civil Works
Item Rate
180 days
NASIRABAD
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
Yes
GE NASIRABAD
₹56,000
Yes
18 Sept 2023
11 Jul 2023
2 Aug 2023
11 Jul 2023
31 Jul 2023
18 Jul 2023
11 Jul 2023 - 18 Jul 2023
Amount
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
S & F XLPE cable end termination, cold shrinkable, outdoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
S & F gang operated air break switch as per IEC 62271-103 amended upto date, rocking/ tilting type, suitable for both horizontal and vertical mounting, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated frequency 50 Hz, continuous current rating 200 Amps, rated short time withstand current for three seconds 16 kA, rated peak withstand current for three seconds 40 kA, rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), minimum isolating distance in open position 310 mm, phase to phase clearance 750 mm, minimum cross sectional area of fixed contact 300 sqmm, minimum cross sectional area of moving contact 250 sqmm, copper connector having minimum cross sectional area of 250 sqm, maximum current density of 1.6 Amps/ sqmm for all current carrying parts, single number of brake per phase, medium grade galvanised iron pipe of 32 mm nominal bore and 5 to 6 metre length in single piece for operating pipe, pad-locking in both ‘on’ and ‘off’ positions with indicators, electroplated nonferrous parts, hot dip galvanised ferrous parts, 3 Nos polymer post insulator per phase as per IEC 61109 amended upto date having rated voltage 12 kV, minimum creepage distance 300 mm, impulse withstand voltage 75 kV, wet power frequency withstand voltage 35 kV, dry wet power frequency withstand voltage 35 kV complete all as specified and as directed.
Supply and fix metal oxide surge arrester without gap for AC system as per IEC 60099-4: 2014, outdoor type, polymer housing, single column and single phase construction, distribution class, heavy duty, nominal discharge current 10 kA, repetitive charge transfer rating (Qrs) more than 0.4 C, thermal charge transfer rating (Qth) more than 1.1 C, nominal system voltage 11 kV, highest system voltage 12 kV, rated voltage of arrester 9 kV, continuous operating voltage 7.2 kV, temporary overvoltage (10.50 kV for 1 s, 9.90 kV for 10 s, 9.35 kV for 100 s), rated short circuit current 20 kA, low short circuit current 600 A, insulation withstand level (lightning impulse voltage 1.2/ 50 µs) 75 kV, lightning impulse residual voltage (8/20 µs) at nominal discharge current maximum 30 kV, high current impulse withstand capability (4/10 µs) 100 kA, minimum creepage distance 300 mm complete all as specified and as directed.
Supplying, installing, connecting, testing & commissioning mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 100 kVA rating, non-sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30⁰ positive phase displacement, off circuit tap changing arrangement for voltage variations of +2.5% to -5% in steps of 2.5% for variation of HV, minimum energy efficiency level 2 (Star 2 as per the notification issued by the Central Government, in consultation with the Bureau of Energy Efficiency and including all the amendments issued up-to-date), 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 including amendment upto and including amendment No. 4 dated 04 Mar 2021 complete with all fittings, accessories and item as specified and as directed. Note: - The energy efficiency level higher than the minimum energy efficiency level as specified here shall be provided without any extra cost in case the transformer of minimum energy efficiency level is not available.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and as directed.
Supply & laying unreinforced precast concrete cable cover class HVP type 1, with peak shape, dimension 300 mm X 180 mm X 40 mm and 65 mm peak thickness as per IS 5820: 1970 complete all as specified and as directed.
Supply & laying unreinforced precast concrete cable cover class LV type 1, flat shape, dimension 250 mm X 150 mm X 40 mm as per IS 5820: 1970 complete all as specified and as directed.
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling, hand punning down complete all as specified and as directed. Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
S & F 11 kV polymeric composite pin insulator, conforming to IEC 61109, material of core (FRP rod): borron free ECR, material of sheds: silicon rubber, material of top end fittings: spheroidal graphite cast iron, malleable cast iron or forged steel, material of bottom end fittings: forged steel, sealing compound for end fitting: RTV Silicon, colour of sheds: grey, rated voltage: 11 kV, highest voltage: 12 kV, dry power frequency withstand voltage: 60 kV, wet power frequency withstand voltage: 35 kV, dry power frequency flashover voltage: 75 kV, wet power frequency flashover voltage: 45 kV, dry lightning impulse withstand voltage: (a) Positive: 75 kV, (b) Negative: 80 kV, dry lightning impulse flashover voltage: (a) Positive: 95 kV, (b) Negative: 100 kV, RIV at 1 MHz when energised at 10 kV / 30 kV (rms) under dry condition < 50 microvolt, creepage distance (minium): 300 mm, minimum failing load: 5 kN complete all as specified and as directed.
S & F 11 kV polymeric composite disc insulator, conforming to IEC 61109, material of core (FRP rod): borron free ECR, material of sheds: silicon rubber, material of end fittings: spheroidal graphite cast iron, malleable cast iron or forged steel, sealing compound for end fitting: RTV Silicon, colour of sheds: grey, rated voltage: 11 kV, highest voltage: 12 kV, dry power frequency withstand voltage: 60 kV, wet power frequency withstand voltage: 35 kV, dry power frequency flashover voltage: 75 kV, wet power frequency flashover voltage: 45 kV, dry lightning impulse withstand voltage: (a) Positive: 75 kV, (b) Negative: 80 kV, dry lightning impulse flashover voltage: (a) Positive: 95 kV, (b) Negative: 100 kV, RIV at 1 MHz when energised at 10 kV / 30 kV (rms) under dry condition < 50 microvolt, creepage distance (minium): 300 mm, minimum failing load: 45 kN complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
M & L for cement concrete M10 (Nominal Mix) using 40 mm nominal size graded crushed stone aggregate 100 mm thick in sub base for laying tiles, pavings etc. complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm galvanised mild steel strip complete all as specified and as directed.
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Supplying, installing, connecting, testing & commissioning mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 160 kVA rating, non-sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30⁰ positive phase displacement, off circuit tap changing arrangement for voltage variations of +2.5% to -5% in steps of 2.5% for variation of HV, minimum energy efficiency level 2 (Star 2 as per the notification issued by the Central Government, in consultation with the Bureau of Energy Efficiency and including all the amendments issued up-to-date), 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 including amendment upto and including amendment No. 4 dated 04 Mar 2021 complete with all fittings, accessories and item as specified and as directed. Note: - The energy efficiency level higher than the minimum energy efficiency level as specified here shall be provided without any extra cost in case the transformer of minimum energy efficiency level is not available.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 70 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
M & L for laying of bricks locally available sub class 'B' bricks, non-modular sizes as per IS 1077: 1992 for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Supply and fix in repairs metal oxide surge arrester without gap for AC system as per IEC 60099-4: 2014, outdoor type, polymer housing, single column and single phase construction, distribution class, heavy duty, nominal discharge current 10 kA, repetitive charge transfer rating (Qrs) more than 0.4 C, thermal charge transfer rating (Qth) more than 1.1 C, nominal system voltage 11 kV, highest system voltage 12 kV, rated voltage of arrester 9 kV, continuous operating voltage 7.2 kV, temporary overvoltage (10.50 kV for 1 s, 9.90 kV for 10 s, 9.35 kV for 100 s), rated short circuit current 20 kA, low short circuit current 600 A, insulation withstand level (lightning impulse voltage 1.2/ 50 µs) 75 kV, lightning impulse residual voltage (8/20 µs) at nominal discharge current maximum 30 kV, high current impulse withstand capability (4/10 µs) 100 kA, minimum creepage distance 300 mm complete all as specified and as directed.
M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine for insertion of GI/CI/PP-R/PVC pipe of any dia/ bore/size complete all as specified and as directed.
M & L for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. complete all as specified and as directed.
Taking down cement plaster on stone/brick/concrete surfaces including racking out joint, hacking for key, scrubbing down with water complete all as specified and as directed.
M & L for brick work with fly ash bricks of class designation 7.5 and non-modular size as per IS 12894: 2002, straight or curved on plan exceeding 6 m mean radius built in cement mortar 1:6 complete all as specified and as directed.
Material and labour for plastering 15 mm thick on fair faces of brick work or concrete surfaces (on vertical surfaces) in cement mortar 1:4 finished even and fair complete all as specified and as directed.
Excavating in post holes (or similar holes) each not exceeding 0.5 cum, getting out in soft/ loose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance not exceeding 50 m and making good surface complete all as specified and as directed.
S & F hot rolled low tensile structural steel of grade E165 as per IS 15911: 2010 as in hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar works complete all as specified and as directed.
Supply only galvanized steel chain link fence fabric of any mesh size and made out of any nominal dia of mesh wire.
Fixing only galvanized steel chain link fence fencing including line wires any mesh, size and type to any type of standards, rails, straining bolts, etc. including provn of binding wire complete all as specified and as directed.
S & F 3.15 mm size mild steel wire as per IS 280: 2006, galvanised coated conforming to the requirement of medium coated as per IS 4826: 1979 or 12753: 1989, in fencing including straining and fixing to wood, concrete or steel posts and/or to straining bolts, including securing with and provision of galvanised iron tying wire, galvanised iron staples or steel pins, complete all as specified and as directed (each line of wire shall be measured be measured).
S & F mild steel screw bolts (machine made), diameter of neck 5 to 10 mm with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exceeding 5 cm but not exceeding 10 cm long complete all as specified and as directed.
Preparation of newly or previously untreated steel surface of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed by Engineer-in-Charge
M & L for preparation of new surfaces of any description wood, steel, iron, concrete, brick, stone, etc., exceeding 10 cm in width or girth and applying one coat of black bituminous paint complete all as specified and as directed.
S & F hot rolled medium and high tensile structural steel of grade E 250 quality C conforming to IS 2062: 2011 as in framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 40 mm nominal size graded crushed stone aggregate 150 mm thick in flooring finished even and fair complete all as specified and as directed.
M & L for preparation of new plaster surface of wall and applying two coats of cement base paint complete all as specified and as directed.
Disconnecting all existing connection with transfomer and taking down and shifting transformer from any substation under the GE to AGE E/M store yard with help of Hydra (Recovery)/JCB/ Crane etc. complete all as specified and as directed.
M/S SHIVA TRADERS
S.G.ENGINEERING COMPANY
M/s SUNIL ENTERPRISES
KIRTIMAN ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .