Office of Executive Engineer TLMD-V JKPTCL, Jammu
Executive Engineer, TLMD-V, JKPTCL, Ambedkar Chowk, Jammu
SITC OF 220V AND 110V BATTERY BANK AND BATTERY CHARGER AT 320 MVA, 220/132/66 KV GRID STATION HIRANAGAR AND 220V BATTERY BANK AND BATTERY CHARGER AT 160 MVA, 220/66 KV GRID STATION GHATTI
2026_PDD_312896_1
TLMD-V/J/01of2026-27 Dated 18-06-2026
Open Tender
Electrical Works
180 days
Hiranagar
AS PER NIT AND SBD
2 documents required · 2 mandatory
₹2,360
Executive Engineer TLMD-V JKPTCL, Jammu
₹1.6 L
Office of Executive Engineer TLMD-V JKPTCL, Jammu
18 Jun 2026
18 Jun 2026
11 Jul 2026
19 Jun 2026
9 Jul 2026
19 Jun 2026
19 Jun 2026 - 25 Jun 2026
25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1(A) Supply Part | |||||
| 1.01 | Battery Bank 220 V,300 AH , of 110 No. cells of 2 V each, sealed maintenance free VRLA type,High
impact Polyprophelene copolymer container,flame
retardant. | 1 | Set | - | - |
| 1.02 | Battery Bank 110 V,300 AH , of 55 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. | 1 | Set | - | - |
| 1.03 | Battery Bank 220 V,600 AH , of 110 No. cells of 2 V each, sealed maintenance free VRLA type,High
impact Polyprophelene copolymer container,flame
retardant. | 1 | Set | - | - |
| 1.04 | 220 V Battery charger (Three phase):(i) Float
charging and load current ratings:30 Amp / 60Amp / 70Amp / 100Amp at 220 V to 252 V D.C.(ii) Boost charging current rating:50 Amps / 55Amp / 60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C | 2 | No | - | - |
| 1.05 | 110 V Battery charger (Three phase):
(i) Float charging and load current ratings: 30 Amp / 60Amp / 70Amp / 100Amp at 220 V to 252 V D.C. (ii) Boost charging current rating: 50 Amps / 55Amp / 60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C | 1 | No | - | - |
| 1.06 | 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete | 165 | Mtr | - | - |
| 2(B) Erection Part | |||||
| 2.01 | Battery Bank 220 V,300 AH , of 110 No. cells of 2 V each, sealed maintenance free VRLA type,High
impact Polyprophelene copolymer container,flame
retardant. | 1 | Set | - | - |
| 2.02 | Battery Bank 110 V,300 AH , of 55 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. | 1 | Set | - | - |