Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Eligibility Credentials are not as per NIT |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-TENDER SALE AND EMD NOT SUBMITTED OFFLINE IN PHYSICAL FORM |
Tender Value
Refer Docs
EMD Value
₹28,017
Closing Date
31 Mar 2023, 12:00 pmClosed
EXECUTIVE ENGINEER (ELECTRICAL)
BSNL ELECTRICAL DIVISION-I, EASTERN COURT, JANPATH, NEW DELHI-110001
SITC of 3.75 TR Standalone Floor Standing Tower type Split AC Units and associated works in 9th Floor Conference Hall at Bharat Sanchar Bhawan, Janpath, New Delhi
2023_BSNL_150250_1
82/NIT/E-Tender/2022-23/ED-I
Open Tender
Electrical Works
Item Rate
7 days
NEW DELHI
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
AO (CASH), O/O CGM, BSNL, NTR, NEW DELHI
₹28,017
1 Apr 2023
25 Mar 2023
1 Apr 2023
25 Mar 2023
31 Mar 2023
25 Mar 2023
Supply of 3.75 TR capacity Standalone Floor standing Tower type Split AC unit having cooling capacity not less than 45000 BTU/Hr complete with all accessories such as floor mounted Standalone (TOWER) type indoor unit with Auto Swing Digital control display, Self-Diagnosis Function, Moisture Removal Dry Mode, Remote control unit, anti-vibration pads etc., Outdoor unit with scroll compressor suitable for operation on 415 Volts ± 10%, 3 Phase, 50Hz A.C. supply, operating refrigerant R-410A etc. complete as per specifications including cartage, loading/unloading etc. complete as required. The offered product should be of reputed make and OEM manufacturing Tower type AC units more than 10 (Ten) years. A certificate regarding this has to be submitted with bid. During Installation of ACs, firm may depute its engineer for correct installation.
ITC of existing 3.75 TR capacity tower type Split AC unit including shifting charges for shifting of indoor & outdoor unit from ground floor to 9th floor, mounting/ fitting of indoor and outdoor units at proper locations, suitable electrical connection / wiring etc., minor civil work etc. complete as required. The work includes fixing of the Indoor Unit on the existing wooden floor by using anti vibration pads so that vibration will not transfer from the unit to the wooden floor.
Supplying and fixing of pre-fabricated MS mounting adjustable frame suitable to withstand the weight (Approximately 98 Kg) & vibrations of outdoor unit, duly phosphatized and powder coated etc., complete as required.
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for AC system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
9.5 mm dia. (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia. (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Providing and fixing rigid uPVC piping complete with fittings, supports as per OEM Standards.
40 mm dia.
25 mm dia.
Supplying and fixing of following sizes XLPE insulated PVC sheathed copper conductor armoured cable of 1.1 KV grade on the existing surface/ cable trays, saddling, making hole in the wall wherever required, testing commissioning etc. complete as required.
4 x 16 sqmm
4 x 6 sqmm
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.
4 x 16 sqmm
4 x 6 sqmm
Supplying and laying 6 x 6 sqmm PVC insulated PVC sheathed copper conductor flexible cable of 1.1 KV grade i/c testing, commissioning etc. complete , as required.
Supplying and fixing of 4 way (4 + 12), Double door surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .
Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for 4 way, Double door triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.
Supplying and fixing 63 Amps. rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of 32 Amp rating TP MCB 415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Note:- 1. The GST / other Input Tax Credit (ITC) taxes shall be quoted by the firm as applicable as per latest amendments of GST Rules. 2. The contractor shall provide correct tariff heads & other details to enable BSNL claim Input Tax Credit. 3. Servicing Scrap items will be credited to the firm. The rate may be quoted accordingly. 4. Bidder must mandatorily quote for all GST components (CGST, SGST, and IGST) as required. 5. If annual maintenance contract charges are required to be quoted as per SOW, basic charges should be shown in column 4 & the Goods and Service Tax (GST) in column 7 to 12. 6. The bidder who submits the offer with concessional Goods and Service Tax (GST) shall submit the proof of applicable concessional GST. In case the Concessional GST is not creditable to BSNL it should be included in the price of the goods/services. 7. In case, dealer is registered under compounding scheme or any rule/notification where the BSNL is not eligible for input tax credit then the bidder should not disclose any amount in column 7 to12 & 14. 8. % age Rate of FF & Packing should be shown of basic unit price excluding all taxes & charges (i.e. as %age of col.4). 9. The FF & packing amount quoted shall not be subject to change after bid evaluation /ordering on account of change of copper, lead base price, change in duties & taxes of item etc. 10. Bidder must mandatorily mention HSN & SAC numbers.15. Evaluation of bids: - The evaluation and comparison of responsive bids shall be done on the basis of Net cost to BSNL on the prices of the goods & Services (i.e. complete work) offered along with all applicable Taxes, packing Forwarding Freight & Insurance charges etc. exclusive of GST. Declaration by Bidder: 1. We hereby declare that in quoting the above prices, we have taken into account the entire credit on inputs available under the GST Act introduced w.e.f. 1 July 2017 and further extended on more items till date. 2. We hereby certify that HSN/SAC shown in column 17 are correct & credit of GST for the amount shown in column 14 above are admissible as per GST Laws. Name of bidder: Seal of Company:
STAR ELECTRIC WORKS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .