| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.4 LAccepted-AOC | ₹37.4 L Quoted ₹38.6 L | L1 | Accepted-AOC Award of Contract |
| 2 | L2₹43.6 L+₹5.0 L (13.1%)Rejected-Finance | ₹43.6 L+₹5.0 L (13.1%) | L2 | Rejected-Finance Not Being Lowest |
| Sl No | Description | Qty | Unit | Ms. S.K. ASSOCIATES L1 | M/s. NILESH SURESH KAWOOR L2 |
|---|---|---|---|---|---|
| 1.00 | Supply & fix in replacement of single pointed air termination Copper rod, 12 mm dia, 300 mm long including taking down existing copper rod complete all as specified and directed. | 20 | Each | 200 ₹4,000 | 185 ₹3,700 Lowest |
| 2.00 | Supply & fix in replacement of Copper strip 25 mm x 3 mm Complete with saddles and fixing screws on including epoxy Insulater for Fitting the strip, including taking down existing Aluminium/ Copper strip complete all as specified and directed. (Note : Rate included with Insulater) | 200 | RM | 650 ₹1,30,000 | 610 ₹1,22,000 Lowest |
| 3.00 | Supply & install in replacement of GI strip 32 mm x 6 mm buried ground/ floor/ surface/ roof with saddle and fixing screws including taking doown existing GI Strip complete all as specified and directed | 410 | RM | 200 ₹82,000 Lowest | 200 ₹82,000 Lowest |
| 4.00 | M&L for REPLACEMENT of earthing with galvanised earth plate 60x60 cm x 6 mm thick electrode of size and 32 x 6mm GI strip buried vertically in ground not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level and connected to copper strip dia by means of nuts, bolts and washers and encased in and including 40mm dia GI medium grade pipe upt 2.4 mtr height form ground level fixed by MS flat iron clamp 40mm x 5mm with nut, bolt and washers, GI strip fixed to base along pole and connected to over head line for providing earthing to HT pole/feeder AB switch LA complete with charcoal dust, salt packed around plate 150 mm thick including watering GI pipe, medium grade 20 mm dia with blanking cap 1.5 mtr long fixed to funnel with wiremesh complete with PCC chamber and RCC chamber over all as per Electrical Plate No 3 of SSR Part I - 2009 incl excavation and earth work in any type of starta and testing on compeltion etc complete all as specified and directed by Engineer-in-Charge
Note :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required
(iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself. | 70 | Each | 6,000 ₹4,20,000 Lowest | 7,000 ₹4,90,000 |
| 5.00 | M&L for earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick, buried vertically in ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to copper strip 20 x 3 mm, by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 40 mm dia light grade pipe for protection of earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2009 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion complete all as specified and directed.
Note:- i) Cost of GI strip 32 x 6 mm and protection pipe 40 mm dia is deemmed to be included in rate quoted
ii) Excavation and earthwork of Soil any type is deemed to be included in rates. | 31 | Each | 12,000 ₹3,72,000 Lowest | 15,000 ₹4,65,000 |
| 6.00 | M&L for replacement of earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 25 x4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed.
Note No 1 :- The unit rate shall also include for excavation & earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I.
Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required
(iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself. | 49 | Each | 6,000 ₹2,94,000 Lowest | 7,010 ₹3,43,490 |
| 7.00 | M&L for replacement of earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI wire 4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed.
Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I.
Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required
(iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself. | 48 | Each Set | 6,000 ₹2,88,000 Lowest | 6,000 ₹2,88,000 Lowest |
| 8.00 | M&L for replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex. head screw etc including Taking down existing complete all as specified and directed by Engineer-in-Charge. | 11 | Each | 675 ₹7,425 | 650 ₹7,150 Lowest |
| 9.00 | Disconnecting burnt out compressor from existing electric and pipe line connections of Refrigerator of capacity 165 / 175 / 210 litres of any make / location, transporting and replacing the same with New compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging complete all as specified and as directed, as per existing make | 4 | Each Job | 3,000 ₹12,000 Lowest | 3,500 ₹14,000 |
| 10.00 | ditto all as per ser item No. 9 above but Refrigerator of capacity 286 / 300 / 310 litres complete all as specified and directed | 6 | Each Job | 3,500 ₹21,000 Lowest | 3,500 ₹21,000 Lowest |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
13 Nov 2025, 6:00 pmClosed
Garrison Engineer (North) Ahilyanagar
Military Engineer Services Garrison Engineers (North) Nagar Pathardi Road Ahmednagar Fort Ahilyanagar 414 002
REPAIR/ MAINT OF LIGHTENING ARRESTER, EARTHING AND CONNECTED ITEMS AND REPAIRS/ MAINT CENTRAL PLANT, COLD STORAGE NO. 1 AND 2 AT MH, DESERT COOLER, DEEP FREEZERS, VOLTAGE STABILISERS, WINDOW SPLIT ACs, REFRIGERATOR AND WATER AT ACCS UNDER GE NORTH
2025_MES_723103_2
8111/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Garrison Engineer (North) Ahilyanagar
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
Garrison Engineers (North) Ahilyanagar
₹84,000
Yes
31 Dec 2025
29 Oct 2025
15 Nov 2025
29 Oct 2025
13 Nov 2025
6 Nov 2025
Amount
Supply & fix in replacement of single pointed air termination Copper rod, 12 mm dia, 300 mm long including taking down existing copper rod complete all as specified and directed.
Supply & fix in replacement of Copper strip 25 mm x 3 mm Complete with saddles and fixing screws on including epoxy Insulater for Fitting the strip, including taking down existing Aluminium/ Copper strip complete all as specified and directed. (Note : Rate included with Insulater)
Supply & install in replacement of GI strip 32 mm x 6 mm buried ground/ floor/ surface/ roof with saddle and fixing screws including taking doown existing GI Strip complete all as specified and directed
M&L for REPLACEMENT of earthing with galvanised earth plate 60x60 cm x 6 mm thick electrode of size and 32 x 6mm GI strip buried vertically in ground not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level and connected to copper strip dia by means of nuts, bolts and washers and encased in and including 40mm dia GI medium grade pipe upt 2.4 mtr height form ground level fixed by MS flat iron clamp 40mm x 5mm with nut, bolt and washers, GI strip fixed to base along pole and connected to over head line for providing earthing to HT pole/feeder AB switch LA complete with charcoal dust, salt packed around plate 150 mm thick including watering GI pipe, medium grade 20 mm dia with blanking cap 1.5 mtr long fixed to funnel with wiremesh complete with PCC chamber and RCC chamber over all as per Electrical Plate No 3 of SSR Part I - 2009 incl excavation and earth work in any type of starta and testing on compeltion etc complete all as specified and directed by Engineer-in-Charge Note :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
M&L for earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick, buried vertically in ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to copper strip 20 x 3 mm, by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 40 mm dia light grade pipe for protection of earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2009 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion complete all as specified and directed. Note:- i) Cost of GI strip 32 x 6 mm and protection pipe 40 mm dia is deemmed to be included in rate quoted ii) Excavation and earthwork of Soil any type is deemed to be included in rates.
M&L for replacement of earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 25 x4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for excavation & earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
M&L for replacement of earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI wire 4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
M&L for replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex. head screw etc including Taking down existing complete all as specified and directed by Engineer-in-Charge.
Disconnecting burnt out compressor from existing electric and pipe line connections of Refrigerator of capacity 165 / 175 / 210 litres of any make / location, transporting and replacing the same with New compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging complete all as specified and as directed, as per existing make
ditto all as per ser item No. 9 above but Refrigerator of capacity 286 / 300 / 310 litres complete all as specified and directed
ditto all as per ser item No. 9 above but Water cooler of capacity 40 / 80 litres complete all as specified and directed
ditto all as per ser item No. 9 above but Deep freezer of capacity 205 to 310 litres complete all as specified and directed
ditto all as per ser item No. 9 above but Window / Split type AC of capacity 1.5 TR complete all as specified and directed
ditto all as per ser item No. 9 above but Window / Split type AC of capacity 2TR complete all as specified and directed
ditto all as per ser item No. 9 above but Cassette type AC of capacity 4TR complete all as specified and directed
Taking Down fan motor / condensor motor and replacing the same with new fan / condensor motor of Copper winding 230 Volts, 50 Hz, SP suitable for water cooler of capacity 40 / 80, 60 / 120 and 60 / 150 litres including connecting and testing complete all as specified and as directed.
ditto all as per ser item No.16 above but of 230 Volts, 50 Hz, SP suitable for frost free refrigerator of capacity 286 / 300 / 310 litres complete all as specified and directed
ditto all as per ser item No. 16 above but suitable for split type AC out door unit of capacity 1.5 / 2 TR complete all as specified and directed
ditto all as per ser item No. 16 above but for split type AC in door unit 1.5/2 TR capacity complete all as specified and directed
ditto all as per ser item No. 16 above but of 230 Volts, 50 Hz, SP suitable for deep freezer of capacity 205 to 310 ltrs cap complete all as specified and directed
Supply and charging only refrigerent gas of required HD i.e hydrocarbon, R134a, R 32 ,R-22 , R-600 , R-290 or R-410A or any latest version for Refrigerators of capacity 165 to 310 ltr capacity including cutting copper pipe and sealing by brazing etc and Repalcement of Capillary tube & filter as required and leak testing complete all as specified and as directed.
ditto all as per ser item No. 21 above but for Water coolers 40 / 80 to 60 / 120 ltr capacity complete all as specified and directed
ditto all as per ser item No. 21 above but for Window / Split type AC of capacity 1.5 TR capacity complete all as specified and directed
ditto all as per ser item No. 21 above but for Window / Split type AC of capacity 2 TR capacity complete all as specified and directed
ditto all as per ser item No. 21 above but for Deep freezer of capacity 205 to 310 litres complete all as specified and directed
S&F running/ starter capacitor 2.5 mfd, 250 volts , AC, from cooling appliances complete all as specified and as directed.
ditto all as per ser item No. 26 above but of 10.0/15.0 mfd complete all as specified and directed
ditto all as per ser item No. 26 above but of 50.0/60.0 mfd complete all as specified and directed .
Supply and fixing in replacement thermostat suitable for window / Split type AC's, Water coolers, Refrigerators and Deep freezers of any make, capacity and model and testing complete all as specified and as directed.
Supply and fixing in replacement over load protector suitable for window/ Split type AC's, Water coolers, Refrigerators and Deep freezers of any make, capacity and model and testing complete all as specified and as directed.
Supply and fixing in replacement 15 mm dia ball valve high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed. (Minimum weight 15mm-142 gms /20 m m - 210 g m s . / 25 mm-455 gms/ 40 mm- 690 gms) from water cooler of any capacity, make, location etc including connecting and testing complete all as specified and as directed.
Supply and fixing in replacement Push cock, 15 mm dia, brass cromium plated ( SS 304 ) self closing type complete all as specified and directed
Supply and fixing in replacement 15 mm dia Stop valves, brass,chromium plated screwed down, high pressure,with crutch or butterfly handle, screwed both ends for iron pipe or for unions complete all as specified and directed
Supply and fixing in replacement Stainless steel SS 304 water drain out tray for water cooler suitable for any make complete all as specified and directed
Supply and fixing in replacement PVC connection 600 mm long with brass ends terminals suitable for water coolers complete all as specified and as directed.
Supply and fixing in replacement PVC pipe 32 mm dia for draining out waste water complete all as specified and as directed.
Supply and fixing in replacement Fan blade set for water cooler fan motor complete all as specified and directed
Supply and fixing in replacement Door light switch assembly of refrigerators of any model, type, size and capacity to suit the existing including connecting and testing complete all as specified and as directed.
Supply and fixing in replacement Lamp electric 230 vots, 50 Hz, 15 Watt, pin / threaded type of refrigerators of any model, type, size and capacity to suit the existing including testing complete all as specified and as directed.
Supply and fixing in replacement Lamp holder of refrigerators of any model, type, size and capacity to suit the existing including testing complete all as specified and as directed.
Supply and fixing in replacement Timer for refrigerator of existing specifications of any model, type, size and capacity including testing complete all as specified and as directed.
Supply and fixing in replacement Bimetal/Heater for frost free refrigerator of any model, type, size and capacity including testing complete all as specified and as directed.
Supply and fixing in replacement Magnetic rubber gasket for refrigerator door of capacity 165 to 310 litres , of any model, type, size and capacity to suit the existing including connecting and testing complete all as specified and as directed.
Supply and fixing in replacement Copper tube 1/2" size for refrigerator, Split AC's of any model, type, size and capacity to suit the existing including connecting and testing complete all as specified and as directed.
ditto all as per ser item No 44 above but of size 1/4"
ditto all as per ser item No 44 above but of size 3/8"
ditto all as per ser item No 44 above but of size 5/8"
Supply and fixing in replacement Freezer box/Evaporative cooling coil for refrigerator of capacity 165 to 310 litres of any model, type, size and capacity including testing complete all as specified and as directed.
Supply and fixing in replacement Condensing coil for refrigerator of capacity 165 to 310 litres of any model, type, size and capacity including testing complete all as specified and as directed.
S&F Plug top 3 pin, 230 Volts, 6 Amps including testing complete all as specified and as directed. Make : Anchor, Havells, Legrand
S&F Plug top 3 pin, 230 Volts, 16 Amps including testing complete all as specified and as directed. Make : Anchor , Havells, Legrands
Supply and fixing in replacement Air filter PVC type of existing window / split type air conditioners of capacity 1.5 / 2 TR,from any position, of any make including testing complete all as specified and directed.
Supply and fixing in replacement Fan blade of existing window / split type air conditioners of capacity 1.5 / 2 TR,from any position, of any make including testing complete all as specified and as directed.
Supply and fixing in replacement MCB,SP,32 Amps 230/240 Volts,50 Hz for existing window / split type air conditioners including testing complete all as specified and directed.
Supply and fixing in replacement Sheet metal enclosure with 3 pin metal clad socket 32 Amps with metal clad plug top including 1 No MCB, SP of capacity 32 Amps for existing window / split type air conditioners ,from any position, of any make including testing complete all as specified and as directed.
Supply and fixing in replacement PVC insulated cable 3 core 2.5 Sq mm, 1100 Volts grade copper conductor, multistranded including testing complete all as specified and directed.
Supply and fixing in replacement PVC insulated cable 3 core copper conductor 1100 Volts grade 1.5 Sq mm for desert coolers including testing complete all as specified and as directed.
Supply and fixing in replacement Fan blade of existing Desert Cooler from any position, of any make including testing complete all as specified and as directed.
Supply and fixing in replacement Heatlion insulation pipe for wrapping copper tape duly fixed with polythelene type to suction and discharge lines for existing window / split type air conditioners 1.5 / 2 TR,from any position, of any make including testing complete all as specified and directed
Supply and fixing in replacement PCB Kit of existing window / split type air conditioners of capacity 1.5 / 2 TR from any position, of any make including testing complete all as specified and as directed.
Supply and fixing in replacement PVC flexible pipe 15 mm dia for desert coolers complete all as specified and directed
Supply and fixing in replacement PVC pipe 15 mm dia with all fittings of existing window / split type air conditioners of capacity 1.5 / 2 TR,from any position, of any make including testing complete all as specified and directed
Supply and fixing in replacement Khus Khus pads/Ultra cool pads of suitable size to dessert cooler of capacity 3000 to 6000 CFM complete all as specified and as directed.
Supply and fixing in replacement Fan motor of copper winding 230 Volts, 50 Hz, SP for desert cooler of any capacity,from any position, of any make including testing complete all as specified and directed Make : Signature , Modi, USHA
Supply and fixing in replacement Water pump, 230 Volts, 50 Hz, SP with discharge head of 1.87 m for desert cooler of any capacity complete all as specified and as directed.
Taking down/out the fan motor from Desert coolers of any make, size,model and capacity, transporting to work shop, opening up, cleaning, taking out burnt winding etc , and rewinding of motor with superior quality of enamelled copper wire of same guage, re-assembling including over hauling of parts and fixing back the motor at the same or desired position including testing and making necessary connections to make it functional complete all as specified and as directed.
ditto all as per ser item No 66 above but of Window / Split type AC motors of capacity 1.5 / 2 TR
Taking down/out window / split type AC 1.5 / 2 TR capacity of any make,from existing postion, transporting and refixing at the new location including making necessary connections to make it functional complete all as specified and directed Note : Gas charging and/or parts if regd shall be measured and paid separetely.
Taking down/out Cassette AC 4 TR capacity of any make,from existing postion, transporting and refixing at the new location including making necessary connections to make it functional complete all as specified and directed Note : Gas charging and/or parts if regd shall be measured and paid separetely.
Taking down/out from existing position Split AC of capacity 1.5 / 2 TR , servicing the same by cleaning, dusting with blower, checking wiring, nuts, bolts, electrical contacts, tightening all loosend parts as required, setting grills and fan blades for proper functioning, oiling, greasing to moving parts and refixing to its original position and testing for smooth functioning complete all as specified and as directed.
M&L for preparing the surfaces by scrapping out the old paint and painting with one coat of painting of existing quality paint to Water cooler of capacity 40 / 80, 60 / 120 and 60 / 150 litres by spray painting complete all as specified and directed
ditto all as per ser item No 71 above but to Desert cooler of capacity 3000 / 4000 Cum per hour
Rewinding of voltage stabilizer for automatic opration single phase naturally air cooled indoor type and desinged for input variation b/t 170 v to 280 v with output voltage stabilized at 230 v with accuracy of + 2.5 % and of capacity 4 / 5 KVA
ditto all as per ser item No 73 above but of capacity 1.0 KVA to 2.0 KVA
Supply and Fix remote / control kit / electronic card of window / split AC including taking down/out electronic card / control kit including refixing back at site after repair & testing complete all as specified and as directed.
S&F sub main wiring with two single core PVC insulated, unsheathed,FRLS stranded copper conductor cable 3 core with 4 Sqmm PVC insulated, unsheathed,FRLS stranded copper conductor cable as earth wire drawn through in and incl PVC casing and caping ISI marked with all necessary accessories and earth wire connected to common earth dolly etc complete all as specified and directed by Engineer-in-Charge. Note: 1.proper colour coding shall be adopted for wiring (For phase-Red,Yellow, Blue, For Earth-Green for Neutral-Black) Note: Two run of 4 sqmm cable i.e for one run for phase, one run for neutral with one run of 4 sqmm cable for earth and one run of PVC casing & caping Shall be measured as one unit.
Supply and fixing in replacement New indoor unit for split AC 1.5 Ton capacity of suitable for existing out door unit fixing at any position, of any make including testing complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement New indoor unit for split AC 2.0 Ton capacity of suitable for existing out door unit fixing at any position, of any make including testing complete all as specified and directed by Engr-in-charge.
M&L for Opening of water cooler body by opening nut bolts and stain less steel body and Detecting gas leakage of condensing, evoparative coils, body leakages and replacing new cooling coil and necessary insulation, rectifying/ arresting the leakages, testing for pressure drop and refixing same as it complete all as specified and as directed by Engr-in-charge.
Supply and fixing of mild steel tray for Desert coolers, with new mild steel sheet, 1.6 mm thick including cutting to shape required,fabricating to size and shape by welding / brazing etc to functional and spray painting to match with the existing surfaces including making necessary connections complete all as specified and as directed.
Supply and fixing in replacement New outdoor unit for split AC 1.5 Ton capacity of suitable for existing indoor unit fixing at any position, of any make including 1.5 Ton Compressor including testing complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement New outdoor unit for split AC 2.0 Ton capacity of suitable for existing indoor unit fixing at any position, of any make including 2.0 Ton Compressor including testing complete all as specified and directed by Engr-in-charge.
Supply & fix in Repair of relay of 5.0 Amp in voltage stabilizer 0.5 KVA to 1.0 KVA including testing complete all as specified and directed by Engr-in-charge.
Supply & fix in Repair of relay of 10 Amp in voltage stabilizer 4 KVA / 5 KVA including testing complete all as specified and directed by Engr-in-charge.
Replacement of Power supply and control card kit complete for 0.5 to 2 KVA Voltage Stabilizer including testing complete all as specified and directed by Engr-in-charge.
Overhauling & Vaccumising of complete system of central AC plant capacity 25 TR with vaccum pump, descanning the refrigerent in suitable container with suitable precautions, isolating the reciprocating compressor by removing nuts and blocking plates of suction and discharge valves, opening compressor, removing the crankshaft & checking it, grinding of the crankshaft & for suitable size of bearing, replacement of unserviceable/ damaged internal parts reassembling complete and leakage testing with and including nirogen gas arresting the leakage, charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only the following parts of central air conditioning palnt of 25 TR capacity Make : Kirloskar, Model - AC 470 :-
(a) Gasket set
(b) Shaft seal assembly
(c) `O' Ring set
(d) Oil filter
(e) Main bush bearing
(f) Suction reeds
(g) oil pressure regulator
(h) Discharge reeds
(i) brass nozzel 3/4'' inches as per existing
(j) oil pressure cut out make:danfos
(k) pressure gauge (low / high / o )
(l) liquid indicator
(m) solenoid valve
(n) Piston Ring
(o) Oil Pump
(p) Connecting Bearing
(q) compressor oil of model RL-32
Descaling of condensor of 25 TR capacity central type AC plant by mechanical and chemical method till removal of scales completely including replacement of gasket and worn out nuts bolts complete all as directed.
Overhauling the cooling tower by scraping out algae scale formed or material deposited in bottom tank on fins nozzles etc by mechanical and chemical method complete including supply and fix M-Seal at leakage point all as directed.
Supply & Charge R-22 or existing type gas to AC plant upto required pressure all as directed.
Overhauling & Vaccumising of complete system of Package AC plant of capacity 11 TR at KK range areawith pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only the following unserviceable accessories of complete package type AC plant of capacity 11TR at kk range area including connecting testing complete all as directed:-
(a) anti vibrational mountings
(b) brass pressure valve 1/2 inches
(c) filter drier
(d) out door unit condencing coil
(e) out door unit condencing motor 1.5 HP 3 phase 415 Volts Cat No-1SEOO90-2NB70
(f) out door unit condencing motor's fan blade
(g) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(h) copper tubes 5/8'' 1/2'' as per existing
(j) solenoid valve
(k) Cooling coil
(l) fan motor belt as per existing
(m) 4 core 4 sq mm cable
(n) compressor heater
M&L for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of PACKAGE AC plant of capacity 11 TR at kk range including connecting testing complete all as directed:-
(a) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle
(b) PVC moulded / backelite cut out with base, 32 Amps, 500 Volts
(c) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity
(d) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(e) Power contactor, 32 Amps (type 3 TA 21-11 A) TP
(f) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz
(g ) Timer switch,230 Volts, 50 Hz CAT NO-SS91270
(h) Single phase preventor 230 Volts, 50 Hz CAT NO-XM81808OOOO
Disconnecting Unserviceable compressor capacity 5.5 TR from existing electric and pipe line connections of any make, transporting and replacing the same with factory / company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed:- NOTES: 1) The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2) Gas charging will be measured and paid separately under the relevent item
M&L for cleaning with blower of air filters and micro filters, condensor coil / cooling coil and servicing of blower motor with oil grease etc of 3 to 11 TR capacity package AC plants washing of air filters with liquid soap and high pressure water till all dirt is removed all as directed.
M&L for taking out blower motor of 3 to 11 TR package type AC plant, transporting to work shop,opening the motor, taking out burnt winding, preparing motor for winding and rewidning of motor with same guage superior enamelled copper wire, replacement of bearings if required, assembling and transporting back, installing on foundation connecting and testing complete all as directed.
M&L for leak testing of package AC 3.0 to 11 TR capacity by using nitogen gas if required repairing to leakage as required by copper brazing etc and testing for pressure drop for 24 hrs complete all as directed.
Disconnecting unserviceable compressor capacity 8.75 TR from existing electric and pipe line connections of any make, transporting and replacing the same with factory / company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed:- NOTES: 1) The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2) Gas charging and nitrogen charging will be measured and paid separately under the relevent item
Overhauling & Vaccumising of complete system of Package AC plant of capacity 8.75 TR with pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil of type RL-32 and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only for replacement of the following unserviceable accessories of complete package type AC plant of capacity 8.75 TR including connecting testing complete all as directed:-
(a) PCB with digital display 230 Volts, 50 Hz
(b) brass pressure valve 1/2 inches
(c) gas filter 1/2 inches
(d) filter drier
(e) out door unit condencing coil
(f) out door unit condencing motor 2 HP 3 phase 415 Volts CAT NO- 1SE00902NB70
(g) out door unit condencing motor's fan blade
(g) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(j) copper tubes 5/8' 1/2' as per existing
(k) solenoid valve
(l) Cooling coil
(m) fan motor belt as per existing
(n) 4 core 4 sq mm cable
(o) compressor heater
(p) anti vibrational mountings
Overhauling & Vaccumising of complete system of Package AC plant of capacity 11 TR at Arjun block area with pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only for replacement of the following unserviceable accessories of complete package type AC plant of capacity 11 TR at Arjun block area including connecting testing complete all as directed:-
(a) PCB with digital display 230 Volts, 50 Hz
(b) brass pressure valve 1/2 inches
(c) gas filter 1/2 inches
(d) filter drier
(e) out door unit condencing coil
(f) out door unit condencing motor 2 HP 3 phase 415 Volts
(g) out door unit condencing motor's fan blade
(h) MCB, TPN, 32 Amps, 50 Hz, 500 Volts MAKE: LEGRAND/ HAGER/ SIEMENS Cat No-DHMGCTNFO006-032
(i) copper tubes 5/8' 1/2' as per existing
(j) solenoid valve
(k) Cooling coil
(l) fan motor belt as per existing
(m) 4 core 4 sq mm cable
(n) compressor heater
(o) anti vibrational mountings
M&L for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of PACKAGE AC plant of capacity 11 TR including connecting testing complete all as directed:-
(a) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle
(b) PVC moulded / backelite cut out with base, 32 Amps, 500 Volts
(c) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity.
(d) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(e) Rotary switch
(f) Power contactor, 32 Amps (type 3 TA 21-11 A) TP
(g) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz
(h) Timer switch,230 Volts, 50 Hz
(j) Single phase preventor 230 Volts, 50 Hz
Supply & fix ball bearing DE/NDE for 30 HP coupled pump
Supply & fix ball bearing DE/NDE for 7.5 HP coupled pump
M&L for 5 micron fine filter of size 610x610x150mm (LXBXT) made of HDPE for 25 TR central AC lant all as specified and directed by Engr-in-charge
M&L for pre filter of size 510 x 610mm made of cellulose pad for 25 TR central AC plant all as specified and directed by Engr-in-charge
Disconnecting unserviceable compressor capacity 11TR from existing electric and pipe line connections of any make,transporting and replacing the same with factory/company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed :- Notes: 1. The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2. Gas charging will be measured and paid seperately under the relevant item.
Supply and intallation of terminal insulation for the supply air ducting (to avoid condensation) with 18mm thick, closed cell elastomeric nitirile rubber insulation sheet, class-O as per BS 476 part 6, fire retardant, co-efficient of thermal conductivityK=0.037W/m.k@20 degree celsius.density 60-85 kg/Cum operating range between -40 degree celsius and +85 degree celsius complete all as specified and directed Make: Superlon/A-flex/Aeroflex/K-flex
Supply and installation testing and commissioning of galvanised steel sheet square/rectangular fabricated from galvanised steel sheet of 22 gauge thick(0.80mm having zink coating of 180gm/sqm total on both side complete with gaskets,elbows,spliters,vaens,supports etc as per IS:655/1963 (Revised upto date ) all as specified including taking down existing duct of any type. Note:- Quoted rate shall include the cost of hanging of duct with GI nuts, bolts and MS angles as required including cutting of wall and making good the distributed surfaces as required for fixing duct at site.
M/s. NILESH SURESH KAWOOR (BID ID -3472243)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
PS8111-2.pdf
Tender Documents • 1.19 MB
BOQ_825741.xls
BOQ • 0.64 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .